MERAWEX ZUP-230V User manual

User Manual ZUP-230V + ZSP121N-DR Nr dok. 0697.00.95-12.0
MERAWEX Sp. z o.o.
ul. Toruńska 8
44-122 Gliwice, Poland
tel. +48 32 23 99 400
fax +48 32 23 99 409
e-mail: m[email protected].pl
http://www.merawex.com.pl
USER MANUALS FOR POWER SUPPLY ZUP-230V
The document contains:
USER MANUAL
Power supply for fire alarm devices, heat and smoke control systems, fire protection and fire
automation systems.
ZUP-230V-400, ZUP-230V-700, ZUP-230V-1000, ZUP-230V-1500
and
USER MANUAL
Power supply for fire alarm devices, heat and smoke control systems, fire
protection devices and fire automation
ZSP121N-DR
designed to operate with the power supply ZUP-230V
14.05.2018

User manual ZUP-230V Nr dok. 0697.00.95-02.3 1/15
MERAWEX Sp. z o.o.
Toruńska 8
44-122 Gliwice, Poland
tel. +48 32 23 99 400
fax +48 32 23 99 409
e-mail: m[email protected].pl
http://www.merawex.com.pl
USER MANUAL
Power supply for fire alarm devices, heat and smoke control systems, fire protection and fire
automation systems.
ZUP-230V-400, ZUP-230V-700, ZUP-230V-1000, ZUP-230V-1500
Meeting the EN 54-4 and EN 12101-10
Certificate of constancy of performance CNBOP No. 1438-CPR-0593
Certificate of admittance CNBOP No. 3183/2018
14 May 2018
Technical description......................................................................................................2
1.1. Application................................................................................................................................2
1.2. Technical data. .........................................................................................................................3
Construction. ..................................................................................................................4
Functioning of outputs. ...................................................................................................6
Description of 230Vac distribution packet of ZUP power supply......................................9
Installation....................................................................................................................10
5.1. General notes........................................................................................................................ 10
5.2. Connecting mains.................................................................................................................. 11
5.3. Connection of external AC output circuits ............................................................................. 11
5.4. Connection of additional outputs........................................................................................... 11
5.5. Connection of battery bank.................................................................................................... 11
5.6. Connection of alarm input from fire alarm control panel (CSP)............................................. 12
5.7. First start................................................................................................................................ 12
5.7.1. Starting power supply.................................................................................................... 12
5.7.2. Checking basic functions............................................................................................... 13
5.7.3. Setting time.................................................................................................................... 14
Additional information...................................................................................................14
6.1. Manufacturer's notes ............................................................................................................. 14
6.2. Proceeding with packaging, used products and batteries..................................................... 14

User manual ZUP-230V Nr dok. 0697.00.95-02.3 2/15
Warnings
▪Before using the device, carefully read this User Manual.
▪Do not touch the internal components of the operating device - risk of electric shock or
burns.
▪Protect the device against any objects or liquids entering it - risk of electric shock and
damage to the device.
▪Do not obscure the ventilation openings - it can damage the device.
▪Provide at least free space of at least 10cm on the sides of the device allowing proper
ventilation.
▪It is forbidden to transport the device with mounted and connected batteries.
▪The device must be powered from the mains with a protective earth terminal.
▪The device may affect the operation of sensitive radio and television equipment located
nearby
Technical description.
1.1. Application.
The ZUP-230V battery backup power supply provides the 230V uninterruptible voltage from the
mains or after its failure, from the DC/AC 230Vac inverter powered from the internal 24V battery bank.
During power failure, the total power is taken from the battery, its presence and efficiency is an
essential element of the power supply’s operation.
The power supply is not an UPS. Most fire protection devices supplied with 230V voltage during
supervision stay in standby mode - no power is consumed. The organization of the power supply’s
work takes into account this fact by setting specific time periods of the inverter's activity, while it takes
energy from the battery. Apart from those time periods the battery is relieved while waiting for a fire
alarm. This allows to extend the supervision time to 72h while maintaining the readiness to operate
powered devices with full power (depending on the type 400 ÷ 1500W).
The power supply enables 230V voltage distribution among 4 various types of receivers requiring
taking, switching or disconnection of power at a given time, depending on a function being performed,
after receiving a signal from outside (e.g. fire alarm). Response times for individual types of outputs
can be set by a user in a wide range by using slide switches. The main application of the ZUP-230V
power supplies includes:
•aeration gates;
•shunt trips of fire protection circuit breakers;
•self-locking, two-way actuators of shutting off dampers of fire ventilation;
•drives of the fire zone separating gates;
•spring actuators of fire protection shutting off dampers;
•blinds of ceiling smoke tanks;
•smoke exhaust fans running after a shutting off damper goes to the opening position;
•self-locking, two-way actuators of fire protection shutting off dampers, closed when a fan
stops;
•devices started in a cascade sequence to reduce the inrush current.
In addition, the 24Vdc uninterruptible voltage of 100W is available to supply other fire protection
devices.
The power supply meets the requirements of the EN 54-4: 2001 + A1: 2004 + A2: 2007 and EN
12101-10: 2007 and the Ordinance of the Ministry of Interior and Administration of the 20 June 2007,
the Book of Acts No. 143 item 1002, with an amendment No. 85 item 553 of 27/04/2010.
In addition, the power supply meets the requirements of the Regulation of the European
Parliament and the Council of Europe (EU) No. 305/2011 of the 9 March 2011. (CPR - Construction
Product Regulation).

