ME96 QUICK START MANUAL
5
• The LCD display contrast changes depending on the angle from
which it is viewed. Install it in a position that ensures a suitable angle
of view.
• Tighten screws using a torque of approx. 0.3~0.5N·m
• To prevent damage to the LCD, take care not to subject the LCD/
front of the main unit to shock/impact.
Auxiliary power supply and instrument ratings
Auxiliary power supply AC100~240V (±15%) 50-60Hz
DC100~240V (−30%, +15%)
Instrument
ratings
Voltage
3-phase, 4-wire: Max. 277/480VAC
3-phase, 3-wire: Delta connection: Max. 220VAC, Star
connection: Max. 440VAC
1-phase, 3-wire: Max. 220/440VAC
1-phase, 2-wire: Delta connection: Max. 220VAC, Star
connection: Max. 440VAC
Current 5A/1A
Frequency 50-60Hz (dual use)
CAUTION CONNECTIONS
• To ensure safety, connections are to be performed by an electrical
engineer qualified in wiring.
• Check connection diagrams carefully before performing connections.
Incorrect connections may result in VT burnout caused by a VT
secondary-side short circuit or high voltage on the CT secondary
side, which may lead to device malfunction, fire or electrical shock.
• Do not work with live wires; there is a risk of electric shock and
exposure to high voltage due to short-circuiting or CT secondary
side opening, which may lead to malfunction, fire or electrical shock.
• Use electrical wire sizes compatible with the rated current. Use of
unsuitable sizes may cause heat generation, which may lead to a
fire.
• After performing connections, check that no connections have been
missed. Missed connections may result in erroneous operation or
high voltage on the CT secondary side, which may lead to a fire or
electrical shock.
nPREPARATIONS BEFORE USE
• Before use, perform settings such as the VT primary voltage, CT
primary current, power scale and demand time limit in accordance
with the operations manual supplied with the product; setting errors
may cause incorrect measurement/operation.
nUSAGE PROCEDURES
• Use the products within the rated range. Using the products
outside the rated range may cause erroneous operation or product
malfunction.
• Do not use the products for special applications such as nuclear
power, aerospace or medical devices/systems.
CAUTION Do not make any modifications to the products. Using
products after modification may cause a malfunction, electrical shock
or fire.
nREPAIRING AT TIME OF MALFUNCTION/ERROR
• If a product listed in this catalog malfunctions, read the
troubleshooting section of the operations manual (detailed version)
and confirm the symptoms. If the problem is not listed, please
3.1 SPECIFICATIONS
Type ME96-SSH-MB, ME96-SSR-MB, ME96-SSE-MB
Phase Wire System 3-Phase 4-Wire, 3-Phase 3-Wire (3CT, 2CT), 1-Phase 3-Wire,
1-Phase 2-Wire (common)
Rating
Current AC5A, AC1A (common)
Voltage
3-Phase 4-Wire: max AC277/480V
3-Phase 3-Wire: (DELTA)max AC220V,
(STAR) max AC440V
1-Phase 3-Wire: max AC220/440V
1-Phase 2-Wire: (DELTA)max AC220V,
(STAR) max AC440V
Frequency 50-60Hz (common)
Item Measurement Item ME96-SSH-
MB
ME96-SSR-
MB
ME96-SSE-
MB
Measurement Elements
Current (A) A1, A2, A3, AN,
A AVG ±0.1% ±0.2% ±0.5%
Current Demand (DA) DA1, DA2, DA3,
DAN, DAAVG ±0.1% ±0.2% -
Voltage (V)
V12, V23, V31,
VAVG (L-L), V1N,
V2N, V3N, VAVG
(L-N)
±0.1% ±0.2% ±0.5%
Active Power (W) W1, W2, W3, ∑W ±0.2% ±0.5 % ±0.5 %
Reactive Power (var) var1, var2, var3,
∑var ±0.2% ±0.5 % -
Apparent Power (VA) VA1, VA2, VA3, ∑VA ±0.2% ±0.5 % -
Power Factor (PF) PF1, PF2, PF3, ∑PF ±1.0% ±2.0 % ±2.0 %
Frequency (Hz) Hz ±2.0 % ±0.5 % ±0.5 %
Active Energy (Wh) Imported, Exported
class0.5S
(IEC62053-
22)
class1.0
(IEC62053-
21)
class1.0
(IEC62053-
21, Only
Imported
Lag)
Reactive Energy (varh)
Imported Lag,
Imported
Lead,Exported Lag,
Exported Lead
class2.0
(IEC62053-
23)
class2.0
(IEC62053-
23)
-
Apparent Energy (VAh) Imported + Exported class2.0 - -
Harmonic Current (HI) Only odd number ±2.0%
(1 to 31)
±2.0%
(1 to 13) -
Harmonic Voltage (HV) Only odd number
Rolling Demand (DW) Rolling Block, Fixing
Block ±0.2% - -
Periodic Active Energy
(Wh)
Periodic Active
Energy 1, Periodic
Active Energy 2
class0.5S
(IEC62053-
22)
class1.0
(IEC62053-
21)
-
Operation Time (h) Operation time 1,
Operation time 2 (Reference)
Analog Output Response
Time 2 s or less (HI and HV:10s or less)
Measuring
Method
Instantaneous
Value
A•V: RMS calculation,W•var•VA•Wh•varh•VAh: Digital
multiplication, PF: Power ratio calculation, Hz: Zero-cross, HI•HV:
FFT
Demand
Value DA: Thermal type calculation , DW: Rolling Demand calculation
Display
Type LCD with backlight
Maximum
Number
of Display
Digits or
Segment
Number
Number of
Display Digits
Upper stage display: 6 digits, Middle stage display: 6 digits, Lower
stage display: 6 digits
A, DA, V, W, var, VA, PF: 4 digits DW, Hz: 3 digits Wh, varh, VAh: 9
digits: 6 digits or 12 digits possible: Harmonic total distortion ratio:
3 digits Harmonic RMS value: 4 digits Operation time: 6 digits
Digital input/output: I/O
Bar Graph 21 Segment-Bar graph, 22 Segment- Indicator
Display Updating Time
Interval 0.5s, 1s
Communication Specification MODBUS®RTU communication
Power Failure Compensation
Non volatile memory (Items: Setting value, MAX/MIN value,
Active/Reactive/Apparent energy, Periodic Active Energy, Rolling
Demand, Operation time)
VA
Consumption
VT 0.1VA/phase, 0.2VA (at direct input 220V)
CT 0.1VA/phase
Aux. Power 7VA (AC110V), 8VA (AC220V), 5W (DC100V)
Auxiliary Power AC100-240V (±15%), DC100 to 240V (-30% +15%)
Weight 0.5kg
Dimension (H x W x D) 96 x 96 x 86
Attachment Method Embedding attachment
Operating Temperature/
Humidity
-5 to +55°C (average temperature: 35°C or less per day)
0 to 85%RH, non condensing
Storage Temperature/
Humidity
-25 to +75°C (average temperature: 35°C or less per day)
0 to 85%RH, non condensing