manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. MAMAC SYSTEMS
  6. •
  7. Transducer
  8. •
  9. MAMAC SYSTEMS PR-283 Manual

MAMAC SYSTEMS PR-283 Manual

Model PR-283
Differential Pressure Transducer With Manifold
Technical Information
Rev. 0
7400 Flying Cloud Drive • Minneapolis, MN 55344-3720 • USA
800-843-5116 • 952-835-1626 • Fax 952-829-5331
www.mamacsys.com
IS.PR283-00
For additional information, see the accompanying data sheet for this transducer.
Ordering Information
Dimensions
Figure 1. Differential Pressure Transducer and Manifold Dimensions
Figure 2. Manifold (VM-705) Dimensions
Specifications
Accuracy*:±1% FS
Overpressure: 300% of rated range
Burst Pressure: 500% of rated range
Maximum Static Pressure: 200% of DP range
Supply Voltage: 12 - 40 VDC;
12 - 35 VAC (VDC output transducers only)
Supply Current: 10 mA maximum VDC output transducers;
20 mA maximum mA output transducers
Enclosure: 18 gage C.R. steel NEMA 4 (IP 65)
Finish: Baked-on enamel PMS2GR88B
Conformance: EMC Standards EN50082-1(1992), EN55014(1993)/EN60730-1(1992), AS/NZ
3548 (1995) EN55022:IEC/CISPR 22 (1993)
Compensated Temperature Range: 0°F to 180°F (-18°C to 82°C)
T. C. Erro r:±0.025%/°F (.03%/°C)
Media Compatibility: Liquids and gases compatible to 316L stainless steel
Port Connection: 1/8-inch NPT
Environmental: 10 to 90% RH non-condensing
Termination: Unpluggable screw terminal block
Wire Size: 12 gage maximum
Load Impedance: 3,000 ohms maximum at 40 VDC (mA output transducers);
1,000 ohms minimum (VDC output transducers)
Weight: 1.0 lb. (.45 kg)
*Includes nonlinearity, hysteresis, and non-repeatability.
Installation
Inspection
Inspect the transducer packaging for signs of damage. If damaged, notify the carrier
immediately.
Requirements
• Tools (not provided):
- Digital volt-ohm meter (DVM)
- Appropriate screwdriver for mounting screws
- Appropriate drill and drill bit for mounting screws
• Appropriate accessories
• Six #10 mounting screws (not provided)
• Training: Installer must be a qualified and experienced technician
WARNING!
• Do not use on oxygen service, in an explosive or hazardous environment, or with flammable
or combustible material.
• Disconnect the power supply before installing the transducer. Failure to do so can result in
electrical shock and equipment damage.
• Make all connections in accordance with the job wiring diagram and national and local
electrical codes.
• Use electrostatic discharge precautions such as wrist straps when installing and wiring the
transducer.
• Avoid installing the transducer in locations where severe shock, vibration, excessive
moisture, or corrosive fumes are present. NEMA 4 housings are primarily intended for
outdoor use to provide a degree of protection against windblown dust, rain, and hose-
directed water.
• Do not exceed ratings for the transducer.
Mounting
Mount the differential pressure transducer on a vertical surface with the 1/8-inch NPT
connection pointing downwards. See Figures 1 and 2 for the transducer’s mounting
dimensions.
1. Mount the valve manifold on the wall using four #10 screws (not provided).
2. Run piping into the valve manifold.
3. Slide the transducer’s male fittings into the compression fittings on the valve manifold.
4. Fasten the transducer to the wall using two #10 screws (not provided).
5. Tighten the valve manifold compression nut until finger tight. Scribe the compression nut
at the 6 o'clock position and then tighten the nut one and one-quarter turns to the 9 o'clock
position.
6. The connection can be disconnected and retightened many times. When retightening the
nut, tighten only until light resistance is felt (original tight position).
7. Run conduit and wiring to the transducer. Connect wiring as shown in Figures 4 through 7,
and set the switch to the correct position.
8. Open the nulling valve (center valve), low pressure valve, high pressure valve, and then
close the nulling valve.
Wiring
Use 12 AWG wire maximum for wiring terminals and copper or stainless steel tubing for the
transducer connections. See Figures 4 through 7 for wiring diagrams and Figures 8 and 9 for
jumper designations.
Wiring for mA Output
The mA output differential pressure transducer must be powered with a 12 - 40 VDC power
supply.
1. Remove the blue terminal block by carefully pulling it off the circuit board. See Figure 4.
2. Locate the [+] and [-] terminal markings on the board.
3. Attach the supply voltage to the [+] lead.
4. Connect the 4 - 20 mA output ([-] terminal) to the controller’s input terminal.
5. Ensure that the power supply common is attached to the common bus of the controller.
6. Reinsert the terminal block to the circuit board and apply power to the transducer.
7. Check for the appropriate output signal by using a DVM set to DC milliamps connected in
series to the [-] terminal.
Figure 4. Differential Pressure Transducer With mA Output
Wiring for VDC Output
The VDC output differential pressure transducer is field selectable for 0 - 5 VDC or 0 - 10 VDC
output and can be powered with either 12 - 40 VDC or 12 - 35 VAC.
1. Remove the blue terminal block by carefully pulling it off the circuit board. See Figure 5.
2. Locate the [+], [-], and [0] terminal markings on the board.
3. Attach the power wires to the [+] and [-] terminals. The [-] terminal is also the negative
output terminal.
4. Connect the [0] terminal, which is the positive VDC output terminal, to the controller’s
input.
