MARTINDALE TEK100 User manual

TEK100/TEK100YE/TEK101
VOLTAGE INDICATOR
INSTRUCTION
MANUAL
ALWAYS READ THESE INSTRUCTIONS BEFORE PROCEEDING
Thank you for buying one of our products. For safety and full
understanding of its benefits please read this manual before use.
Technical support is available from 01923 441717 and
support@martindale-electric.co.uk
CONTENTS
1 Safety Information 1
1.1 Meaning of Symbols and Markings 1
1.2 Precautions 2
2 Introduction 4
2.1 Inspection 4
2.2 Description 4
2.3 Accessories 4
3 Operation 5
3.1 Self Test 5
3.2 Proving Check 5
3.3 Testing for the Presence of Voltage 6
3.4 Voltage Testing Considerations 6
4 Maintenance 8
4.1 Battery Replacement 8
4.2 Cleaning 8
4.3 Repair & Service 8
4.4 Storage Conditions 9
5 Warranty 9
Measurement Categories 10
Specifications
1. SAFETY INFORMATION: Always read before proceeding.
REMEMBER: SAFETY IS NO ACCIDENT
These instructions contain both information and warnings that are necessary
for the safe operation and maintenance of this product. It is recommended
that you read the instructions carefully and ensure that the contents are
fully understood. Failure to understand and to comply with the warnings and
instructions can result in serious injury, damage or even death.
Particular attention should be paid to the Warnings, Precautions and Technical
Specifications.
Please keep these instructions for future reference. Updated instructions and
product information are available at: www.martindale-electric.co.uk
1.1 Meaning of Symbols and Markings
Caution - risk of danger & refer to instructions
Caution - risk of electric shock
Equipment protected by double or reinforced insulation
(Class II)
CAT IV (Measurement Category IV) is applicable to test and measuring
equipment connected at the source of the building’s low-voltage
MAINS installation.
For further information on measurement categories see page 10 or
visit www.martindale-electric.co.uk/measurement_categories.php
Equipment complies with relevant EU Directives
End of life disposal of this equipment should be in accordance
with relevant EU Directives
1
2
1.2 Precautions
This product has been designed with your safety in mind, but
please pay attention to the following warnings and cautions before
use.
Warnings
In order to avoid the danger of electrical shock, it is important that
proper safety measures are taken when working with voltages
exceeding 30V AC rms, 42V AC peak or 60V DC.
Where applicable other safety measures such as use of protective
gloves, goggles etc. should be employed.
The voltage indicator must only be used by a skilled and competent
person who is familiar with the relevant regulations, the safety risks
involved and the consequent normal safe working practices, and is
capable of interpreting the results under the conditions and for the
purposes for which it has been constructed.
Before each use the unit should be examined for damage, cracks,
cuts or scratches. If there is any doubt the voltage indicator should
not be used.
Make sure the unit is dry, clean and free from dust, grease and
moisture while in use to avoid the danger from electric shock due
to surface leakage.
Before and after each use, the voltage indicator must be proven
using a suitable proving device or a known good voltage source.
Do not use the voltage indicator if any expected indication LED’s
fail to illuminate correctly during proving.
3
Testing for a voltage that exceeds the specified limits of the voltage
indicator may damage the unit and expose the operator to a shock
hazard. Always check the voltage indicator’s specified limits before
use.
The voltage indicator must only be used on CAT IV, CAT III and
CAT II installations up to 600V to earth, and within the operating
temperature and humidity range specified.
Do not use the voltage indicator if the battery casing is not fitted.
Always keep your fingers behind the finger guard.
The voltage indicator will not detect DC voltage.
Do not use the voltage indicator during rain or precipitation.
The voltage indicator must not be dismantled or modified in any
way by unauthorized persons. The safety of the voltage indicator
cannot be guaranteed under such circumstances and must not be
used.
Cautions
Avoid severe mechanical shock or vibration and extreme
temperature.
To avoid possible corrosion from a leaking battery, remove the
battery if discharged, or when the unit is not in use for an extended
period.
4
2. INTRODUCTION
2.1 Inspection
Examine the shipping carton for any sign of damage. Inspect the
