Mercoid SBLTX Series User manual

eries BLTX ubmersible Level Transducer
pecifications - Installation and Operating Instructions
Bulletin L-37
The BLTX ubmersible Level Transducer is manufactured for years of trouble free
service. The transducer consists of a piezoresistive sensing element, encased in a 316
SS housing. Bullet nose design protects diaphragm from damage. Comes equipped
with a 270-pound tensile strength, shielded, vented cable. Ventilation tube in the cable
automatically compensates for changes in atmospheric pressure above the tank.
Intrinsic afety Approval Classification
The SBLTX is UL listed for use in Hazardous (Classified) Locations. The protection
method is by Intrinsic Safety, “ia”. It was investigated by UL under UL Standard 913
8th Edition, CAN/CSA C22.2 No. 60079-0:15 and CAN/CSA C22.2 No. 60079-11:14.
Hazardous (Classified) Location Intrinsically Safe For:
Class I Div. 1 Groups A,B,C,D
Class II Div. 1 Groups E,F,G
Class III Div. 1
Class I Zone 0 AEx ia IIC T4 Ga
Zone 20 AEx ia IIIC T135°C Da
Ex ia IIC T4 Ga
Ex ia IIIC T135°C Da
Ta = -20°C to 80°C (ETFE Cable)
Ta = -20°C to 65°C (Polyurethane Cable)
Install in accordance with Control Drawing 001833-43.
See Control Drawing 001833-43 for Entity Parameters.
ATEX: EU TYPE CERTIFICATE NO. DEM O 18 ATEX 2080
ATEX STANDARDS: EN 60079-0:2012/A11:2013
EN 60079-11:2012
ATEX CLASSIFICATION: 0518 II 1 G Ex ia IIC T4 Ga (-20°C ≤ Tamb ≤ 80°C
(ETFE Cable)) (-20°C ≤ Tamb ≤ 65°C (Polyurethane Cable))
0518 II 1 D Ex ia IIIC T135°C Da (-20°C ≤ Tamb ≤ 80°C (ETFE Cable))
(-20°C ≤ Tamb ≤ 65°C (Polyurethane Cable))
IECEx CERTIFICATE OF CONFORMITY: IECEx UL 18.0086
IECEx STANDARDS: IEC 60079-0: 2011 6TH ED.
IEC 60079-11:2011 6TH ED.
IECEx CLASSIFICATION: Ex ia IIC T4 Ga (-20°C ≤ Tamb ≤ 80°C (ETFE Cable))
(-20°C ≤ Tamb ≤ 65°C (Polyurethane Cable))
Ex ia IIIC T135°C Da (-20°C ≤ Tamb ≤ 80°C (ETFE Cable)) (-20°C ≤ Tamb ≤ 65°C
(Polyurethane Cable))
INSTALL IN ACCORDANCE WITH CONTROL DRAWING 001833-46
SEE CONTROL DRAWING 001833-46 FOR ENTITY PARAMETERS.
PECIFICATION
ervice: Compatible liquids.
Wetted Materials: 316 SS, 316L SS, epoxy adhesive; Cable: Polyether
polyurethane or ETFE; Bullet Nose: PVC.
Accuracy: ±0.25% of full scale.
Temperature Limit: ETFE Cable Equipped -4 to 176°F (-20 to 80°C);
Polyurethane Cable Equipped -4 to 149°F (-20 to 65°C).
Compensated Temperature Range: -4 to 176°F (-20 to 80°C).
Thermal Effect: Less than ±0.02% full scale/ °F.
Pressure Limit: 2X full scale.
Power Requirement: 10 to 28 VDC.
Output ignal: 4 to 20 mA DC, 2-wire.
Response Time: 50 ms.
Max. Loop Resistance: 900 ohms.
Electrical Connections: Wire pigtail.
Mounting Orientation: Suspended in tank below level being measured.
Weight: 2.2 lb (1.0 kg).
Agency Approvals: CE, See Intrinsic Safety Approval Classification.
MERCOID DIVI ION
DWYER IN TRUMENT , INC.
P.O. BOX 258 • MICHIGAN CITY, IN 46360 U. .A.
Phone: 219/879-8000 www.dwyer-inst.com
Fax: 219/872-9057 e-mail: info@dwyermail.com
BREATHER TUBE
SUBMERSIBLE
CABLE
1/2 NPT
6-15/16
[176.21]
Ø1
[Ø25.40]
WARNING: Use with approved safety barriers using
entity evaluation.

