EM-8058 Rev.6 P. 1 / 4
INSTRUCTION MANUAL
LIGHTNING SURGE PROTECTOR FOR
RS-485 / RS-422 (ultra-slim) MODEL MD74R
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Surge protector....................................................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
LIMITATION APPLICABLE TO M-RESTER
The M-RESTER will protect electronics equipment from
damage caused by lightning by absorbing most of the
surge voltages.
However, M-RESTER may not be effective against cer-
tain extremely high voltages caused by a direct or almost
direct hit by lightning.
M-RESTER must be installed according to this installa-
tion / instruction manual.
GENERAL
■FUNCTION & FEATURES
• High discharge current capacity 20 kA (8 / 20 µs), 1 kA
(10 / 350 µs)
• Ultra-thin 7-mm-wide module can be mounted in high
density
• Excellent protection employing multi-stage SPD circuits
• DIN rail mounting and grounding
• Shield terminal provided
■SPECIFICATIONS
See Table 1.
Table 1. Specications
LINE TO LINE LINE TO SG LINE/SG TO EARTH SHLD TO EARTH
Max. continuous operating voltage (Uc)
±5V 5V ±160V ±160V *1
Voltage protection level (Up)
@4kV (1.2 / 50 µs)
±25V 25V ±800V ±800V *1
Leakage current @Uc ≤ 200µA ≤ 200µA ≤ 10µA ≤ 10µA*1
Response time ≤ 4 nsec. ≤ 4 nsec. ≤ 20 nsec. ≤ 20 nsec.*1
Approx. capacitance @ 100 kHz 300 pF 300 pF 100 pF 100 pF
Max. discharge current (Imax) 20kA (8 / 20 µs), 1.0kA (10 / 350 µs)
Nominal current (IN) 100mA
Internal series resistance 2Ω ±10% per line
Input attenuation -0.5 dB max. @DC...2.0 MHz, Z0 = 110Ω
*1. Values for the MD74R-FF. Shortcircuited for the MD74R-FG.
056 222 38 18 mailbox@sentronic.com www.sentronic.com
SENTRONIC AG
MD74R
EM-8058 Rev.6 P. 2 / 4
POINTS OF CAUTION
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -25 to +85°C
(-13 to +185°F) with relative humidity within 30 to 90%
RH in order to ensure adequate life span and operation.
• This unit needs a DIN rail as earth grounding bar. Ox-
ide coating of an aluminium rail may lower the electric
conductivity between this module and the ground. Use a
steel or copper rail.
■DIELECTRIC STRENGTH TESTING
• The surge protector starts discharging when 160V or
greater voltage (with floating shield type) or several volts
(with grounding shield type) is applied between lines and
earth. Remove the grounding wire before conducting a
test. Be sure to return the wire after the test.
■AND ....
• We recommend that you keep spare surge protectors so
that you can replace them when necessary.
• Lightning surge can enter not only through signal lines
but also through power supply lines. We recommend that
you also use the Lightning Surge Protector for Power
Lines for adequate protection.
COMPONENT IDENTIFICATION
Body
Spring Loader
DIN Rail Mounting
Adaptor (for grounding)
Connection
Diagram
(left side)
Model No.
Indication
INSTALLATION
Mount the unit on a DIN rail. Once installed, do not move
it to another DIN rail.
■MOUNTING THE UNIT ON A DIN RAIL
A)Hang the upper hook of the DIN rail mounting adaptor at
the rear side of unit, on the DIN rail.
B)Push in the lower in keeping pressing the unit to the DIN
rail.
C)DIN rails generally have slight individual variability in
size. If you find it difficult to push in the lower part, go
back to (A) and hang the upper part more deeply onto the
rail and try (B) again.
A
DIN Rail
B
■REMOVING THE UNIT
A)Push down the spring loader utilizing a minus screwdriv-
er.
B)Confirm that it is pulled enough down and pull out the
lower part of the unit.
C)Detach the upper part from the DIN rail.
A
B
Spring Loader
C
056 222 38 18 mailbox@sentronic.com www.sentronic.com
SENTRONIC AG
MD74R
EM-8058 Rev.6 P. 3 / 4
TERMINAL CONNECTION
Connect the unit as in the diagram below.
Be sure to ground the DIN rail on which the unit is mounted and cross-wire between the rail and FG terminal of the protected
