5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8119 Rev.12 P. 1 / 3
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Surge protector....................................................................(1)
DIN rail mounting adaptor*...............................................(1)
Screws for DIN rail mounting (M4 × 8)* ...........................(2)
*Included with option code /A33
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
LIMITATION APPLICABLE TO M-RESTER
The M-RESTER will protect electronics equipment from
damage caused by lightning by absorbing most of the
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.
CAUTION (DISCHARGE CAPACITY)
The discharge capacity
of this unit has been in-
creased to 5000 Amps.
However, using an older
style base socket with
any upgraded head ele-
ment could decrease the
overall effectiveness of
the unit.
The upgraded version
element and socket are
distinguished by blue labels affixed to them. If you are re-
placing the head element only, be sure to check the label
color of the base socket that is already installed.
GENERAL
■FUNCTION & FEATURES
• Designed specifically for 4 – 20mA DC and pulse signal
line including both 4-wire and 2-wire transmitters
• Absorbs surges only without affecting instrumentation
signal
• No interruption of signal by unplugging surge protector
element.
■SPECIFICATIONS
LINE TO LINE LINE TO
EARTH
MDP-24-1 MDP-65-1
Max. continuous
operating voltage (Uc)
30V 70V ±140V
Voltage protection level
(Up) @1kV (100A)
40V 80V ±650V
Voltage protection level
(Up) @2kV (1kA)
45V 110V ±800V
Leakage current ≤ 5µA
@30V DC
≤ 5µA
@70V DC
≤ 5µA
@±140V DC
Capacitance @1 MHz ≤ 1000pF ≤ 1000pF ≤ 100pF
Response time ≤ 4 nsec. ≤ 4 nsec. ≤ 20 nsec.
Max. dishcharge current (Imax)
5000A (8 / 20 µs)
Nominal current (IN) 100mA
Internal series resistance
20 Ω ±10% including return
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
• Continuous operating voltage must be less than 75V.
■ENVIRONMENT
• When heavy dust or metal particles are present in the
air, install the surge protector inside proper housing with
sufficient ventilation.
• Do not install the surge protector where it is subjected to
continuous vibration. Do not subject the unit to physical
impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■DIELECTRIC STRENGTH TEST
• Loosen the screw located at the left-center of the element
and remove the element module from the base before
conducting a dielectric strength testing. Otherwise the
element will start discharging at a voltage exceeding the
max. continuous operating voltage (Uc), which can cause
insulation failure of the module.
Be sure to return the element and fasten securely after
the test.
■AND ....
• We recommend that you keep spare surge protectors so
that you can replace them when necessary.
• Lightning surge can enter not only through signal lines
but also through power supply lines. We recommend that
you also use the surge protectors for power line for suf-
ficient protection.
New Element Label
Blue: 5000A
(Black: 1000A)
New Base Label
Blue: 5000A
(Yellow: 1000A)
LIGHTNING SURGE PROTECTOR
FOR STANDARD SIGNAL LINE & PULSE USE MODEL
MDP-24-1
MDP-65-1
MDP-24-1 / MDP-65-1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8119 Rev.12 P. 2 / 3
COMPONENT IDENTIFICATION
M•RESTER
Ground Terminal (G)
(used as mounting bracket)
Head Element Base
Specifications
Head Element is secured to Base
with screw when the surge protector
is shipped from Factory.
INSTALLATION
In order to separate the head element from the base, loosen
the screw located at the left-center of the element.
■WALL MOUNTING
Refer to the drawings below.
• EXTERNAL DIMENSIONS unit: mm (inch)
P–P+
S–S+
23.5 (.93)
80 (3.15)
2–5 (.20) dia.
MTG HOLE
90 (3.54)
100 (3.94)
4–M4 SCREW
GROUND TERMINAL (G)
(used as mounting bracket)
27 (1.06)53 (2.08)
80 (3.15)
45 (1.77)
HEAD ELEMENT
BASE
• MOUNTING REQUIREMENTS unit: mm (inch)