CAUTION: Do not exceed specified supply voltage ratings.
Permanent damage not covered by warranty will result. This
device is not designed for 120 or 240 volt AC operation. Use
only on 10 to 28 VDC.
IN TALLATION
1. Location: Select a location where the temperature of the transducer will be
between -4 and 176°F (-20 to 80°C) for ETFE cable or -4 and 149°F (-20 to 65°C)
for polyurethane cable. Distance from the receiver is limited only by total loop
resistance.
2. Position: The transducer is not position sensitive. However all standard models
are originally calibrated with the unit in a position with the pressure connection
downward. Although they can be used at other an gles, for best accuracy it is
recommended that units be installed in the position calibrated at the factory.
3. Mounting: The transducer can be mounted via several methods. It can be
suspended from the electrical cable, it can be placed resting on the bottom of the
tank in either horizontal or vertical orientation, or it can be attached to a pipe or
hang wire by the 1/2˝ NPT male connection on the top of the housing.
4. Electrical Connections
Wire Length - The maximum length of wire connecting the transducer and receiver
is a function of wire size and receiver resistance. Wiring should not contribute more
than 10% of the receiver resistance to total loop resistance. For extremely long runs
(over 1000 feet), choose receivers with higher resistance to minimize the size and
cost of connecting leads. Where wiring length is under 100 feet, wire as small as
22 AWG can be used.
5. Wiring
An external power supply delivering 10-28 VDC with minimum current capability of
40 mA DC (per transducer) is required to power the control loop. See Fig. A for
connection of the power supply, transducer and receiver. The range of appropriate
receiver load resistance (RL) for the DC power supply voltage available is
expressed by the formula:
RL Max = Vps – 10V
20 mA DC
Shielded cable is recommended for control loop wiring.
Black wire is negative (-) and red wire is positive (+).
MAINTENANCE
After final installation of the pressure transducer and its companion receiver, no
routine maintenance is required. A periodic check of system calibration is
suggested. The Series SBLTX transducer are not field repairable and should be
returned if repair is needed (field repair should not be attempted and may void
warranty). Be sure to include a brief description of the problem plus any relevant
application notes. Contact customer service to receive a return goods authorization
number before shipping.
POWER
SUPPLY
10-28 VDC
-
RECEIVER
BLACK
RED
PRESSURE
TRANSDUCER mA
Fig. A
Fig. B

“” “ ”
“ ”
≥
≥

©Copyright 2018Dwyer Instruments, Inc. Printed in U.S.A. 10/18 FR# 443550-00 Rev. 5
MERCOID DIVI ION
DWYER IN TRUMENT , INC.
P.O. BOX 258 • MICHIGAN CITY, IN 46360 U. .A.
Phone: 219/879-8000 www.dwyer-inst.com
Fax: 219/872-9057 e-mail: info@dwyermail.com
“ ” “”
“ ”
≥
≥
Other Mercoid Transducer manuals
Popular Transducer manuals by other brands

Siedle
Siedle Novotechnik TH1 CANopen user manual

Siemens
Siemens XRS-5 Quick start manual

Trerice
Trerice TA901 Installation, operation and maintenance instructions

CONTINENTAL CONTROL SYSTEMS
CONTINENTAL CONTROL SYSTEMS WattNode Pulse Quick install guide

Faller
Faller 180633 quick start guide

Knick
Knick VariTrans P 41000 TRMS user manual