User manual ZUP-230V Nr dok. 0697.00.95-02.3 3/15
1.2. Technical data.
Basic operating parameters of power supplies.
EN 54-4
Max. battery
capacity
Imax_a
Imax_b
230Vac
24Vdc
230Vac
24Vdc
ZUP-230V-400
45Ah
400 W
2.0 A
400 W
3.5 A
ZUP-230V-700
45Ah
700 W
1.9 A
700 W
3.3 A
ZUP-230V-1000
45Ah
1000 W
1.7 A
1000 W
3.2 A
ZUP-230V-1500
75Ah
1500 W
0.4 A
1500 W
3.0 A
EN 12101-10
Max. battery
capacity
Imax_a
Imax_b
230Vac
24Vdc
230Vac
24Vdc
ZUP-230V-400
45Ah
0 W
0.33 A
400 W
3.5 A
ZUP-230V-700
45Ah
0 W
0.26 A
700 W
3.3 A
ZUP-230V-1000
45Ah
0 W
0.15 A
1000 W
3.2 A
ZUP-230V-1500
75Ah
0 W
0.41 A
1500 W
3.0 A
Holes inthe
cabinet's bottom
ZUP-230V 8
Dimensions and weight
A
B
C
D
E
F
G
Weight with
battery
ZUP-230V-400 -700 -1000
455
406
207
438
310
360
410
42 kg 45Ah
ZUP-230V-1500
555
456
207
488
410
410
470
65 kg 75Ah
Fig.1. Dimensions and placement of mounting holes of ZUP-230V power supplies.
Basic electrical and environmental parameters.
Power
Mains voltage
230V - 25% +10% 50Hz
Outputs 230Vac *1)
Output voltage 230Vac
- when mains present *2)
- when mains absent *2)
equals to mains voltage
230V ±3% 50Hz *3)
Fuses on each output
5x20mm 6.3AF
Output 24Vdc
Rated voltage of output 24Vdc *4)
27.1V
Range of voltage changes 24Vdc *5)
21…28.8V
Battery bank
Maximum battery charging current
- battery of 45Ah
- battery of 47Ah
1.7A
2.8A
Quiescent current consumption from battery
- when inverter is operating
- when inverter is off
0.78A/400W, 0.93A/700W,
1.08A/1000W, 1.33A/1500W
26mA

User manual ZUP-230V Nr dok. 0697.00.95-02.3 4/15
- after disconnection of discharged battery
0.33mA
Maximum, additional resistance in battery circuit Ri max. *6)
25mΩ/45Ah; 19mΩ/75Ah
Environment
Operating temperature
-5…+40°C
Level of security EN 60529:2003
IP 42
*1) The power and output circuits of 230Vac have the common conductor N.
*2) The presence of the mains voltage is recognized for the voltage of above 184V ±11V.
*3) The voltage is not synchronized with the mains voltage.
*4) With a battery charged at 25
C.
*5) The specified range includes the voltage between the voltage of the discharged battery bank (at the end of the
battery cycle) and the voltage of the bulk charging.
The detailed description of the ZSP121N-DR power supply operation is included in a separate User Manual.
*6) The markings according to the EN 54-4 + A1 + A2 standard
Standards compatibility
Electrical safety
EN 60950-1:2007 + A1:2011 class I
Functionality
EN 54-4:2001 + A1:2004 + A2:2007
Functionality class
EN 12101-10:2007 class A
Environmental class
EN 12101-10:2007 class 1
Radio disturbances
EN 55022:2013 class B
EMC immunity
EN 50130-4:2012 + A1:2015
EMC emission
EN 61000-3-2:2007 + A1:2010 + A2:2010
EN 61000-3-3:2011
Construction.
Power supply assembly
Equipment
Quantity
Notes
Power supply ZUP-230V
1
Battery bank 12V
2
Capacity depends on type of power supply
Temperature sensor
1
For power supply ZSP121N-DR
Cable (connector) of battery bank
1
Equipped with 2 ring cable lugs Ø6
Glands M16×1.5
2
Quantity can be changed when ordering
Glands M20×1.5
3
Quantity can be changed when ordering
Note
The power supply casing has holes protected with glands prepared for mechanical removal during
assembly:
•in the upper part for 5 M16 × 1.5 glands and 7 M20 × 1.5 glands;
•in the lower part for 3 M16 × 1.5 glands and 5 M20 × 1.5 glands.
The possible location of all glands on the power supply casing is shown in Fig.1.
The simplified diagram of the power supply is shown in Fig.2. The power supply includes:
•main 230Vac power distribution block (ZUP);
•24Vdc/230Vac inverter;
•24V battery bank;
•ZSP121N-DR power supply, basic function of which is charging and supervision of the
battery bank and powering 230V power distribution block.