5. Reinsert the terminal block to the circuit board and apply power to the transducer.
6. Check the appropriate VDC output by using a DVM set to DC volts connected to the [0]
and [-] terminals.
CAUTION!
• If using grounded AC, ensure that the hot wire is on the [+] terminal. In addition, if using a
controller without built-in isolation, use an isolation transformer to supply the transducer.
• This transducer contains a half-wave rectifier power supply and must not be powered from
transformers powering other devices with non-isolated full-wave rectifier power supplies.
• When multiple transducers are powered from the same transformer, damage will result
unless all 24-gage power leads are connected to the same power lead on all transducers.
Maintain the correct phasing when powering more than one transducer from a single
transformer.
RANGE OUTPUT
R1 (psig)
R2 (psig)
R3 (psig)
R4 (kPa)
R5 (kPa)
R6 (kPa)
0 to 5.0 / 0 to 10 / 0 to 20
0 to 25 / 0 to 50 / 0 to 100
0 to 75 / 0 to 150 / 0 to 300
0 to 35 / 0 to 70 / 0 to 140
0 to 175 / 0 to 350 / 0 to 700
0 to 500 / 0 to 1000 / 0 to 2000
mA
VDC
4 - 20 mA two-wire
0 - 5 or 0 - 10 VDC
(field selectable)
Figure 3. Differential Pressure
Transducer
Page 2 of 2
IS.PR283-00
Figure 5. Differential Pressure Transducer With VDC Output
Typical Applications (wiring diagrams)
Figures 6 and 7 illustrate typical wiring diagrams for the mA output differential pressure
transducer.
Figure 6. Wiring the mA Output Differential Pressure Transducer
With an External DC Power Supply
Figure 7. Wiring the mA Output Differential Pressure Transducer
Where the Controller or Meter Has an Internal DC Power Supply
Figures 8 and 9 illustrate typical wiring diagrams for the VDC output differential pressure
transducer.
Figure 8. Wiring the VDC Output Differential
Pressure Transducer
Figure 9. Wiring the VDC Output Differential Pressure
Transducer With a DC Power Supply
Adjustments
Jumper Configuration
Jumper configuration varies according to the output type of the differential pressure transducer.
Range configurations for transducers are listed in Table 1. Jumper selections for transducers
with mA output are shown in Figure 10; jumper selections for transducers with VDC output are
shown in Figure 11.
Figure 10. Jumper Selections for mA Output Differential
Pressure Transducers
Figure 11. Jumper Selections for VDC Output Differential
Pressure Transducers
Checkout
1. Verify that the transducer is mounted in the correct position.
2. Verify the appropriate input signal and supply voltage.
3. Verify the appropriate input configuration.
CAUTION!
• Never connect 120 VAC to the differential pressure transducer. AC voltage should never be
supplied to a transducer intended for DC power.
Transducer Operation
1. Adjust the pressure to obtain the maximum output signal for the appropriate range.
2. Ensure that output is either 20 mA or 5 or 10 VDC.
3. Adjust the pressure to obtain a minimum output signal.
4. Ensure that output is either 4 mA or 0 VDC.
Calibration
All transducers are factory calibrated to meet or exceed published specifications. If field
adjustment is necessary, follow these instructions:
Calibration of mA Output Differential Pressure Transducers
1. Connect the [+] and [-] terminals to the appropriate power source.
2. Connect the DVM in series to the [-] terminal.
3. Apply low pressure to the transducer and carefully adjust the zero trimmer [Z] to obtain the
desired low output pressure.
4. Apply high pressure to the transducer and adjust the span trimmer [S] to obtain the desired
high output pressure.
5. Repeat steps 3 and 4 until the transducer is fully calibrated.
Calibration of VDC Output Differential Pressure Transducers
1. Connect the [+] and [-] terminals to the appropriate power source. The [-] terminal is also
the negative output terminal.
2. Connect the DVM on DC volts across the [0] and [-] terminals.
3. Apply low pressure to the transducer and carefully adjust the zero trimmer [Z] to obtain the
desired low output pressure.
4. Apply high pressure to the transducer and adjust the span trimmer [S] to obtain the desired
high output pressure.
5. Repeat steps 3 and 4 until the transducer is fully calibrated.
Maintenance
Perform regular maintenance on the total system to ensure the sustained optimum performance
of the differential pressure transducer.
Field Repair
Do not attempt to repair the differential pressure transducer. Replace a malfunctioning
transducer with a functional transducer if necessary.
Warranty
See the accompanying data sheet for additional information. For technical / application
assistance, call your nearest office.
Copyright ©Mamac Systems 2003. All rights reserved.
Mamac Systems reserves the right to change any specifications without notice to improve the
performance, reliability, or function of our products.
Table 1. Jumper Range Configurations
Range A B C
R1 0 to 5 0 to 10 0 to 20
R2 0 to 25 0 to 50 0 to 100
R3 0 to 75 0 to 150 0 to 300
R4 0 to 35 0 to 70 0 to 140
R5 0 to 175 0 to 350 0 to 700
R6 0 to 500 0 to 1000 0 to 2000
EUROPE AUSTRALIA
Baird House, Units 6 & 7
Dudley Innovation Centre
Pensnett Estate • Kingswinford
West Midlands • DY6 8XZ
United Kingdom
01384-271113 • Fax 01384-271114
4 Armiger Court, Unit 2
Holden Hill • S.A. 5088
Australia
08-8359-4333 • Fax 08-8395-4433
ASIA CANADA
No. 22 Lorong 21A Geylang
#11-02 Chin Hin Hang Building
Singapore • 388431
65-6392-7273 • Fax 65-6392-7276
155 Mcintosh Drive, Unit 5
Markham • Ontario • L3R 0N6
Canada
905-474-9215 • Fax 905-474-0876