unit and any accessories for damage. If there is any damage then
consult your distributor immediately.
2.2 Description
The TEK100 is a non-contact voltage indicator suitable for detecting
the presence of AC voltage in the range of 100V to 600V.
The TEK100/YE and TEK101 are designed to be less sensitive, and
detect the presence of AC voltage in the range of 180V to 600V.
The TEK101 has an extended probe tip for access to confined
spaces.
A self test circuit checks the functionality and battery of the voltage
indicator.
2.3 Battery Installation
Refer to Section 4.1 (Battery Replacement) for the battery
installation instructions for the TEK100, TEK100YE and TEK101.
5
3. OPERATION
3.1 Self Test
The self test checks the functionality and battery, a proving check
should always be performed prior to use.
Set the voltage indicator OFF/PROVE/VAC switch to PROVE and
check for the following:
The LED is continuously illuminated;
The
V
~LED is flashing;
There is an audible tone.
Set the OFF/PROVE/VAC switch to VAC and check that only the
LED is still continuously illuminated and the audible tone has
ceased.
Do not use the voltage indicator if either LED fails to illuminate or
the buzzer fails to sound.
If both LED’s and the buzzer do not function, replace the battery
(see section 4.1 Battery Replacement) and retest the unit.
3.2 Proving Check
Before and after use, verify the voltage indicator is functioning
correctly on a known good voltage source.
Do not use the voltage indicator if either of the LED’s fails to
illuminate or the buzzer fails to sound during proving.
Warning
If the voltage source exceeds the specified limits of the voltage
indicator the unit may be damaged and the operator exposed
to a shock hazard. Always check the voltage magnitude of the
voltage source before proceeding with a proving check.
6
3.3 Testing for the Presence of Voltage
Warning
Non-contact voltage indicators are not suitable to determine
if a circuit is not hazardous live. A double pole voltage test
should always be used for that purpose.
Grip the voltage indicator fully and firmly around the hand grip
to obtain optimum and consistent sensitivity. A loose grip during
testing may reduce the unit’s sensitivity.
Set the OFF/PROVE/VAC switch to VAC.
Taking all necessary safety precautions and referring to section
3.4, apply the voltage indicator probe tip to the cable or area you
wish to test for voltage.
When an AC voltage is detected the V
~LED will flash and the
buzzer will sound.
Switch the tester off when not in use to conserve battery power.
3.4 Voltage Testing Considerations
From some directions the neutral and earth conductors in cables
will shield the live, so it is important that a cable is probed from all
directions.
When testing for the presence of voltage in multi-core cables
always run the probe tip of the voltage indicator along a short
length of cable so as to overcome the natural twist in conductors.
Be aware that if the presence of AC voltage is not indicated,
voltage could still be present. The unit indicates active voltages
7
in the presence of electrostatic fields. If the field strength is low
the unit may not indicate. This could be due to factors such as:
Low mains voltage (<100V AC rms, <180V for the TEK100/YE
and TEK101)
Shielded wire/cables
Thickness and types of insulation
Distance from the voltage source
Low battery
If testing at locations with high background noise levels, always
determine whether the buzzer is perceptible before relying solely
on the buzzer indication.
8
4. MAINTENANCE
4.1 Battery Replacement
To avoid shock or injury, remove the voltage indicator from
the vicinity of any external circuits before proceeding.
To gain access to the battery compartment, undo the screw
securing the battery compartment cover and lift off the cover.
Fit a new 9V, PP3 alkaline battery (IEC 6LR61, NEDA 1604A).
Replace the battery cover and the screw.
4.2 Cleaning
To reduce the risk of surface leakage, this instrument must
be kept in a clean condition.
Prior to cleaning, remove the voltage indicator from the
vicinity of any external circuits before proceeding.
If contamination is found, clean with a damp soft cloth and if
necessary a mild detergent or alcohol. Do not use abrasives,
abrasive solvents, or detergents which can cause damage to the
unit. If a mild detergent is used, the unit should subsequently
be thoroughly cleaned with a water dampened soft cloth. After
cleaning, dry and allow to remain in a dry environment for 2 hours