User manual ZUP-230V Nr dok. 0697.00.95-02.3 5/15
Fig.2. Simplified diagram of ZUP-230V power supplies.
The 230V power distribution block (ZUP) switches the power outputs of the AC-1, AC 2, AC-3 and
AC-4 external devices in accordance with their functions, while supplying the voltage from mains
(230Vac power) or from the inverter in the event of power failure. Each output is equipped with its own
fuse.
The diagram shows exemplary connection of the external device (ACTUATOR # 1) from the AC-3
output.
The suitable action of switching outputs and power is initiated independently when power failure or
it can be forced by a fire alarm signal (CSP input). The input can be operated from multiple locations
after setting the line control mode. You can also disable the line control mode, forcing a simple two-
state operation.
The correct supply of the whole packet is indicated by the green LED OPERATION.
The power supply inverter operates continuously, which reduces the time it takes to switch from the
mains to the battery operation mode. Its starting and backup operation takes place from the ZSP121N-
DR power supply output. Then the ZINW-1 connector and the corresponding yellow LED on the ZUP's
power supply packet are on.
In case of necessity of loading the inverter (e.g., when power failure), its power is switched directly
onto the battery bank. The ZINW-2 connector is connected and the corresponding red LED on the
power supply packet are on.
Such the way of operation allows for independent supervision of the battery bank; its charging,
voltage and current measurement, resistance measurement and battery circuit continuity monitoring.
The inverter is connected directly to the battery only when significant current is required. It is also
possible to completely disconnect it after discharging the battery, which prevents it from damage.
The ZSP121N-DR power supply, in addition to the functions related to supervision of the battery
and powering the electronic circuits, allows for connecting additional external devices powered with
24V (OUT1 output) and for output of the binary signal (relay outputs), general fault (GEN FLT) and

User manual ZUP-230V Nr dok. 0697.00.95-02.3 6/15
mains power failure indication (MAINS FLT). In addition, the power supply can take one external fault
signal (EXT FLT).
In standard, the power supply also take a signal on its INT FLT input on a fault from the ZUP power
supply packet (outbound output) by transferring it to the general fault indication output (GEN FLT). The
power supply also triggers the LED indication on the box door. The green LED MAINS indicates the
presence of the mains power and the yellow LED FAULT is on simultaneously with the GEN FLT
signal indication.
The detailed description of the ZSP121N-DR power supply operation is included in its separate
User Manual.
Note
On the cabinet doors instead of the MAINS and FAULT descriptions, the following pictograms can
be used, respectively: and
Functioning of outputs.
Note
The basic operation of the 230 V outputs of the ZUP-230V power supply has been described
below. It is possible, after prior arrangement, to produce such a version, in which outputs will present
other time dependencies and in particular, several outputs will have the same functionality. This allows
for direct connection of several loads, which should be powered in the same way.
Output AC-1
The AC-1 output is intended for devices that after a power failure and during a fire alarm require
maintaining the 230V voltage for some time, e.g.:
- aeration gate drive (activated by a separate fire alarm signal, but it requires 230V power to
operate);
- shunt trips of fire protection circuit breaker (it is activated manually with a button, but requires
the 230V power to operate).
Fig.3. Voltage timings for AC-1 output.
The voltage at the AC-1 output is always present when the mains voltage is present and for a
preset T1 time after its disappearance and additionally during a fire alarm in the absence of the mains
power for the T2+T3 time. When switching from the mains power to the inverter operation and vice
versa, the output has a temporary voltage drop (about 150ms).
If the fire alarm occurred already after the inverter turned off (the T1 time counted down), the
inverter restart takes place with some delay: 2s is the time to recognize the alarm occurrence and the
next 10s is the time needed to start the inverter
Description of times that can be set by a user.
A detailed way of setting times is provided in point 5.7.3.
The time T1 can be set from 1 minute up to 8 hours, which also determines the maximum time of
battery operation after power failure
The time T2 can be set from 1 up to 6 minutes and from 1 up to 6 hours, which also determines the
maximum time of activity of the power supply after a fire alarm. If a fire alarm occurred during the
countdown of the T1 time, i.e. after the mains power failure, the countdown of the T1 time is
MAINS POWER
FIRE ALARM
OUTPUT AC-1
T1
~150ms
~2s
T2+T3
~10s
Operating from
MAINS
Operating from
BATTERY
Operating from
BATTERY

User manual ZUP-230V Nr dok. 0697.00.95-02.3 7/15
interrupted and the countdown of the T2 time begins.
The time T3 results from the operation of the AC-4 output and it can range from 5 up to 65s.
Warning. Separate use of T2 and T3 times is included in the AC-4 output description.
Outputs AC-2A and AC-2B
The AC-2 output is intended for devices whose state is switched by a fire alarm signal, e.g.:
- self-locking, two-way actuator of shutting off damper of fire ventilation;
- drive of the fire zone separating gate;
or that can be activated during the fire alarm, e.g.:
- aeration or smoke exhaust fan switched on during a fire
Fig.4. Voltage timings for AC-2 output.
A fire alarm causes voltage loss at the AC-2A output (if present, i.e. when the mains present) and
the appearance of voltage at the AC-2B output (regardless of whether the mains is present). The
voltage on this output is maintained for a certain period of time T2+T3 (see the description of the times
of the AC-1 output), so that the actuator can change its state.
The response to a fire alarm always takes place with a delay of ~2s required for its correct
recognition. If a fire alarm occurred with the inverter turned off, it will be restarted with an additional
delay of about 10s.
Return to the safe position, i.e. the correct position before the fire alarm occurs (voltage present at
the AC-2A output and no voltage at the AC2-B output), is possible when the mains power present and
when is no fire alarm.
Output AC-3
The AC-3 output is intended for devices whose condition is backed-up by means of the external
power source and, which after a fire alarm appears, independently switch in a safe position by
switching it off, e.g.:
- spring actuator of fire damper;
- blind of ceiling smoke tank.
OUTPUT AC-2A
OUTPUT AC-2B
3
T2
+
T
T2+T3
~2s
~10s
~2s
MAINS POWER
FIRE ALARM
Operating from
MAINS
Operating from
BATTERY