25 (.97) min. 2–M4 SCREW
90 (3.54)
■DIN RAIL MOUNTING (Only for /A33)
1. MOUNTING ONTO THE ADAPTOR
Before DIN rail mounting, secure the mounting bracket of
MDP to the mounting adaptor with a screw provided with
this product. In this step, secure at one point.
DIN Rail Mounting Adaptor
M•RESTER
2. DIN RAIL MOUNTING
Set the base socket so that its mounting slider is at the bot-
tom. Position the upper hook at the rear side of base socket
on the DIN rail and push in the lower. When removing the
socket, push down the mounting slider utilizing a minus
screwdriver and pull.
DIN Rail Mounting Slider
35 mm wide
DIN Rail
3. GROUNDING
Secure the mounting bracket at the other point with the
other screw. In this step, secure the grounding wire togeth-
er with the screw.
M•RESTER
Solderless Te r
minal
• MOUNTING REQUIREMENTS unit: mm (inch)
8.5
(.33)
[3.3 (.13)]
DIN RAIL
35mm wide
80 (3.15)
45 (1.77)
4
(.18)
2–M4 MOUNTING SCREW
(used as ground terminal (G))
MDP-24-1 / MDP-65-1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8119 Rev.12 P. 3 / 3
TERMINAL CONNECTION
Connect the unit as in the diagram below.
Be sure to cross-wire between the Ground terminal (G) and that of the protected equipment. When the surge protector is con-
nected with a device which has no ground terminal such like M-System’s (See figure below), ground the M-RESTER Ground
terminal (G) only.
M-RESTER
IN
M-RESTER
CURRENT LOOP SUPPLY
(protected device)
2-WIRE TRANSMITTER
(protected device)
CENTRAL
STATION
FIELD
G
FROM
FIELD
TO
CENTRAL
STATION
+
–
P–
P+
S–
S+
P–
P+
S–
S+
CABLE
GG
G
+
–
■ PROTECTING TWO-WIRE SIGNAL LINES ■ PROTECTING ELECTRONIC INSTRUMENTS’ I/O
P+
G
P–
S+
S–
+
–
+
–
U
V
G
Receiver
(protected device)
+
–
+
–
U
V
G
Transmitter
(protected device) M-RESTER
S+
G
S–
P+
P–
M-RESTER Signal
Line
*1
*2*2
*1. Install a circuit protector when the transmitter output current exceeds 100mA.
*2. The M-RESTER is designed in particular to protect signal lines.
To protect power supply lines, install other types of surge protectors.
■GROUNDING
M-RESTER PROTECTED
EQUIPMENT
G
G
CROSSOVER WIRE
GROUNDING
(100 ohms or less)
A crossover wire between M-RESTER ground and the ground or
metallic housing of the equipment is required for protection.
If the protected equipment has no ground terminal, ground the
M-RESTER only.
When the M-RESTER is mounted with DIN Rail Mounting Adapter,
connect the grounding wire to the mounting screw of the M-RESTER.
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.8 N·m
MAINTENANCE
Check surge protectors periodically. Many cases of light-
ning are ignored, and even lightning at a far distance often
causes inductive surges.
We recommend that you check your surge protector about
twice a year, before and after the rainy season. Check
whenever you experience a strong lightning occurrence.
Checking procedure is explained in the following:
■CHECKING
WIRING
1) Make sure that wiring is done as instructed in the con-
nection diagram.
2) Make sure that the Ground terminal (G) is connected to
the metallic housing of protected equipment.
3) Make sure that the Ground terminal (G) is grounded to
earth.
DISCHARGE FUNCTION
The M-RESTER Tester is available for checking the ele-
ment module of this surge protector.
If you do not have one, approximate checking can be con-
ducted as following.
1) Remove all wiring connected to the surge protector when
you test the element module.
2) Check resistance across the following terminals on the
high resistance range of multimeter and confirm no con-
duction (The meter shows ≥ 10 MΩ). When measuring
across (S+) – (S–), connect the multimeter so that positive
voltage is applied to (S+) terminal.
Terminals (S+) – (S–), (S+) – (G), (S–) – (G)
3) Check that discharging occurs across the same terminals
with a 500V DC 1000 MΩ insulation tester (The tester
shows ≤ 20 MΩ).
If any of the above tests shows negative, replace the protec-
tor.

