  9. M-system MGA-100 User manual

M-system MGA-100 User manual

This manual suits for next models

1

Other M-system Surge Protector manuals

M-system MD7PM User manual

M-system

M-system MD7PM User manual

M-system MAT2 Series User manual

M-system

M-system MAT2 Series User manual

M-system MDP-DM3 User manual

M-system

M-system MDP-DM3 User manual

M-system MDCAT-A Series User manual

M-system

M-system MDCAT-A Series User manual

M-system MD7LWA User manual

M-system

M-system MD7LWA User manual

M-system MAL-230x User manual

M-system

M-system MAL-230x User manual

M-system MD6 24 Series User manual

M-system

M-system MD6 24 Series User manual

M-system MDP-100T User manual

M-system

M-system MDP-100T User manual

M-system MDCAT-SPE-A User manual

M-system

M-system MDCAT-SPE-A User manual

M-system MMA User manual

M-system

M-system MMA User manual

M-system MDP-100 User manual

M-system

M-system MDP-100 User manual

M-system MDP-24-1 User manual

M-system

M-system MDP-24-1 User manual

M-system MDP-SP User manual

M-system

M-system MDP-SP User manual

M-system MDP-200T User manual

M-system

M-system MDP-200T User manual

M-system MD73W User manual

M-system

M-system MD73W User manual

M-system MD6x-24 User manual

M-system

M-system MD6x-24 User manual

M-system MDP-65T User manual

M-system

M-system MDP-65T User manual

M-system MH-1201 User manual

M-system

M-system MH-1201 User manual

M-system MDP-JS User manual

M-system

M-system MDP-JS User manual

M-system MDCAT-SPE User manual

M-system

M-system MDCAT-SPE User manual

M-system MDP-LWA User manual

M-system

M-system MDP-LWA User manual

M-system MAKN User manual

M-system

M-system MAKN User manual

M-system MDP-24T User manual

M-system

M-system MDP-24T User manual

M-system MD7G User manual

M-system

M-system MD7G User manual

Popular Surge Protector manuals by other brands

Philips Theatre Director SPP4200WA/17 Owner's manual & warranty

Philips

Philips Theatre Director SPP4200WA/17 Owner's manual & warranty

CyberPower CSP600WSU user manual

CyberPower

CyberPower CSP600WSU user manual

UTP BALUN SP-VD08 user manual

UTP BALUN

UTP BALUN SP-VD08 user manual

ELAC ProteK PR91-W Setup guide

ELAC

ELAC ProteK PR91-W Setup guide

Tsubaki TSM4000M1 instruction manual

Tsubaki

Tsubaki TSM4000M1 instruction manual

CyberPower B1006T user manual

CyberPower

CyberPower B1006T user manual

QVS PP134C Specification sheet

QVS

QVS PP134C Specification sheet

Davis Instruments Radio Surge Protector user guide

Davis Instruments

Davis Instruments Radio Surge Protector user guide

CyberPower B300WRC1 user manual

CyberPower

CyberPower B300WRC1 user manual

Panamax MAX 5400-EX owner's guide

Panamax

Panamax MAX 5400-EX owner's guide

OBO Bettermann ÜSM-20-230I1PE65 installation instructions

OBO Bettermann

OBO Bettermann ÜSM-20-230I1PE65 installation instructions

CyberPower CSP604T user manual

CyberPower

CyberPower CSP604T user manual

CyberPower CSP706T user manual

CyberPower

CyberPower CSP706T user manual

Mitsubishi Electric LITOL LTM-125RF manual

Mitsubishi Electric

Mitsubishi Electric LITOL LTM-125RF manual

Intermatic PS3000 installation instructions

Intermatic

Intermatic PS3000 installation instructions

Siemens SICROWBAR 7VV3003 operating instructions

Siemens

Siemens SICROWBAR 7VV3003 operating instructions

Joslyn Surgitron I 1260 Installation, operation and maintenance manual

Joslyn

Joslyn Surgitron I 1260 Installation, operation and maintenance manual

Minuteman MMS7120RCT user guide

Minuteman

Minuteman MMS7120RCT user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Lightning surge protector...................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTALLATION / INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, and basic main-
tenance procedure.
LIMITATION APPLICABLE TO M-RESTER
The M-RESTER will protect electronics equipment from
damage caused by lightning by absorbing most of the
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.
GENERAL
■FUNCTION & FEATURES
• Designed specifically for AC power supplies up to 2 amps
• 2A fuse provided to protect the power source in case of
breakdown of discharge element itself due to surges in far
excess of peak voltage
• Power indicator LED provided
• Simple installation with compact plug-in construction
■SPECIFICATIONS
BETWEEN LINES
LINE TO GND
MGA-100 MGA-200
Discharge voltage (p-p)
190V min. 410V min. 410V min.