before use.
4.3 Repair & Service
There are no user serviceable parts in this unit other than those
that may be described in section 4. Return to Martindale Electric if
9
faulty. Our service department will quote promptly to repair any fault
that occurs outside the guarantee period.
Before the unit is returned, please ensure that you have checked the
unit and battery.
4.4 Storage Conditions
The instrument should be kept in warm dry conditions away from
direct sources of heat or sunlight, and in such a manner as to
preserve the working life of the unit. It is strongly advised that the
unit is not kept in a tool box where other tools may damage it.
5. WARRANTY AND LIMITATION OF LIABILITY
This Martindale product is warranted to be free from defects in material
and workmanship under normal use and service. The warranty period
is 2 years and begins on the date of receipt by the end user. This
warranty extends only to the original buyer or end-user customer,
and does not apply to fuses, disposable batteries, test leads or to any
product which, in Martindale’s reasonable opinion, has been misused,
altered, neglected, contaminated, or damaged by accident or abnormal
conditions of operation, handling or storage.
Martindale authorised resellers shall extend this warranty on new and
unused products to end-user customers only but have no authority to
extend a greater or different warranty on behalf of Martindale.
Martindale’s warranty obligation is limited, at Martindale’s option, to refund
of the purchase price, free of charge repair, or replacement of a defective
product which is returned to Martindale within the warranty period.
This warranty is the buyer’s sole and exclusive remedy and is in lieu of
all other warranties, expressed or implied, including but not limited to any
implied warranty of merchantability or fitness for a particular purpose.
10
Martindale shall not be liable for any special, indirect, incidental or
consequential damages or losses, including loss of data, arising from
any cause or theory.
Since some jurisdictions do not allow limitation of the term of
an implied warranty, or exclusion or limitation of incidental or
consequential damages, the limitations and exclusions of this warranty
may not apply to every buyer. If any part of any provision of this
warranty is held invalid or unenforceable by a court or other decision-
maker of competent jurisdiction, such holding will not affect the validity
or enforceability of any other provision or other part of that provision.
Nothing in this statement reduces your statutory rights.
Specification
TEK100/TEK100YE/TEK101
Non-contact Voltage Indicator
Electrical
Voltage range: 100V to 600V AC rms (TEK100)
180V to 600V AC rms (TEK100YE & TEK101)
Frequency range: 45Hz to 1kHz
Voltage sensitivity: see table 1
Table 1. Typical Sensing Distances for Energised Cables at 50Hz
Cable Type
TEK100 TEK100YE &
TEK101
at 115V at 230V at 230V
Flat 1mm
2
twin & earth 3mm 23mm 3 mm
Flat 2.5mm
2
twin & earth 5mm 23mm 3 mm
Round 1.5mm
2
2mm 18mm 2 mm
Environmental
Temperature (Operating & Storage): -10°C to 40°C.
Humidity (Operating & Storage): d85% R.H.
Altitude: up to 2000m
Pollution degree: 2
General
Power: 9V, PP3 alkaline battery (IEC 6LR61, NEDA 1604A)
Current consumption: 34mA max
Dimensions: 205 x 36 x 25 mm
Weight: approx. 120g (battery included)
Includes: 9V PP3 battery, instructions
Safety
Conforms to BS EN61010-1 CAT IV 600V (TEK100 & TEK100/YE)
CAT IV 1000V (TEK101)
Class II, double insulation
EMC
Conforms to BS EN61326-1
Specification
TEK100/TEK100YE/TEK101
Non-contact Voltage Indicator
17th Edition Testers
Accessories
 Calibration Equipment
Continuity Testers
Electricians’ Kits
Environmental Products
Full Calibration & Repair Service
Fuse Finders
Digital Clamp Meters
Digital Multimeters
Labels
Microwave Leakage Detectors
Motor Maintenance Equipment
Multifunction Testers
Non-trip Loop Testers
Pat Testers & Accessories
Phase Rotation Testers
Proving Units
Socket Testers
Thermometers & Probes
Test Leads
Voltage Indicators
Specialist Metrohm Testers (4 & 5kV)
Specialist Drummond Testers
Check out what else you can get from Martindale:
Martindale Electric Company Limited
Metrohm House, Penfold Trading Estate, Imperial Way, Watford WD24 4YY, UK
Tel: +44 (0)1923 441717 Fax: +44 (0)1923 446900
E-mail: [email protected]
Website: www.martindale-electric.co.uk
© 2014 Martindale Electric Company Ltd.
Registered in England No. 3387451. Rev 7 LIT100