device as shown in Figure 1 in order to equalize the earth potential.
When the unit is connected with a device which has no FG terminal, ground the surge protector only.
■EXTERNAL DIMENSIONS unit: mm (inch)
8
6
5
4
1
2
3
7
4
1
5
2
6
3
8
7
95 (3.74)
7
(.28)
98 (3.86) [1.5 (.06)]
8–M3 EURO
TERMINAL
DIN RAIL
(35 mm wide)
DIN RAIL
ADAPTOR
WIRE INSERTION ANGLE: approx. 20°
57 (2.24)
1.9 (.07)
■Figure 1. GROUNDING
M-RESTER PROTECTED
EQUIPMENT
FG
CROSSOVER WIRE
Cross-wire from the DIN rail to the metal housing of the protected device
to equalize the ground potential.
Ground only the surge protector when the protected device has no
grounding terminal.
DIN RAIL ADAPTOR
(for grounding)
DIN RAIL
Grounding
■CAUTION WHEN WIRING
Hold the module steady at the front when you
tighten/loosen screw terminals.
056 222 38 18 mailbox@sentronic.com www.sentronic.com
SENTRONIC AG
MD74R
EM-8058 Rev.6 P. 4 / 4
■CONNECTION DIAGRAM
5 2
6 3
7
8
DISCHARGE
ELEMENT
DISCHARGE
ELEMENT
DIN RAIL ADAPTOR
(for grounding)
4 1
52
63
78
41
Series ResistanceSeries Resistance
Protected DeviceMD74R-FF
SG
SHLD
FG
+
–
*2
LINE
DIN RAILDIN RAIL
GroundingGrounding
MD74R-FG*1
Crossover Wire
*5*3*3
*4*4
Crossover Wire
*5
(SHLD)(SHLD)
DISCHARGE
ELEMENT
DISCHARGE
ELEMENT
DIN RAIL ADAPTOR
(for grounding)
Protected Device
SG
SHLD
FG
+
–
LINE
Surge
Side
Surge
Side
Protected
Side
Protected
Side
*1. Choose the MD74R-FG when the shield wire is to be grounded.
*2. When SHLD and SG terminals are not isolated, DO NOT connect the surge protector’s terminal 7 to SHLD.
*3. Oxide film on the surface of an aluminium rail may lower the electric conductivity between this module and the ground.
Use a steel or copper rail.
*4. Be sure to ground the DIN rail. Recommended grounding resistance max. 100 ohms.
*5. Cross-wire from the DIN rail to the metal housing of the protected device to equalize the ground potential.
Ground only the surge protector when the protected device has no grounding terminal.
WIRING INSTRUCTIONS
■EURO TERMINAL
Torque: 0.3 N·m
Applicable wire size: 0.2 – 2.5 mm2
Stripped length: 8 mm
MAINTENANCE
Check surge protectors periodically. Many cases of light-
ning are ignored, and even lightning at a far distance often
causes inductive surges.
We recommend that you check your surge protector about
twice a year, before and after the rainy season. Check
whenever you experience a strong lightning occurrence.
Checking procedure is explained in the following:
■CHECKING
WIRING
1) Make sure that wiring is done as instructed in the con-
nection diagram.
2) Make sure that the DIN rail is connected to the metal
enclosure of protected device.
3) Make sure that the surge protector is securely attached
to the DIN rail, and that the rail is grounded to earth.
DISCHARGE ELEMENT
Preliminary checking can be conducted as following.
For detailed checking, send the surge protector back to M-
System.
1) Remove all wiring connected to the surge protector when
you test the module.
2) Check resistance across the following terminals on the
high resistance range of multimeter (measuring current
≤ 0.25 µA) and confirm no conduction.
Terminals (4) – (5), (4) – (6), (5) – (6),
(6) – (DIN rail), (8) – (DIN rail)
The tester should show 1 MΩ or greater at (4) – (5), (4)
– (6), (5) – (6) and 10 MΩ or more at other terminals.
When measuring across (4) – (6) and (5) – (6), connect the
tester’s probe so that the positive voltage is applied to (4)
and (5) respectively.
For the MD74R-FG, (8) – (DIN rail) should show approx.
0 Ω.
3) Confirm conduction across the same terminals with a 500
V DC 1000 MΩ insulation tester in the same manner as
with the tester. The tester should show 20 MΩ or less.
4) If any of the above tests shows negative, please contact
M-System’s Sales Office or representatives.
056 222 38 18 mailbox@sentronic.com www.sentronic.com
SENTRONIC AG