Max. surge voltage* 400V max. 800V max. 800V max.
Leakage current <2mA
@150V DC
<2mA
@300V DC
<1mA
@300V DC
Response time <0.1 μsec.
Discharge current 1000A (8 / 20 μsec.)
Max. load current 2A
Rated line voltage 120V AC or 170V DC (MGA-100)
250V AC or 350V DC (MGA-200)
*The maximum voltage that could pass through M-RESTER.
Protected equipment must be able to withstand this voltage
for a very short time period.
POINTS OF CAUTION
■ENVIRONMENT
• When heavy dust or metal particles are present in the at-
mosphere, install M-RESTER inside proper housing and
ventilate it.
• Do not install the M-RESTER where it is subjected to
continuous vibration. Do not apply physical impact to the
M-RESTER.
• Environmental temperature must be within -5 to +55°C
in order to ensure adequate life span and operation.
■WIRING
• DO NOT perform dielectric strength tests with wires con-
nectedtotheunit.Otherwisetheelementwillstartdischarg-
ing at discharge voltage,which can cause insulation failure.
Be sure to return the wires after the test.
■FUSE
• Even when a strong lightning surge exceeding discharge
current capacity of lightning arrester enters to power
supply cables, the MRESTER protects the equipment to
some extent but its discharge element may fail. The fuse
will be blown in such a case, which is indicated with the
monitor LED turned OFF. We recommend that you im-
mediately replace the M-RESTER with a new one.
■AND ....
• We recommend that you keep spare M-RESTERs so that
you can replace them when necessary.
COMPONENT IDENTIFICATION
Body
Monitor LED
Terminal Cover
Specification Label
LIGHTNING SURGE PROTECTOR FOR POWER SUPPLY USE
(2A; rack-mounted) MODEL
MGA-100/MGA-200
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8271 Rev.4 P. 1 / 3
INSTRUCTION MANUAL
INSTALLATION
Refer to the following drawings.
■EXTERNAL DIMENSIONS unit: mm (inch)
102 (4.02)
3 (.12)
51 (2.01)
80 (3.15)
TERMINAL COVER
2–4.3 (.17) dia.
MTG HOLE
7–M3.5 SCREW
8 (.31)
91 (3.58)
99 (3.90 )
25 (.98)
12
3
56
78
MONITOR LEDs
ch.1
ch.2
■MOUNTING REQUIREMENTS mm (inch)
91 (3.58)
83 (2.27)
26 (1.02)
ANGLE BRACKET
2–M3.5 SCREW
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
Be sure to cross-wire between the Ground terminal (3) and
metallic housing of the protected equipment. (100W max.)
M-RESTER
PROTECTED
EQUIPMENT
7
1
V(–)
U(+)
V(–)
U(+)
3
5
G
Connection example with Ch.1
■GROUNDING
M-RESTER PROTECTED
EQUIPMENT
G
G
CROSSOVER WIRE
GROUNDING
(100 ohms or less)
A crossover wire between M-RESTER ground and ground or metallic
housing of equipment is required for protection.
If the protected equipment has no ground terminal, ground the
M-RESTER only.
MGA-100 / MGA-200
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8271 Rev.4 P. 2 / 3
MAINTENANCE
Check M-RESTER periodically. Many cases of lightning are
ignored, and even lightning at a far distance often causes
inductive surges. We recommend that you check your M-
RESTER about twice a year, before and after the rainy sea-
son. Check whenever you experience a strong lightning oc-
currence. Checking procedure is explained in the following:
■CHECKING
WIRING
• Make sure that wiring is done as instructed in the con-
nection diagram.
• Make sure that the Ground terminal (3) is connected to
the metallic housing of protected equipment.
• Make sure that the Ground terminal (3) is grounded to
earth.
■DISCHARGE FUNCTION
Remove all the wires connected to the M-RESTER and test
its discharge capability as follows:
• Apply 150V DC across the terminals (1) – (7) and (2) – (8)
with a resistor of approx. 10kW in serial. Measure leak-
age current. (≤1mA standard) Check also that the power
indicator LED is ON.
• Then apply 250V DC and check that discharging occurs.
(≥2mA standard)
• Apply 300V DC across the following terminals and meas-
ure leakage current. (≤1mA standard)
Terminals (1) – (3), (7) – (3), (2) – (3), (8) – (3)
• Then apply 500V DC and check that discharging occurs.
(≥2mA standard)
• If DC power source is not available, check resistance
across the following terminals on the high resistance
range of multimeter (infinite standard).
Terminals (1) – (7), (1) – (3), (7) – (3), (2) – (8), (2) – (3), (8) – (3)
• Check that discharging occurs across the same terminals
with a 500V DC megger. (Indicator of the megger reaches
over-scale.)
• If any of the above tests shows negative, replace the whole
M-RESTER unit.
MGA-100 / MGA-200
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8271 Rev.4 P. 3 / 3