This manual suits for next models

2

Other MARTINDALE Measuring Instrument manuals

MARTINDALE CM69 User manual

MARTINDALE

MARTINDALE CM69 User manual

MARTINDALE CM82 User manual

MARTINDALE

MARTINDALE CM82 User manual

MARTINDALE CB12 User manual

MARTINDALE

MARTINDALE CB12 User manual

MARTINDALE SP75 User manual

MARTINDALE

MARTINDALE SP75 User manual

MARTINDALE FD650/R User manual

MARTINDALE

MARTINDALE FD650/R User manual

MARTINDALE VI13700G User manual

MARTINDALE

MARTINDALE VI13700G User manual

MARTINDALE CMi210 User manual

MARTINDALE

MARTINDALE CMi210 User manual

MARTINDALE DH85 User manual

MARTINDALE

MARTINDALE DH85 User manual

MARTINDALE FD500 User manual

MARTINDALE

MARTINDALE FD500 User manual

MARTINDALE AV90 User manual

MARTINDALE

MARTINDALE AV90 User manual

MARTINDALE PSI4000 User manual

MARTINDALE

MARTINDALE PSI4000 User manual

MARTINDALE AV85 User manual

MARTINDALE

MARTINDALE AV85 User manual

MARTINDALE LM195 User manual

MARTINDALE

MARTINDALE LM195 User manual

MARTINDALE VR2230 Operator's manual

MARTINDALE

MARTINDALE VR2230 Operator's manual

MARTINDALE VI13800 User manual

MARTINDALE

MARTINDALE VI13800 User manual

MARTINDALE CM58 User manual

MARTINDALE

MARTINDALE CM58 User manual

MARTINDALE PM85 User manual

MARTINDALE

MARTINDALE PM85 User manual

MARTINDALE CM79 User manual

MARTINDALE

MARTINDALE CM79 User manual

MARTINDALE VR2250 Operator's manual

MARTINDALE

MARTINDALE VR2250 Operator's manual

MARTINDALE LM192 User manual

MARTINDALE

MARTINDALE LM192 User manual

MARTINDALE CO90 User manual

MARTINDALE

MARTINDALE CO90 User manual

MARTINDALE FD500 User manual

MARTINDALE

MARTINDALE FD500 User manual

MARTINDALE LM82 User manual

MARTINDALE

MARTINDALE LM82 User manual

MARTINDALE CT60 User manual

MARTINDALE

MARTINDALE CT60 User manual

Popular Measuring Instrument manuals by other brands

Tektronix PRISM user manual

Tektronix

Tektronix PRISM user manual

wtw Oxi 330i operating manual

wtw

wtw Oxi 330i operating manual

BRONKHORST mini CORI-FLOW ML120 instruction manual

BRONKHORST

BRONKHORST mini CORI-FLOW ML120 instruction manual

Boonton 92BD instruction manual

Boonton

Boonton 92BD instruction manual

Addi-Data MSX-E3711 Quick installation

Addi-Data

Addi-Data MSX-E3711 Quick installation

BRONKHORST FLOW-CONTROL Series instruction manual

BRONKHORST

BRONKHORST FLOW-CONTROL Series instruction manual

Keison PFP7 Operating and service manual

Keison

Keison PFP7 Operating and service manual

LaserLiner ThermoMaster operating instructions

LaserLiner

LaserLiner ThermoMaster operating instructions

Seca 287 Instruction manual and guarantee

Seca

Seca 287 Instruction manual and guarantee

ROHDE & GRAHL R&S ZPH Series manual

ROHDE & GRAHL

ROHDE & GRAHL R&S ZPH Series manual

Sper scientific 840012 instruction manual

Sper scientific

Sper scientific 840012 instruction manual

Fluidwell F127-P-EL-TP manual

Fluidwell

Fluidwell F127-P-EL-TP manual

CAI 600 Series user manual

CAI

CAI 600 Series user manual

Endress+Hauser Levelflex FMP50 operating instructions

Endress+Hauser

Endress+Hauser Levelflex FMP50 operating instructions

Parkwood KXer-Single manual

Parkwood

Parkwood KXer-Single manual

sauter FK Series instruction manual

sauter

sauter FK Series instruction manual

Hach TitraLab Basic user manual

Hach

Hach TitraLab Basic user manual

DISTELL Fish Fatmeter quick start guide

DISTELL

DISTELL Fish Fatmeter quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.