manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. M-system
  6. •
  7. Surge Protector
  8. •
  9. M-system MDK-24 User manual

M-system MDK-24 User manual

Other M-system Surge Protector manuals

M-system MD74R User manual

M-system

M-system MD74R User manual

M-system MDP-200T User manual

M-system

M-system MDP-200T User manual

M-system MDP-RB User manual

M-system

M-system MDP-RB User manual

M-system MDP-24T User manual

M-system

M-system MDP-24T User manual

M-system MGD-24 User manual

M-system

M-system MGD-24 User manual

M-system MDP-100 User manual

M-system

M-system MDP-100 User manual

M-system MD7PL User manual

M-system

M-system MD7PL User manual

M-system MD7LC User manual

M-system

M-system MD7LC User manual

M-system MMH-1 User manual

M-system

M-system MMH-1 User manual

M-system MD6 24 Series User manual

M-system

M-system MD6 24 Series User manual

M-system MD7LWA User manual

M-system

M-system MD7LWA User manual

M-system MDPA-24 User manual

M-system

M-system MDPA-24 User manual

M-system MDP-JS User manual

M-system

M-system MDP-JS User manual

M-system MATP User manual

M-system

M-system MATP User manual

M-system MDP-D Series User manual

M-system

M-system MDP-D Series User manual

M-system MDH User manual

M-system

M-system MDH User manual

M-system MDCAT 5E User manual

M-system

M-system MDCAT 5E User manual

M-system MD7PM User manual

M-system

M-system MD7PM User manual

M-system MGA-100 User manual

M-system

M-system MGA-100 User manual

M-system MAKN User manual

M-system

M-system MAKN User manual

M-system MDK-LC User manual

M-system

M-system MDK-LC User manual

M-system MDPA-24 User manual

M-system

M-system MDPA-24 User manual

M-system MAT2 Series User manual

M-system

M-system MAT2 Series User manual

M-system 6SN User manual

M-system

M-system 6SN User manual

Popular Surge Protector manuals by other brands

Philips Theatre Director SPP4200WA/17 Owner's manual & warranty

Philips

Philips Theatre Director SPP4200WA/17 Owner's manual & warranty

CyberPower CSP600WSU user manual

CyberPower

CyberPower CSP600WSU user manual

UTP BALUN SP-VD08 user manual

UTP BALUN

UTP BALUN SP-VD08 user manual

ELAC ProteK PR91-W Setup guide

ELAC

ELAC ProteK PR91-W Setup guide

Tsubaki TSM4000M1 instruction manual

Tsubaki

Tsubaki TSM4000M1 instruction manual

CyberPower B1006T user manual

CyberPower

CyberPower B1006T user manual

QVS PP134C Specification sheet

QVS

QVS PP134C Specification sheet

Davis Instruments Radio Surge Protector user guide

Davis Instruments

Davis Instruments Radio Surge Protector user guide

CyberPower B300WRC1 user manual

CyberPower

CyberPower B300WRC1 user manual

Panamax MAX 5400-EX owner's guide

Panamax

Panamax MAX 5400-EX owner's guide

OBO Bettermann ÜSM-20-230I1PE65 installation instructions

OBO Bettermann

OBO Bettermann ÜSM-20-230I1PE65 installation instructions

CyberPower CSP604T user manual

CyberPower

CyberPower CSP604T user manual

CyberPower CSP706T user manual

CyberPower

CyberPower CSP706T user manual

Mitsubishi Electric LITOL LTM-125RF manual

Mitsubishi Electric

Mitsubishi Electric LITOL LTM-125RF manual

Intermatic PS3000 installation instructions

Intermatic

Intermatic PS3000 installation instructions

Siemens SICROWBAR 7VV3003 operating instructions

Siemens

Siemens SICROWBAR 7VV3003 operating instructions

Joslyn Surgitron I 1260 Installation, operation and maintenance manual

Joslyn

Joslyn Surgitron I 1260 Installation, operation and maintenance manual

Minuteman MMS7120RCT user guide

Minuteman

Minuteman MMS7120RCT user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Lightning surge protector...................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTALLATION / INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, and basic main-
tenance procedure.
LIMITATION APPLICABLE TO M-RESTER
The M-RESTER will protect electronics equipment from
damage caused by lightning by absorbing most of the
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.
GENERAL
■FUNCTION & FEATURES
• Specifically designed to protect 4 to 20mA DC signal line
including both 4-wire and 2-wire transmitters from dam-
age caused by lightning surges
