CC-Link System (ME96SSHA-MB/ME96SSRA-MB with ME-0040C-SS96 (optional plug-in module))
MODBUS
®
TCP Communication (ME96SSHA-MB/ME96SSRA-MB with ME-0000MT-SS96 (optional plug-in module))
Data Logging (ME96SSHA-MB/ME96SSRA-MB with ME-0000BU-SS96 (optional plug-in module))
Analog/Pulse/Alarm Output System (ME96SSHA-MB/ME96SSRA-MB with ME-4210-SS96 (optional plug-in module))
»Applicable to analog output, pulse output and alarm output with the aid of the
optional module ME-4210-SS96
»Remote monitoring of A, DA, V, W, var, VA, PF, Hz, Harmonics Current RMS value
and Harmonics voltage RMS value at 4 to 20mA output (max. 4 outputs)
»Active energy, reactive energy, apparent power and periodic energy (ME96SSHA-
MB) can be monitored by pulse output (max. 2 pulses)
»Can remotely monitor upper/lower limit alarm by contact output (max. 2 points)
»There is available an optional module usable
not only for the conventional MODBUS®RTU
(RS-485) communication and CC-Link
communication, but also for MODBUS®TCP
communication in an Ethernet environment.
»There is available an optional module which can retain data even when communication cannot be established.
<Analog output specifications>
• 4-20mA
• 4 outputs
• Resistance load 600Ωor less
<Pulse output specifications>
• No-voltage a contact point
• 35VDC, 0.1A
• Select output from pulse widths of 0.125, 0.5 or 1s
<Alarm output specifications>
• No-voltage a contact point
• 35VDC, 0.1A
<Digital input specifications>
• 1 point (24VDC)
CC-Link IE
Analog output
Pulse output
Alarm output
SWITCH / HUB
Ethernet
PLC
Data in more than one logging unit can
be managed with one SD memory card.
Note: Use the SD memory card (EMU4-SD2GB) made by Mitsubishi Electric.
Use of any memory card other than our product (EMU4-SD2GB) is not covered by the warranty.
CSV file data
ME96 Super-S Series Ver.A Features
Improved Measurement Functions
ME96SSHA-MB
(
High-performance class
)
ME96SSRA-MB
(Standard class)
ME96SSEA-MB
(Economy class)
MODBUS®RTU communication
Plug-in module (options)
• Analog/Pulse/Contact output/input
• CC-Link communication
•
Digital input/output (for MODBUS®RTU communication)
• Backup (on SD card)
• MODBUS®TCP communication
MODBUS®RTU communication
Plug-in module (options)
• Analog/Pulse/Contact output/input
• CC-Link communication
•
Digital input/output (for MODBUS®RTU communication)
• Backup (on SD card)
• MODBUS®TCP communication
MODBUS®RTU communication
A, DA, V, Hz = ±0.1%
W, var, VA, PF = ±0.2%
Wh = class 0.5S (IEC62053-22)
varh = class 1S (IEC62053-24)
Harmonics = 31st-deg (max)
Rolling demand = W, var, VA
A, DA, V = ±0.2%
Hz = ±0.1%
W, var, VA, PF = ±0.5%
Wh = class 0.5S (IEC62053-22)
varh = class 1S (IEC62053-24)
Harmonics = 19th-deg (max)
Rolling demand = W, var, VA
A, DA, V = ±0.5%
Hz = ±0.2%
W, PF = ±0.5%
Wh = class 0.5S (IEC62053-22)
Harmonics = Only total
Optional Plug-in Modules
Note: Optional Plug-in Module can not be used with ME96SSEA-MB.
Model name
ME-4210-SS96
ME-0040C-SS96
ME-0052-SS96
ME-0000BU-SS96
ME-0000MT-SS96
Analog output
4
—
—
—
—
Pulse/Alarm output
2
—
—
—
—
Contact input
1
4
5
—
—
Contact output
—
—
2
—
—
Transmission function
—
CC-Link
—
SD CARD
MODBUS®TCP
Used with
ME96SSHA-MB
ME96SSRA-MB
»Optimum transmission system for remote monitoring using Mitsubishi PLC
»Contact signals can be remotely monitored by installing the optional module ME-0040C-SS96.
This is helpful in wiring and space saving.
»Digital unit signal can be latched for over 30ms, and there is no need for external latch circuits
Abnormal Signal (Facility)
Abnormal Signal (Earth Leakage)
Abnormal Signal (Temperature)
Circuit Breaker Status Signal, etc.
<CC-Link Interface>
• Max. Baud rate: 10Mbps
• Max. Connection Distance: 100m (10Mbps)~
1,200m (156kbps)
• Max. Connection Units: 42
• Digital Input: 4 points (24VDC)
CC-Link
CC-Link IE
MELSEC Series
MODBUS
®
RTU System (ME96SSHA-MB/ME96SSRA-MB with ME-0052-SS96 (optional plug-in module))
Central monitor
RS485/USB
converter
RS485 (MODBUS®RTU)
USB
»MODBUS®RTU communication system optimizes computer monitoring operations
»Attachment of ME-0052-SS96 (optional) enables remote monitoring of the contact input signal
and on/off control of the contact output signal
»
Digital input signals can be latched for over 30ms, and there is no need for external latch circuits
ME-0052-SS96
optional unit
Tripping
Closing
AL
PAL
TAL
Turning on/off breaker, etc.
<MODBUS® RTU Interface Specifications>
• Max. Baud rate: 38.4kbps
• Max. Connection Distance: 1,200m
• Max. Connection Units: 31
<Optional Plug-in Module ME-0052-SS96>
• Digital Input: 5 points (24VDC)
• Digital Output: 2 points (35VDC)
Model name Transmission/Option specifications Main measurement items
»Improved accuracy of active energy, reactive energy and power factor and expanded measurement ranges of harmonics and
demand values have been realized.
3 4