User manual ZUP-230V Nr dok. 0697.00.95-02.3 8/15
Fig.5. Voltage timing for AC-3 output.
If the voltage was present at the AC-3 output, it disappears after a fire alarm occurred for its
duration, but not shorter than T2+T3 (see the description of the times of the AC-1 output). The
response to a fire alarm always takes place with a delay of ~2s required for its correct recognition. The
voltage recovery at the AC-3 output is possible when the mains present and when is no fire alarm. The
voltage on this output is additionally maintained also after the mains power failure in the absence of a
fire alarm, so as not to unnecessarily move the devices to the position appropriate for the fire alarm
only due to the power failure. The voltage maintenance in this state is limited by the maximum battery
life T1.
When switching from the mains to the inverter operation, there is a temporary voltage drop on the
output (about 150ms).
Outputs AC-4A and AC-4B
The AC-4 output is intended for devices that should start operating with some delay after a fire
alarm, e.g.
- smoke exhaust fan, which can be activated only after passing the shut-off valve to the fully
open position;
- self-braking, two-way actuator of fire ventilation shutting-off damper, which should close the
damper only after stopping the fan.
- cascade-operated devices to reduce the inrush current.
Fig.6. Time waveforms for AC-4 output.
The AC-4 output has the AC-2 output functionality. The only difference is the additional delay in
switching after the fire alarm is recognized by the T3 time (see the description of the times for the AC-
1 output).
The response to a fire alarm always takes place with a delay of ~2s required for its correct
recognition. If the fire alarm occurred with the inverter turned off, it will be restarted with an additional
delay of about 10s.
OUTPUT AC-3
T2+T3
T1
~150ms
~2s
MAINS POWER
FIRE ALARM
OUTPUT AC-4A
OUTPUT AC-4B
T2
~2s
T3
T2
~2s
~10s
T3
MAINS POWER
FIRE ALARM
Operating from
BATTERY
Operating from
MAINS
Operating from
BATTERY

User manual ZUP-230V Nr dok. 0697.00.95-02.3 9/15
Description of 230Vac distribution packet of ZUP power supply.
L
H
ALCSP
P541.2
AC-1
AC-3
AC-2
AC-4
L N PE
L N
4A AC-4B N
230V
T2+T3
IN W
ALP
+ -+ -+ -
T2: m in
123h5 302010
T3: s
T1: h
1 2 53010521 T1: m in
CSP PARAM
ON OFF
2A AC-2B N AC-3 N AC-1 N
G201
ZAS ZSP
CSPWYUSZ
PE
ZSTTEST
PROG
ZAS
WY INW ZAS 230V
PRACA
ZINW-2
ZINW-1
1 2 5 6
ON
3 4 7 8
1 2 5 6
ON
3 4 7 8
+INW
+AKU
Fig.7. View of 230Vac distribution packet of ZUP-230V power supplies.
Description of 230Vac distribution packet components.
Designation
Description
Connectors
ZAS 230V
230Vac mains power input (*)
WY INW
230Vac inverter output (*)
AC-1, AC-2
AC-3 AC-4
Outputs for powering external devices and their corresponding fuses.
PE
Additional contact (connector) of the PE mains (unused).
ZAS ZSP 230V
Additional 230Vac mains output (unused).
PROG
UP programming connector (do not connect!)
G201
Digital communication connector (do not connect!).
WYUSZ
Fault output signal - isolated OC output (connection with ZSP121N-DR power
supply) (*)
- CSP line fault after 90s;
- battery voltage below 24V;
- no voltage at the inverter output after 8s.
CSP
Fire alarm signal input from the Fire Alarm Control Panel:
- alarm state must last longer than 2s;
- see CSP PARAM and AL CSP.
ZAS
External 24Vdc power (*)
+INW
Positive power bus of inverter. (*)
+AKU
Positive pole of battery bank. (*)
Buttons
TEST
Button for testing power supply (simulating a fire alarm):
- power supply reacts when button is pressed for longer than 2s;
- the button allows to shorten T2+T3 (see LED T2+T3), but only after fire alarm.
ZST
The button allows you to start power supply from battery ("cold start"):
- see point 5.7.1
Switches
CSP PARAM
Switch enabling parameterization of CSP input:

User manual ZUP-230V Nr dok. 0697.00.95-02.3 10/15
- ON parameterization is required (10kΩ||1kΩ);
- OFF parameterization is not required (ordinary binary input);
- factory setting: OFF
AL CSP
Jumper setting active state of CSP alarm:
- jumper in L position or its absence: fire alarm active in low state;
- jumper in H position: fire alarm active in high state;
- factory setting: L
T1 min, T1 h
Slide switch setting T1 time:
- sum of individual settings: 1, 2, 5, 10, 30min and 1, 2, 5h;
- factory setting: see section 5.7.3
T2 min/h
Slide switch setting T2 time:
- sum of individual settings: 1, 2, 3 and unit selection: min or h;
- factory setting: see section 5.7.3
T3 s
Slide switch setting T3 time:
- sum of individual settings: 5, 10, 20, 30s;
- factory setting: see section 5.7.3
LED signalization
ZINW-1
Signalization of connection of inverter to ZSP121N-DR power supply (yellow
LED).
ZINW-2
Signalization of connection of inverter directly to battery (red LED).
PRACA
Mains power signalization (green LED).
INW
Inverter operation signalization (green LED):
- off: inverter is not working (no voltage at its 230Vac output);
- flashing: inverter power voltage too low (below 24V), inverter operating;
- on: mains voltage correct, inverter operating;
- blinking: no battery or mains voltage too low (below 22V)
ALP
Signalization of fire alarm (red LED):
- off: no alarm;
- on: fire alarm has occurred (also when TEST button was used);
- flashing: line fault of fire alarm input from the CSP detected .
T2+T3
T2 and T3 countdown start signalization (yellow LED):
- it is possible to finish countdown of these times faster by means of TEST button.
(*) Connections made by the power supply manufacturer.
Installation.
5.1. General notes.
The place where the power supply should be installed should be chosen so as not to expose it to
the mechanical damage, and to not exceed the permissible parameters of temperature and air
humidity. If possible, the power supplies should be installed in fire-partitioned areas (e.g. electrical
switchboards, technical rooms, cable shafts, etc.).
The power supply cabinet can be attached directly to the wall through the four holes in its rear wall
or with four spacers. The location of the fixing holes is shown in Fig.1. Use metal bushings and steel
screws for mounting. PVC dowels should not be used. In the case of direct hole mounting in the rear
wall of the cabinet, it is advisable to remove the inverter first by loosening the two nuts at its bottom,
slightly deflecting it and sliding it downwards.
The accumulator bank, due to its weight and dimensions, should be placed in the cabinet as the
last element; after all cable connections have been made.
Note.
The selection of wires in power and control systems for the fire protection equipment should take
into account the §187 of the Regulation of the Minister of Infrastructure of March 12, 2009 (Journal of
Laws No. 56, item 461) regarding technical conditions for buildings and their location, together with
later changes.

User manual ZUP-230V Nr dok. 0697.00.95-02.3 11/15
5.2. Connecting mains
The mains power cable with a minimum cross-section of 3×1.5 mm2, after passing through one of
the glands in the casing of the power supply, should be connected to single-track connectors, as
shown in the Fig.2.
Note.
The mains connection must be made as a permanent installation with the continuity of the neutral
line (N). The installation switch described below must be in the active line (L).
The power supply is not equipped with its own mains switch, therefore it is required to use a special
installation switch outside the power supply. The switch should also be used as an overload and short-
circuit protection device and allow to power the devices of high inrush current. We recommend using
the S301 C16A installation switch. This switch should be clearly marked as being used in the fire
system and cannot be used simultaneously in other circuits.
Warning.
Switching on the mains with a switch located outside the power supply can only be performed with
the fully assembled internal cabling of the power supply unit, including the connected and correctly
installed inverter. It is unacceptable to leave the 230Vac power plug disconnected from the inverter
output.
5.3. Connection of external AC output circuits
The external connections cables should be run through the selected holes in the cabinet's body
(after removing the jumpers) and fastened by twisting the appropriate glands. The cables to be
connected to the AC-1, AC-2, AC-3 and AC-4 outputs, after fixing them in the glands, should be led in
a large arc in the inverter plane before they are fixed by cable holders and connected to appropriate
terminals of the ZUP power supply . The external cable insulation should be removed directly behind
the cable holder. To make the connections of 230Vac power in the fire protection systems, 3-wire
cable of the HDGs type 1.5mm2 is recommended. For devices made in the 2nd class of insulation, it is
possible to use 2-wire cables, without using the connection with the PE bus bar.
Several loads can be connected to the power supply at the same time. The sum of their power
cannot, however, exceed the maximum power indicated for a given execution device. Attention should
be paid to the nature of the load provided by some loads. For example, induction motors can take
significant current when starting, which can lead to a blown fuse placed on a given output or prevent
proper start of the inverter. In this case, it is possible to use a soft starter system (so called soft-
starter), for example, the ZUP-MS type of the MERAWEX. However, a user is asked to consult the
manufacturer, due to different nature of loads, which may require setting individual device operation
parameters.
5.4. Connection of additional outputs
These connections concern the outputs of the ZSP121N-DR power supply shown in Fig.2. It should
be noted that all signal outputs and inputs are referenced to the negative output terminal of the power
supply. A detailed description of the outputs of this power supply is included in a separate User
Manual.
From the output OUT1 of the ZSP121N-DR power supply, only current of the values described in
the table Basic operating parameters of power supplies can be taken (point 1.2 Technical data).
5.5. Connection of battery bank
The battery bank, placed with its terminals from the side of the casing door, should be connected
with two cables that are already led out of the power supply, paying particular attention to the polarity:
red cable to the positive pole of one battery, blue to the negative of the second one. Finally, connect
the both batteries with each other, by means of the cable (connector) provided by the manufacturer.
Incorrect connection can lead to destruction of the power supply.
The battery should be connected with the battery disconnector switched off and its fuse removed.
Although each of the component devices (the ZSP121N DR power supply, ZUP and inverter) has its