Other MAMAC SYSTEMS Transducer manuals

MAMAC SYSTEMS PR-274 Manual

MAMAC SYSTEMS

MAMAC SYSTEMS PR-274 Manual

MAMAC SYSTEMS PR-264 Manual

MAMAC SYSTEMS

MAMAC SYSTEMS PR-264 Manual

MAMAC SYSTEMS EP-311 Series Manual

MAMAC SYSTEMS

MAMAC SYSTEMS EP-311 Series Manual

MAMAC SYSTEMS HU-224 User manual

MAMAC SYSTEMS

MAMAC SYSTEMS HU-224 User manual

MAMAC SYSTEMS PR-274 Manual

MAMAC SYSTEMS

MAMAC SYSTEMS PR-274 Manual

MAMAC SYSTEMS PR-264 Manual

MAMAC SYSTEMS

MAMAC SYSTEMS PR-264 Manual

MAMAC SYSTEMS PR-276 Manual

MAMAC SYSTEMS

MAMAC SYSTEMS PR-276 Manual

MAMAC SYSTEMS HU-224 User manual

MAMAC SYSTEMS

MAMAC SYSTEMS HU-224 User manual

MAMAC SYSTEMS PR-276 Manual

MAMAC SYSTEMS

MAMAC SYSTEMS PR-276 Manual

MAMAC SYSTEMS EP-313 User manual

MAMAC SYSTEMS

MAMAC SYSTEMS EP-313 User manual

MAMAC SYSTEMS PR-243 Manual

MAMAC SYSTEMS

MAMAC SYSTEMS PR-243 Manual

Popular Transducer manuals by other brands

bk ultrasound E14CL4b user guide

bk ultrasound

bk ultrasound E14CL4b user guide

Endress+Hauser iTEMP TMT82 Safety instructions

Endress+Hauser

Endress+Hauser iTEMP TMT82 Safety instructions

Balluff BTL7-P511-M Series user guide

Balluff

Balluff BTL7-P511-M Series user guide

Airmar TRIDUCER P39 Owner's guide & installation instructions

Airmar

Airmar TRIDUCER P39 Owner's guide & installation instructions

MG L2PNA instruction manual

MG

MG L2PNA instruction manual

Raymarine REALVISION 3D RV-3 Series installation instructions

Raymarine

Raymarine REALVISION 3D RV-3 Series installation instructions

Veris Industries PH Series installation instructions

Veris Industries

Veris Industries PH Series installation instructions

kries IKI-LUM 92 Assembly instructions

kries

kries IKI-LUM 92 Assembly instructions

JUMO HC103 operating instructions

JUMO

JUMO HC103 operating instructions

Eminent LINEAR FIELD Guide manual

Eminent

Eminent LINEAR FIELD Guide manual

Simrad ES333-7C -  REV A datasheet

Simrad

Simrad ES333-7C - REV A datasheet

S+S Regeltechnik PREMASGARD SHD Operating Instructions, Mounting & Installation

S+S Regeltechnik

S+S Regeltechnik PREMASGARD SHD Operating Instructions, Mounting & Installation

PCI FT-1003 Operation & maintenance manual

PCI

PCI FT-1003 Operation & maintenance manual

HESCH HE 5409 operating instructions

HESCH

HESCH HE 5409 operating instructions

Minebea TMOFB-NM Series instruction manual

Minebea

Minebea TMOFB-NM Series instruction manual

Sensor Technology TorqSense RWT430 Series user manual

Sensor Technology

Sensor Technology TorqSense RWT430 Series user manual

Thyracont B VSP63D Assembling instructions

Thyracont

Thyracont B VSP63D Assembling instructions

Hydac HLT 1100 Series user manual

Hydac

Hydac HLT 1100 Series user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.