9
9-1. COOL ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons.
(TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31˚C
Indoor fan continues to operate regardless of thermostat's OFF-ON at set speed.
1. Coil frost prevention
When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.
The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of
indoor heat exchanger rises.
2. Discharge temperature protection
The compressor is controlled by the temperature of discharge temperature thermistor RT62 for excess rise protection
of compressor discharge pressure.
9-2. DRY ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone.
(2) Select DRY mode with OPERATION SELECT button.
(3) The set temperature is determined from the initial room temperature.
(4) DRY operation will not function when the room temperature is 13˚C or below.
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
However, in AUTO fan operation, fan speed becomes Low.
2. The operation of the compressor and indoor/outdoor fan
Compressor operates by room temperature control and time control.
Set temperature is controlled to fall 2˚C from initial room temperature.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
3. Coil frost prevention
• The operation is as same as coil frost prevention during COOL mode.
• Indoor fan operates at the set speed and the compressor stops for 5 minutes, because protection (Coil frost preven-
tion) has the priority.
However, when coil frost prevention works while the compressor is not operating, it's speed becomes Low.
9-3. FAN ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone.
(2) Select FAN mode with OPERATION SELECT button.
(3) Select the desired fan speed. When AUTO, it becomes Low.
Only indoor fan operates. Outdoor unit dose not operate.
9-4. "I FEEL CONTROL" ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button on the remote controller. OPERATION INDICATOR lamp of the indoor unit
turns ON with a beep tone.
(2) Select "I FEEL CONTROL" mode with OPERATION SELECT button.
(3) The operation mode is determined by the room temperature at start-up of the operation.
• Once the mode is fixed, the mode dose not change by room temperature afterwards.
• Under the ON-TIMER ( ) operation, mode is determined as follows.
When the system is stopped on the remote controller, and restarted within 2 hours in " I FEEL CONTROL" ( ) mode,
the system operates in previous mode automatically regardless of the room temperature.
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
Initial room temperature
25
°C
or more
more than 13
°C
,
less than 25
°C