User manual ZUP-230V Nr dok. 0697.00.95-02.3 12/15
own fuse, the common disconnector enables reliable disconnection of the battery from the entire
power supply.
All connections should be made carefully, remembering that during the battery operation (when no
mains power) the current consumed by the inverter can reach up to 80A.
In order to properly compensate for the temperature of battery floating voltage, the temperature
sensor of the ZSP121N-DR power supply should be placed between the side walls of the both
batteries.
5.6. Connection of alarm input from fire alarm control panel (CSP).
The fire alarm input from the CSP can be set both in the operating mode with parameterization in
which the resistance of the signal line is monitored during both the supervision and alarm time as well
as in the normal binary input operation mode. In both cases, however, it is required that the
parameters of the control circuit be within certain specified limits:
- for the input with parameterization of the resistance value, taking into account the resistance
of connections and leakage resistance (between the lines) cannot differ by more than 10%;
- for the binary input, the short-circuit resistance cannot be higher than 1kΩand the leakage
resistance (between lines) must not be lower than 100kΩ.
If these values are exceeded, the power supply signalizes the WYUSZ fault.
Fig.8. Ways to connect CSP fire alarm input.
5.7. First start.
The designations used in the description come from Fig.2. and Fig.7.:
MAINS - green LED on the door of the power supply box
FAULT - yellow LED on the door of the power supply box
PRACA - green LED on the 230Vac voltage distribution packet
ZINW-1 - yellow LED on the 230Vac voltage distribution packet
ZINW-2 - red LED on the 230Vac voltage distribution packet
AC-1 - 230Vac voltage on the AC-1 output terminals
ALP - red LED on the 230Vac voltage distribution packet
INW - green LED on the 230Vac voltage distribution packet
AC-2A - 230Vac voltage on the AC-2A output terminals
Symbols used in the tables:
+- LED on, voltage present at AC-1 output
-- LED off, no voltage at the AC-1 output
+/-- LED flashing
+/–– - LED blinking
5.7.1. Starting power supply.
Notes:
•connect voltage indicator or load (bulb, motor, etc.) to the AC-1 output;
WYUSZ
CSP
ZAS
ZUP
Fire alarm
ALARM CSP
10
k
1
k
input
CSP PARAM
ON
Switch
WYUSZ
CSP
ZAS
ZUP
ALARM CSP
CSP PARAM
OFF
Operation mode with parameterization
Simple binary input mode
Fire alarm
input
Switch

User manual ZUP-230V Nr dok. 0697.00.95-02.3 13/15
•in the initial state, the mains should be disconnected (with the installation switch outside
the power supply) as well as the battery bank (W-BAT switch);
•each activation of the power supply causes the LEDs to switch on for a moment: INW,
ALP, T2+T3;
•LED OPERATION is on continuously during operation of the power supply;
•signalization states have been indicated in the tables below.
Checking 230Vac voltage backup capacity
LED diodes on
box door
LED diodes on 230Vac voltage distribution
packet
Output
MAINS
FAULT
OPERATION
ZINW-1
ZINW-2
INW
AC-1
W-BAT battery switch switched
on (no reaction required)
–
–
–
–
–
–
–
W-BAT battery switch switched
off
–
–
–
–
–
–
–
Mains switched on
+
+
+
–
–
+/–
+
W-BAT battery switch switched
on
+
–
+
+
–
+
+
Mains switched off
+/–
+
+
+
+
+
+
after time T1
+/–
+
+
–
–
–
–
Switching on the battery switch (without mains) should not cause a permanent reaction of the
power supply. The correct starting (with the battery connected and the mains on) should result in
appearing the voltage on the AC-1 output. After power failure, the voltage should be maintained for the
time T1.
Starting the PSU from the battery, without mains power ("cold start")
LED diodes on
box door
LED diodes on 230Vac voltage
distribution packet
Output
MAINS
FAULT
PRACA
ZINW-1
ZINW-2
INW
AC-1
W-BAT battery switch
switched on
–
–
–
–
–
–
–
ZST button press
–
–
+
+
+
–
–
after a dozen or so
seconds
+/–
+
+
–
–
–
–
The ZST button allows you to start the power supply from the battery, without the power supply.
After such the start, the power supply switches into the state corresponding to the end of the T1
countdown in which the power supply during the battery operation waits for a fire alarm signal.
5.7.2. Checking basic functions.
Initial status: power supply switched on, mains on, battery connected.
Initial settings for the CSP fire alarm input:
- CSP PARAM switch: ON
- AL CSP jumper: L
Checking operation of CSP fire alarm input.
LED diodes on 230Vac voltage
distribution packet
Output
ALP
ZINW-1
ZINW-2
INW
AC-2A
CSP input not connected
+/–
+
–
+
+
Connecting 10kΩresistor to CSP input
–
+
–
+
+

