3
(2) Low-pressure twinning kit in CMY-ER100CBK
Use 1in table "(1) Package Contents." Attach items g, h,
and ito the stop valve sheet metal and then to the low-
pressure twinning kit to hold it into place.
1. Attach item hto the stop valve sheet metal.
2. Attach the packing and saddle.
3. Secure the low pressure twinning kit.
(3) Routing the pipe through the bottom
(1) Braze item 6high-pressure pipe to the refrigerant service valve so
that the dimples on the pipe are parallel to the edge of the cutout
hole. ([pand the end of the ¿eld-supplied pipes, and braze them to
item 6high-pressure pipe.
(2) Attach item 1low-pressure twinning kit to the sheet metal of the
refrigerant service valve with item 3screw, and braze it to the
refrigerant service valve.
(3) Braze item 5elbow pipe to the ¿eld-supplied pipe ¿rst, and then
braze it to item 1low-pressure twinning kit.
() )lare the ¿eld-supplied pipe end, and braze the pipe to the low-
pressure pipe in the middle.
(5) Wrap the pipe in front of item 1low-pressure twinning kit with item
8pipe cover, and attach compressor cables to item 8pipe cover
with item ecable tie to keep them out of direct contact with the
pipes.
(4) Routing the pipe through the front
(1) Braze item 7high-pressure pipe to the refrigerant service valve.
(2) Attach item 1low-pressure twinning kit to the sheet metal of the
refrigerant service valve with item 3screw, and braze it to the
refrigerant service valve.
(3) Braze item 5elbow pipe to the ¿eld-supplied pipe ¿rst, and then
braze it to item 1low-pressure twinning kit.
(4) Braze item 4elbow pipe to the low-pressure pipe in the middle.
(5) Wrap the pipe in front of item 1low-pressure twinning kit with item
8pipe cover, and attach compressor cables to item 8pipe cover
with item ecable tie to keep them out of direct contact with the
pipes.
(5) Slope of twinning pipes (high-pressure side only)
Make sure the slope of the twinning pipes are at an angle
within ±15˚ to the horizontal plane.
If the slope exceeds the specified angle, the unit may be
damaged.
Note. Refer to the figure below for the installation position of the twinning pipe.
· Before heating the pipes, place a wet towel on the refrigerant service
valve to keep its temperature below 120
˚C [248˚F]
.
· Direct the flame away from the cables and sheet metals inside the unit
so as not to burn them.
CAUTION
· Before heating the pipes, place a wet towel on the refrigerant service
valve to keep its temperature below 120
˚C [248˚F]
.
· Direct the flame away from the cables and sheet metals inside the unit
so as not to burn them.
CAUTION
g,h,i
33
1
1
3
5
1
3
5
4
7
8
Section to be brazed locally
Connect the pipe so that the
dimples on the 6high pressure
pipe are parallel to the edge of
the cutout hole.
8
Wrap the pipe cover here.
Attach compressor cables to pipe
cover with cable tie to keep them
out of direct contact with the pipes.
Wrap the pipe cover here.
Attach compressor cables to pipe
cover with cable tie to keep them
out of direct contact with the pipes.
Field-supplied pipes
Field-supplied
pipes
Field-supplied pipes
±15˚
Twinning pipe on the high-pressure side
Slope of the twinning pipe is at an angle within ±15° to the horizontal plane.
Refrigerant
service valve