Other M-system Surge Protector manuals

M-system MD7TC User manual

M-system

M-system MD7TC User manual

M-system MDP-RB User manual

M-system

M-system MDP-RB User manual

M-system MDH User manual

M-system

M-system MDH User manual

M-system MDP-LWA User manual

M-system

M-system MDP-LWA User manual

M-system MDCAT-SPE-A User manual

M-system

M-system MDCAT-SPE-A User manual

M-system MD-LC2 Service manual

M-system

M-system MD-LC2 Service manual

M-system MMAH Series User manual

M-system

M-system MMAH Series User manual

M-system MD6x-24 User manual

M-system

M-system MD6x-24 User manual

M-system MGA-100 User manual

M-system

M-system MGA-100 User manual

M-system MDP-DM3 User manual

M-system

M-system MDP-DM3 User manual

M-system MDP-24-1 User manual

M-system

M-system MDP-24-1 User manual

M-system MAL-230x User manual

M-system

M-system MAL-230x User manual

M-system MD7LC User manual

M-system

M-system MD7LC User manual

M-system MDP-LWA User manual

M-system

M-system MDP-LWA User manual

M-system MAKN User manual

M-system

M-system MAKN User manual

M-system MDP-TL User manual

M-system

M-system MDP-TL User manual

M-system MMAJ User manual

M-system

M-system MMAJ User manual

M-system MDR2 User manual

M-system

M-system MDR2 User manual

M-system MDCAT-SPE User manual

M-system

M-system MDCAT-SPE User manual

M-system MD73W User manual

M-system

M-system MD73W User manual

M-system 6SN User manual

M-system

M-system 6SN User manual

M-system MDP-24T User manual

M-system

M-system MDP-24T User manual

M-system MD7G User manual

M-system

M-system MD7G User manual

M-system MD7PA User manual

M-system

M-system MD7PA User manual

Popular Surge Protector manuals by other brands

Nexxt Solutions Smart Wi-Fi dual plug manual

Nexxt Solutions

Nexxt Solutions Smart Wi-Fi dual plug manual

Philips SPP1187WA Specification sheet

Philips

Philips SPP1187WA Specification sheet

Genie GSP1000 quick start guide

Genie

Genie GSP1000 quick start guide

CPT PSM3-20 TNC Series installation instructions

CPT

CPT PSM3-20 TNC Series installation instructions

Current Technology PX3 Installation, operation and maintenance manual

Current Technology

Current Technology PX3 Installation, operation and maintenance manual

Lowell ACSP2004-IG-GTF manual

Lowell

Lowell ACSP2004-IG-GTF manual

Wiremold legrand SENTREX installation instructions

Wiremold

Wiremold legrand SENTREX installation instructions

Intermatic IG3240RC3 installation instructions

Intermatic

Intermatic IG3240RC3 installation instructions

Micro Innovations SP01F quick start guide

Micro Innovations

Micro Innovations SP01F quick start guide

LPS PP-2/110 Series installation instructions

LPS

LPS PP-2/110 Series installation instructions

Infinite L-com SRCN-C033 user guide

Infinite

Infinite L-com SRCN-C033 user guide

Trust PW-3100 Product information

Trust

Trust PW-3100 Product information

SurgeX SX-1115ip-X user manual

SurgeX

SurgeX SX-1115ip-X user manual

Eaton SPD Series instruction manual

Eaton

Eaton SPD Series instruction manual

North Shore Safety LineGard PGFS-13105 INSTALLATION AND TESTING PROCEDURE

North Shore Safety

North Shore Safety LineGard PGFS-13105 INSTALLATION AND TESTING PROCEDURE

Intermatic IG1240RC user manual

Intermatic

Intermatic IG1240RC user manual

FRO­NIUS Symo GEN24 Plus quick start guide

FRO­NIUS

FRO­NIUS Symo GEN24 Plus quick start guide

Tripp Lite TLP707TEL Specifications

Tripp Lite

Tripp Lite TLP707TEL Specifications

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.