User manual ZUP-230V Nr dok. 0697.00.95-02.3 14/15
Connecting additional 1kΩresistor to CSP
input
+
+
–
+
–
Disconnection of additional 1kΩresistor
from CSP
–
+
–
+
–
after time T2+T3
–
+
–
+
+
With the parameterization of the fire alarm input set, its failure activates fault signalization, which
should disappear after connecting a 10kΩresistor. In this state, connection of a 1kΩresistor is
recognized as occurrence of a fire alarm, which results in switching off the voltage from the AC-2A
output. The subsequent disconnection of the 1kΩresistor (disabling the fire alarm) should result in the
output on the AC-2A output, but only after the countdown of the time T2+T3.
5.7.3. Setting time
There are two slide switches on the 230Vac voltage distribution packet that allow you to set all
three times to organizing the activation of the AC-1, AC-2, AC-3 and AC-4 outputs of the power
supply.
Time T1:
- maximum battery life after power failure (from 1min up to 8h)
Setting:
- sum of individual settings: 1, 2, 5, 10, 30min and 1, 2, 5h.
Example in picture: (1+5+10)min + (1+2)h = 3h and 16min
Time T2:
- maximum time of power supply activity after a fire alarm (from
1min to 6min and from 1 up to 6h)
Setting:
- sum of individual settings: 1, 2, 3 and unit selection: min. or h.
Example in picture: (1+2)min = 3min
Time T3:
- delay of AC-4 output operation (from 5s up to 65s)
Setting:
- sum of individual settings: 5, 10, 20, 30s
Example in picture: (5+30)s = 35s
The absolute values of the set times depend on the construction and the required way of powering
a specific object.
Factory settings: T1: 5min T2: 5min T3: 5s
Additional information
6.1. Manufacturer's notes
The producer reserves the right to introduce construction and technological changes that do not
impair the quality of the product .
6.2. Proceeding with packaging, used products and batteries
T1: h
125
3010521 T1: min
1 2 5 6
ON
3 4 7 8
T2: min
1 2 3 h 5 302010
T3: s
1 2 5 6
ON
3 4 7 8

User manual ZUP-230V Nr dok. 0697.00.95-02.3 15/15
The product packaging is made of materials that can be recycled (wood, paper,
cardboard, plastics). Unnecessary packaging should be distributed to the recipient of the
waste.
This marking on the product indicates that the product should not be disposed of with
municipal waste at the end of its usage time, but must be returned to the collection point
for waste electronics. Waste batteries are hazardous waste and must be disposed
of. This will contribute to avoiding harmful effects on human health and the environment
as a result of uncontrolled waste disposal.

User manual ZSP121N-DR Nr dok. 0696.00.95-02.0 Strona 1/8
MERAWEX Sp. z o.o.
44-122 Gliwice
ul. Toruńska 8
Poland
tel. +48 32 23 99 400
fax +48 32 23 99 409
e-mail: [email protected]
http://www.merawex.com.pl
USER MANUAL
Power supply for fire alarm devices, heat and smoke control systems, fire
protection devices and fire automation
ZSP121N-DR
designed to operate with the power supply ZUP-230V
27 March 2018
Warnings
Read all the tips and recommendations below. Failure to observe them can cause damage to the
device, electric shock, fire or serious injury.
▪It is forbidden to transport the device with mounted and connected batteries. It may result
in serious internal damage and the loss of safety of use.
▪Installation and connections may be carried out only when the batteries are removed.
▪When connecting batteries, pay special attention to the polarity compatibility with the
description near the connector.
▪Do not obstruct the ventilation. Provide at least free space of at least 10cm on the sides of
the device allowing the proper ventilation. Otherwise, the device may be damaged or battery
bank can be prematurely used out.
▪Mount the device in a place where it will not be exposed to direct sunlight..
▪The device must be powered from the mains with a protective earth terminal.
▪Before connecting the device, check the quality of all connections made.
▪The device may affect the operation of sensitive radio and television equipment located
nearby.
▪The device may only be serviced by the manufacturer's service department or
specialized companies authorized by the manufacturer.
Technical description
The power supplies have been designed for uninterruptible powering of 24V fire protection devices
and meet the requirements of the EN 54-4 and EN 12101-10 standards. The source of backup power
are two, 12V lead-acid batteries of the VRLA type. The power supplies are designed for mounting on
the TS-35 rail, inside cabinets or inside the other IP42 devices.

User manual ZSP121N-DR Nr dok. 0696.00.95-02.0 Strona 2/8
Electrical parameters.
Power
Mains
165…230…253V 50Hz
Power factor
0.66
Leakage current in the protective conductor
0.6mA
Efficiency in nominal conditions
87%
Output
Number of outputs
2
Protection of outputs
fuses 5x20mm 6.3AF
Output voltage
- with battery connected
- without batteries
21.0…28.8V (depending on battery condition and
ambient temperature)
26.4…28.8V (depending on ambient temperature)
Max. output current
4.5A (total from both outputs)
Hiccup type overload protection
after overloading of up to 10V (at current of 5.5A)
Ripple voltage
max. 150mVpp
Output current Imax. b *1)
4A
Output current Imax. a *1)
- with batteries of 45Ah
- with batteries of 75Ah
acc. to EN 54-4
2.35A
1.25A
acc. to EN 12101-10
0.46A/72h; 1.13A/30h
0.78A/72h
Battery bank control
Output protection
fuse 5x20mm 8AF
Battery charging current limitation *2)
- for batteries of 45Ah
- for batteries of 75Ah
1.7A(CL plugs open –jumper removed)
2.8A(CL shorted –jumper on)
Bulk charging start
5 min after exceeding 25% level of charging current
limitation
Correct end of bulk charging
- 2h from moment when charging current drops to
90%
- Immediately after current drops below 25% of
charging current
Bulk charging emergency termination
- battery temperature has exceeded 40°C
- temperature sensor fault detected
- total charging time exceeded 20h when limitation of
2.8A and 18h at 1.7A
Floating operation voltage at 25°C
27.1V (2.26V/cell)
Bulk charging voltage at 25°C
27.8V (2.32V/cell)
Temperature compensation of floating
operation voltage and bulk charging
-48mV/°C (-4.0mV/cell/°C)
Overriding battery voltage limits
- minimum voltage
- maximum voltage
26.4V (2.2V/cell)
28.8V (2.4V/cell)
LVDD at
21V
Battery connection
- recognition of battery connection
- automatic battery connection
>10V (signalization only)
>21.6V (1.8V/cell)
Quiescent current consumption from batteries
- battery connected
- battery disconnected
16mA (without external LED signalization 7mA)
160uA
Measurement of battery circuit resistance
- Ri max * 1)
- measurement repetition period
only during floating operation
45mΩ/45Ah; 34mΩ/75Ah *2)
10min
Relay signalization outputs
Output characteristics
- number of relays
- maximum loadability of contacts
- type of contacts available
- active signalization state
2
30Vdc/1A
three switchable contacts (NO and NC)
relay de-energized