• Absorbs surges only without affecting transmitted sig-
nals.
■SPECIFICATIONS
BETWEEN LINES
LINE TO GND
Discharge voltage 30V min. ±290V min.
Max. surge voltage* 40V max. ±650V max.
Leakage current ≤5µA
@30V DC
≤5µA
@±290V DC
Response time ≤0.1 µsec.
Discharge current 5000A (8 / 20 µsec.)
Maximum load current 100mA
Internal series resistance 20Ω ±5%
Maximum line voltage 30V
*The maximum voltage that could pass through M-RESTER.
Protected equipment must be able to withstand this voltage for a
very short time period.
POINTS OF CAUTION
■ENVIRONMENT
• When heavy dust or metal particles are present in the at-
mosphere, install M-RESTER inside proper housing and
ventilate it.
• Do not install the M-RESTER where it is subjected to
continuous vibration. Do not apply physical impact to the
M-RESTER.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) and relative humidity within 30 – 90% RH
in order to ensure adequate life span and operation.
■DIELECTRIC STRENGTH TEST
• The unit will start discharging when 290V or greater
voltage is applied bewteen lines and ground. DO NOT
perform dielectric strength tests with wires connected to
the unit.
■AND ....
• We recommend that you keep spare M-RESTERs so that
you can replace them when necessary.
• Lightning surge can enter not only through signal lines
but also through power supply lines. We recommend that
you also use the Lightning Arrester for Power Lines for
sufficient protection.
COMPONENT IDENTIFICATION
Body
Specification
Label
Connection
Diagram Label
LIGHTNING SURGE PROTECTOR FOR
STANDARD SIGNAL LINE USE MODEL MDK-24
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8134 Rev.4 P. 1 / 3
INSTRUCTION MANUAL
INSTALLATION
Set the unit so that its DIN rail adapter is at the bottom.
Hung the upper hook at the rear side of unit on the DIN rail
and push in the lower. When removing the unit, push down
the DIN rail adapter utilizing screwdriver (–) and pull.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
EXTERNAL DIMENSIONS mm (inch)
10–M3.5 SCREW
8 (.31)
80 (3.15)
50 (1.97) 50 (1.97) [3.3 (.13)]
35.4 (1.39)
DIN RAIL
35mm wide
TERMINAL
COVER
•When mounting, no extra space is needed between units.
■TERMIANL ASSIGNMENT
54321
10
9876
MDK-24
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8134 Rev.4 P. 2 / 3
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
Be sure to cross-wire between the ground terminal (No. 5 or 10) and that of the protected equipment.
When the M-RESTER is connected with a device which has no ground terminal such like M-System's (See figure to the right),
ground the M-Rester ground terminal (No. 5 or 10) only.
M-RESTER M-RESTERrtmXeriw-2
tnempiuqEdetcetorPtnempiuqEdetcetorP
G
S
S
2
1
7
6
5
7
6
2
1
Current Loop
Supply
–
+
G
5
INP
■GROUNDING
M-RESTER PROTECTED
EQUIPMENT
G
G
CROSSOVER WIRE
GROUNDING
(100 ohms or less)
A crossover wire between M-RESTER ground and ground or metallic
housing of equipment is required for protection.
If the protected equipment has no ground terminal, ground the
M-RESTER only.
MAINTENANCE
Check M-RESTER periodically. Many cases of lightning are
ignored, and even lightning at a far distance often causes
inductive surges.
We recommend that you check your M-RESTER about twice
a year, before and after the rainy season. Check whenever
you experience a strong lightning occurrence.
Checking procedure is explained in the following:
■CHECKING
WIRING
• Make sure that wiring is done as instructed in the con-
nection diagram.
• Make sure that the ground terminal (No. 5 or 10) is con-
nected to the metallic housing of protected equipment.
• Make sure that the ground terminal (No. 5 or 10) is
grounded to earth.
■DISCHARGE ELEMENTS
Remove all wiring connected to M-RESTER when you test
the discharge elements.
• Check resistance across the following terminals on the
high resistance range of multimeter (infinite standard).
When measuring across (6) – (7), connect the multimeter
so that positive voltage is applied to (6) terminal.
Terminals (6) – (7), (6) – (10), (7) – (10)
• Check that discharging occurs across the same terminals
with a 500V DC megger. (Indicator of the megger reaches
over-scale.)
• If any of the above tests shows negative, replace the M-
RESTER.
MDK-24