This manual suits for next models

1

Other M-system Surge Protector manuals

M-system MD73W User manual

M-system

M-system MD73W User manual

M-system MD7ST User manual

M-system

M-system MD7ST User manual

M-system MDP-200T User manual

M-system

M-system MDP-200T User manual

M-system MMH-1 User manual

M-system

M-system MMH-1 User manual

M-system MDPA-24 User manual

M-system

M-system MDPA-24 User manual

M-system MA-100 User manual

M-system

M-system MA-100 User manual

M-system MATP User manual

M-system

M-system MATP User manual

M-system MDP-JS User manual

M-system

M-system MDP-JS User manual

M-system MDP-65T User manual

M-system

M-system MDP-65T User manual

M-system MMA User manual

M-system

M-system MMA User manual

M-system MDPA-24 User manual

M-system

M-system MDPA-24 User manual

M-system MDR2 User manual

M-system

M-system MDR2 User manual

M-system MD7PA User manual

M-system

M-system MD7PA User manual

M-system MDH User manual

M-system

M-system MDH User manual

M-system MD74R User manual

M-system

M-system MD74R User manual

M-system MD6 24 Series User manual

M-system

M-system MD6 24 Series User manual

M-system MD6x-24 User manual

M-system

M-system MD6x-24 User manual

M-system MD7PM User manual

M-system

M-system MD7PM User manual

M-system MH-1201 User manual

M-system

M-system MH-1201 User manual

M-system MAT2 Series User manual

M-system

M-system MAT2 Series User manual

M-system MDK-LC User manual

M-system

M-system MDK-LC User manual

M-system MDP-LWA User manual

M-system

M-system MDP-LWA User manual

M-system MGD-24 User manual

M-system

M-system MGD-24 User manual

M-system MDP-4R User manual

M-system

M-system MDP-4R User manual

Popular Surge Protector manuals by other brands

Eaton BUSSMAN Series installation manual

Eaton

Eaton BUSSMAN Series installation manual

Koblenz SS-2000 USBAC operating instructions

Koblenz

Koblenz SS-2000 USBAC operating instructions

Amtrol SURGE-TROL SPT-11 Installation & operation instructions

Amtrol

Amtrol SURGE-TROL SPT-11 Installation & operation instructions

Intermatic 177547 installation instructions

Intermatic

Intermatic 177547 installation instructions

Siemens FireSeeker FS-100 quick start guide

Siemens

Siemens FireSeeker FS-100 quick start guide

OPTI-UPS MG2T / MG3T Specifications

OPTI-UPS

OPTI-UPS MG2T / MG3T Specifications

Emerson Liebert Surge and Signal Protection Specifications

Emerson

Emerson Liebert Surge and Signal Protection Specifications

Supra MD02EU/SP quick start guide

Supra

Supra MD02EU/SP quick start guide

Ilsco SSI SpecPRO CSM Series manual

Ilsco

Ilsco SSI SpecPRO CSM Series manual

Panamax MIP20 instructions

Panamax

Panamax MIP20 instructions

MTL Surge Technologies MA05/D Installation instructions & user manual

MTL Surge Technologies

MTL Surge Technologies MA05/D Installation instructions & user manual

SC&T SP006PH-10G user manual

SC&T

SC&T SP006PH-10G user manual

Cooper Bussmann BRICK 6125TD Specification sheet

Cooper Bussmann

Cooper Bussmann BRICK 6125TD Specification sheet

Ultra Products ULT31571 Specifications

Ultra Products

Ultra Products ULT31571 Specifications

Mersen Surge-Trap instructions

Mersen

Mersen Surge-Trap instructions

Adcom ACE-515 owner's manual

Adcom

Adcom ACE-515 owner's manual

Qoltec Monolith 53894 user manual

Qoltec

Qoltec Monolith 53894 user manual

Sollatek DSP-D instruction manual

Sollatek

Sollatek DSP-D instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.