User manual ZSP121N-DR Nr dok. 0696.00.95-02.0 Strona 3/8
Binary inputs of external indications
External signal input protection
3.3V/0.7mA, protection ±30V/50mA
Input for connecting tamper switch (tamper)
3.3V/0.7mA
*1) Markings acc. to EN 54-4 + A1 + A2
*2) Possibility of switching by a user. The limitation of the charging current and the threshold of the maximum
resistance of the battery circuit are switched simultaneously.
Operating conditions
Ambient temperature during operation
-25…+55°C
Storage temperature range
-25…+85°C
Relative humidity (non-condensing)
30…80%
Direct sun exposure
unacceptable
Surges during operation
unacceptable
Compliance with standards
Basic requirements, functionality
EN 54-4 + A1 + A2, EN 12101-10, ISO 7240-4
Electromagnetic compatibility
EN 50130-4 + A1
Electrical safety
Class I acc. to EN 60950-1 + A1
Mechanical parameters
Dimensions
- body
- maximum dimension over the TS-35 rail
160 × 97 × 46 mm
54 mm
160
53.5
4612
96.8
5.2
Power supply assembly:
- temperature sensor (attached permanently or fitted with a plug);
- jumper on the INT FLT signalization input connector;
- of the maximum CL charging current selection jumper
Optional equipment:
- module of the 6 additional outputs of the ZSP100-OUT6 type
- tamper with the cables
Installation and connection.
The power supply has been designed for mounting on a TS-35 rail and for use with battery banks.
Releasing the latch on the rail is possible by pressing the lever over the power supply with your fingers
or by pulling it down using a screwdriver inserted into a rectangular hole under the power supply.
Removing the power supply is possible by its slight deviation from the rail towards yourself and

User manual ZSP121N-DR Nr dok. 0696.00.95-02.0 Strona 4/8
upwards. Mounting can be done in the reverse order, also without the use of a lever, by snapping the
bracket on the rail.
The power supply must be connected to a permanent installation by using a protective conductor
and taking into account the L, Nand PE markings. It is recommended to equip the installation with a
surge protection system. The power supply voltage should not be disconnected with the main fire
protection switch. It is required to install in the power circuits, outside of the power supply, an installation
switch with a nominal current of at least 3A. The power box and the circuit breaker should be marked
with red color and the power supply number. One switch should protect one power supply. The switch
mounted on the casing of the power supply can be used for testing purposes –to check the voltage
supply during power failure.
After making the remaining connections (24V voltage outputs and signalization circuits) and after
connecting the external LED signalization harness and possibly the tamper, the batteries should be
connected as the last item.
The power supply has been designed for cooperation with two maintenance-free batteries, which
should be placed in its immediate vicinity. The end of the temperature sensor of the power supply
should be inserted between the two batteries, which afterwards should be maximally pushed together.
Pay special attention to the polarity of the power supply and battery connections. If the connection is
wrong, the battery circuit fuse will be damaged. The following figure shows the polarity of the connected
BAT battery. Firstly, the batteries should be connected to the power supply packet and then connected
to each other.
The power supply is adapted to connect an external LED signalization located, for example, on the
cabinet in which the power supply and batteries have been installed.
It is possible to select between two levels of charging current limitation, battery banks depending on
their capacity. The details are included in the Electrical parameters table. Simultaneously with
switching the level of the charging current limitation, the threshold of the permissible resistance of the
battery circuit Ri max is switched over.
By default, a jumper is mounted on the CL connector, which sets the higher charging current and the
lower value of the resistance Ri max.
LED
EFL
FLT
INT
MAINS
TEMP
BAT
CL
TMP
G201
G200
PE N L
PE BATOUT 1 OUT 2 GEN FLT MAINSFLT EXTFLT
2 31 4
1. 6.
7. 8.
2.
3. 4.
9.
10. 11.
14.
13.12.
15.
16.
17.
18.
20. 21.
19.
5.
This manual suits for next models
4
Table of contents
Other MERAWEX Power Supply manuals

MERAWEX
MERAWEX ZSPM-75-05 User manual

MERAWEX
MERAWEX ZSP100 Series User manual

MERAWEX
MERAWEX ZDSO400-DR2 User manual

MERAWEX
MERAWEX ZUP-230V-BM-400S User manual

MERAWEX
MERAWEX ZDSO400-ER1 User manual

MERAWEX
MERAWEX ZSP135-DR-2A-1 User manual

MERAWEX
MERAWEX ZSP135-DR-2A-1 User manual

MERAWEX
MERAWEX ZMS-1A-12V10A User manual