Accuracy*: ± 1% FS
Overpressure: 300%
Burst Pressure: 500%
Supply Voltage: 12–40 VDC
12–35 VAC (VDC output units only)
Supply Current: VDC Units – 10 mAmax.
mAUnits – 20 mAmax.
Enclosure: 18 Ga C. R. Steel NEMA4 (IP-65)
Finish: Baked on enamel – PMS2GR88B
Conformance: EMC Standards EN50082-1(1992)
EN55014(1993)/EN60730-1(1992)
Compensated Temp Range: 0°F to 180°F
(-18°C to 82°C)
T. C. Error: ±0.025%/°F (.03%/°C)
Media Compatibility: Liquid/gases compatible to
316L stainless steel
Port Connection: 1/8" NPT
Environmental: 10–90%RH Non-Condensing
Termination: Unpluggable screw terminal block
Wire Size: 12 Ga max.
Load Impedance: 1.6K ohms max. at 40 VDC (mA
output units)
1K ohms min. (VDC output units)
Weight: Enclosure 1.0 lbs. (.45 kg)
*Includes non-linearity, hysteresis and non-repeatability
RANGE OUTPUT
SPECIFICATIONS
Inspection
Requirements
Mounting
R1 (psig)
R2 (psig)
R3 (psig)
R4 (kPa)
0 to 100 / 0 to 50 / 0 to 25
0 to 300 / 0 to 150 / 0 to 75
0 to 500 / 0 to 250 / 0 to 125
0 to 700 / 0 to 350 / 0 to 175
(4–20 mA 2-wire)
(0–5 VDC/0–10 VDC
field selectable)
mA
VDC
For Additional Information See PR-264 Data Sheet
INSTALLATION
8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA
800-843-5116 • 952-556-4900 • Fax 952-556-4997
Model PR-264
Technical Information
TI.264-04
PRESSURE TRANSDUCER
Inspect the package for damage. If damaged, notify the
appropriate carrier immediately. If undamaged, open the
package and inspect the device for obvious damage.
Return damaged products.
Warning:
• Do not use on oxygen service, in an explosive/hazardous
environment, or with flammable/combustible media.
•Disconnect power supply before installation to prevent
electrical shock and equipment damage.
•Make all connections in accordance with the job wiring diagram
and in accordance with national and local electrical codes. Use
copper conductors only.
Caution:
•Use electrostatic discharge precautions (e.g., use of wrist
straps) during installation and wiring to prevent equipment
damage.
•Avoid locations where severe shock or vibration, excessive
moisture or corrosive fumes are present. NEMAType 4
housings are intended for outdoor use primarily to provide
a degree of protection against wind-blown dust, rain, and
hose-directed water.
•Do not exceed ratings of the device.
•Tools (not provided)
- Digital Volt-ohm Meter (DVM)
- Appropriate screwdriver for mounting screws
- Appropriate drill and drill bit for mounting screws
•Appropriate accessories
•Two #8 self-tapping mounting screws (not provided)
•Training: Installer must be a qualified, experienced technician
Wiring Use maximum 12 AWG wire for wiring terminals. Use copper or
stainless steel tubing for the connection to the transducer. Refer
to Figures 1, 2, 3, & 4 for wiring information and Figures 5& 6for
switch designations.
(Wiring Instructions continued on pages 2 and 3.)
ORDERING INFORMATION: PR-264-
R5 (kPa)
R6 (kPa)
0 to 2000 / 0 to 1000 / 0 to 500
0 to 3500 / 0 to 1750 / 0 to 875
RoHS
The PR-264 must be mounted on a vertical surface with the 1/8"
NPT connection pointed downward. Refer to Figure 7 for
mounting dimensions.
1. Remove the transducer cover using a Phillips head
screwdriver.
2. Select the mounting location.
3. Mount transducer on a vertical surface with two #8 self-tapping
screws (not provided).
4. Pull wires through bottom of enclosure and make necessary
connections.
5. Replace the unit cover and make pneumatic connections.