7
The following symptoms are not air conditioner failures:
•The air blown out from the air conditioner can sometimes give off odors. This is due to cigarette smoke contained in the air of the room, the smell of
cosmetics, the walls, furniture, etc., absorbed in the air conditioner.
•A hissing noise can be heard immediately after the air conditioner is started or stopped. This is the sound of the refrigerant flowing inside the air
conditioner. The problem is insignificant.
•The air conditioner sometimes snaps or clicks at the beginning or end of cooling/heating operation. This is the sound of friction on the front panel and
other sections due to inflation and contraction caused by temperature change. The problem is insignificant.
Range of application
The range of working temperatures for both the indoor and outdoor units of the series Y, R2, Multi-S is as below.
Caution:
The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.
Note:As an applicable humidity standard for both indoors and outdoors, we recommend use within a range of 30 - 80% relative humidity.
Warning:
If the air conditioner operates but does not cool or heat (depending on model) the room, consult your dealer since there may be a refrigerant
leak. Be sure to ask the service representative whether there is refrigerant leakage or not when repairs are carried out.
The refrigerant charged in the air conditioner is safe. Refrigerant normally does not leak, however, if refrigerant gas leaks indoors, and comes
into contact with the fire of a fan heater, space heater, stove, etc., harmful substances will be generated.
Model P32 P40 P50 P63 P80 P100 P125
Power source (Voltage<V>/Frequency) <Hz> ~N/220-230-240/50, 220/60
Capacity (Cooling/Heating) <kW> 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 9.0/10.0 11.2/12.5 14.0/16.0
Dimension (Height) <mm> 258 (30) 298 (30)
Dimension (Width) <mm> 840 (950)
Dimension (Depth) <mm> 840 (950)
Net weight <kg> 22 (5) 24 (5) 32(5)
Fan Airflow rate
(Low-Middle2-Middle1-High)
<m3/min> 11-12-13-14 12-13-14-16 14-15-16-18 16-18-20-22 19-22-25-27 21-24-27-29
Noise level
(Low-Middle2-Middle1-High)
<dB> 27-28-29-31 27-28-30-32 28-29-31-33 30-32-35-37 33-36-39-41 35-38-41-43
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27 °C DB/19 °C WB, Outdoor 35 °C DB
Heating: Indoor 20 °C DB, Outdoor 7 °C DB/6 °C WB
*2 This figure ( ) indicates panel’s.
■PLFY-P·VAM-E Series
5. Specifications
Model P40 P63 P100 P125
Power source (Voltage<V>/Frequency) <Hz> ~N/220-230-240/50, 220/60
Capacity (Cooling/Heating) <kW> 4.5/5.0 7.1/8.0 11.2/12.5 14.0/16.0
Dimension (Height) <mm> 210 270
Dimension (Width) <mm> 1000 1310 1620
Dimension (Depth) <mm> 680
Net weight <kg> 27 34 37 43
Fan Airflow rate
(Low-Middle2-Middle1-High)
<m3/min> 8-10-11-12 12-14-16-18 18-20-23-25 26-28-32-35
Noise level
(Low-Middle2-Middle1-High)
<dB> 29-33-36-38 32-34-37-39 36-38-41-43 37-39-42-44
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27 °C DB/19 °C WB, Outdoor 35 °C DB
Heating: Indoor 20 °C DB, Outdoor 7 °C DB/6 °C WB
■PCFY-P·VGM-E Series
Model P20 P25 P32 P40 P50
Power source (Voltage<V>/Frequency) <Hz> ~N/220-230-240/50, 220/60
Capacity (Cooling/Heating) <kW> 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3
Dimension (Height) <mm> 295 340
Dimension (Width) <mm> 815 990
Dimension (Depth) <mm> 158 235
Net weight <kg> 8.5 16
Fan Airflow rate
(Low-Middle2-Middle1-High)
<m3/min> 4.9-5.2-5.6-5.9 8-9.5-10.5-11.5 9-10-11-12
Noise level
(Low-Middle2-Middle1-High)
<dB> 32-33-35-36 33-36-38-41 34-37-40-43
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27 °C DB/19 °C WB, Outdoor 35 °C DB
Heating: Indoor 20 °C DB, Outdoor 7 °C DB/6 °C WB
■PKFY-P·VAM-E Series
Model P20 P25 P32 P40
Power source (Voltage<V>/Frequency) <Hz> ~N/220-230-240/50, 220/60
Capacity (Cooling/Heating) <kW> 2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0
Dimension (Height) <mm> 230 (30)
Dimension (Width) <mm> 854 (1000)
Dimension (Depth) <mm> 395 (470)
Net weight <kg> 14 (3.0)
Fan Airflow rate
(Low-Middle2-Middle1-High)
<m3/min>
6.5-7.2-8.0-8.6
7.3-8.0-8.6-9.3
7.7-8.7-9.7-10.7
Noise level
(Low-Middle2-Middle1-High)
<dB> 27-30-33-36 32-34-36-37 33-35-37-39
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27 °C DB/19 °C WB, Outdoor 35 °C DB
Heating: Indoor 20 °C DB, Outdoor 7 °C DB/6 °C WB
*2 This figure ( ) indicates panel’s.
■PMFY-P·VBM-E Series
■PKFY-P·VGM-E Series
4. Troubleshooting
PUHY
–5 °C - 43 °C DB
–15 °C - 15.5 °C WB
Mode
Cooling
Heating
Indoor unit
15 °C - 24 °C WB
15 °C - 27 °C DB
PURY
–5 °C - 43 °C DB
–12 °C - 15 °C WB
PUMY
–5 °C - 46 °C DB
–12 °C - 15.5 °C WB