
convenient location in a listed outlet box with
approved strain relief.
3.06.4
NOTE:
A remote switch, if installed,
will operateonly if the local On/Off switch on the
face of the inverter is turned "On". You may use
several switches or relays in parallel in lieu of one
remote switch.
3.07 120 VAC / 240 VAC Output
3.07.1
CAUTION:
Do not connect another
source of AC power directly to the output of the
inverter.This will result in damage to the inverter
that is not covered under warranty!
3.07.2The 120 VAC output of the inverter is
provided at the GFCI receptacle outlet on the
inverter.
3.07.3 The dual output 120 / 240 VAC is
presented behind the wiring compartment panel
for direct hardwire wire leads. The two black wires
are hot (use one black for 120 VAC), the white wire
is neutral and the green wire is ground. The cable
clamp strain relief should be used to secure the field
wires.
3.07.4 The hardwire A.C. output is not
ground fault circuit interrupt, (GFCI) protected.
GFCI outlets should be installed at all appropriate
locations per NEC 551. The GFCI outlet should be
Leviton, Model 6599 or UL listed equivalent. The
GFCI outlet should be Hubbell GFR5352XX (20A)
or GFR5252XX (15A).
3.07.5 The remote AC outlets should be
mounted at a convenient location in a listed outlet
box with approved strain relief.
4. START UP/OPERATION
4.01To operate the inverter, turn the switch to
“ON”. Assure that the output breakers are reset.
Ifthe remote switch is used, the inverter is turned
“On” or “Off” by the remote switch.
5. CUSTOMER SERVICE
TROUBLESHOOTING
5.01 MDS power offers free phone consulta-
tionconcerninginstallationortroubleshooting. Call
the Customer Service Department at:
1-800-931-4919 or 1-514-369-4919.
Fax: 1-514-369-4817
5.02 If the inverter fails to operate, use the
following troubleshooting procedure.
5.02.1 Connecta100wattlightbulbto the
inverter output.
5.02.2 Make sure that the inverter is
turned “On”, and the circuit breakers are reset.
5.02.3 Check the connection to the
remoteswitch,ifused. +24VDC mustbepresent
at the violet wire for the unit to operate. If not,
check any fuses in the remote switch circuit.
5.02.4 Observe the fault indicating lights
on the front of the inverter.
a) The Low input voltage light indicates a
low batterycondition.Switchtheinverter“Off”for
5 seconds, then “On” again. The light coming on
again indicates a fault in the battery wiring, bat-
tery capacity and voltage or the line fuse.
b) The Overload light indicates an output
wiringshortcircuitoraloadthatistoolargeforthe
power rating of the inverter. Switch the inverter
“Off”, remove the short circuit or excessive load
from the output, then switch the inverter back
“On”. c) The High temperature light indicates the
inverter has overheated. The unit will automati-
cally turn back on when it has cooled to 400C.
Verify that the inverter is not in a closed compart-
ment and that the fan is not blocked.
5.03 Call MDS Power, Inc. for technical assis-
tance and/or a return authorization number if the
abovestepsarecompletedandtheinverterstillwill
not operate satisfactorily.
Page 4