KSGD-01W/S SEMI CONDUCTOR STAND ALONE
REFRIGERANT LEAK DETECTOR
Installation Manual
Instructions for :-
KSGD-01W/S Semi Conductor Standalone Refrigerant Leak Detector
For safe and correct use please read the installation manuals supplied with the equipment.
Issue 1
Manufactured on behalf of
MITSUBISHI ELECTRIC UK

Contents
KSGD-01W/S Semi Conductor Standalone Refrigerant Leak Detector
2
Page
3 - 4 Safety precautions
5 General Detail / Features
6 Installation Instructions / Internal View / Wiring
7 Operation / Technical Specification / Operation Matrix
Caution:
 Do not use the existing refrigerant piping.
The old refrigerant and refrigerator oil in the existing piping contains a large amount of chlorine which may cause the refrigerator oil of
the new unit to deteriorate. Use refrigerant piping made of C1220 (CU-DHP) phosphorus deoxidized copper as specified in the JIS H3300"
Copper and copper alloy seamless pipes and tubes". In addition, be sure that the inner and outer surfaces of the pipes are clean and
free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
Contaminants on the inside of the refrigerant piping may cause the refrigerant residual oil to deteriorate.
 Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing.
(Store elbows and other joints in a plastic bag.) If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and
compressor problems may result.
 Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
The refrigerator oil will degrade if it is mixed with a large amount of mineral oil.
 Use liquid refrigerant to fill the system.
If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.
 Do not use a refrigerant other than R410A.
If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerator oil to deteriorate.
 Use a vacuum pump with a reverse flow check valve.
The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate.
Do not use the following tools that are used with conventional refrigerants. (Gauge manifold, charge hose, gas leak detector,
reverse flow check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment.)
 If the conventional refrigerant and refrigerator oil are mixed in the R410A, the refrigerant may deteriorate.
If water is mixed in the R410A, the refrigerator oil may deteriorate.
Since R410A does not contain any chlorine, gas leak detectors for conventional refrigerants will not react to it.
 Do not use a charging cylinder. Using a charging cylinder may cause the refrigerant to deteriorate.
Be especially careful when managing the tools.
 If dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
Before installing the unit, make sure you read all the “Safety precautions”.
Warning: Carefully read the labels affixed to the main unit.
Safety precautions
Symbols used in the text
Warning: Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution: Describes precautions that should be observed to prevent damage to the unit.
Warning:
Ask the dealer or an authorised technician to install the unit.
Improper installation by the user may result in water leakage, electric shock, or fire.
Use the specified cables for wiring. Make the connections securely so that any outside forces acting on the cables are not
applied to the terminals. Inadequate connection and fastening may generate heat and cause a fire.
Never repair the unit. If the controller must be repaired, consult the dealer.
If the unit is repaired improperly, electric shock, or fire may result.
When handling this product, always wear protective equipment. EG: Gloves, full arm protection namely boiler suit, and safety glasses.
Improper handling may result in injury.
If refrigerant gas leaks during installation work, ventilate the room.
If the refrigerant gas comes into contact with a flame, poisonous gases will be released.
Install the controller according to this Installation Manual.
If the unit is installed improperly, electric shock, or fire may result.
Have all electric work done by a licensed electrician according to "Electric Facility Engineering Standard", "Interior Wire
Regulations" and the instructions given in this manual and always use a special circuit.
If the power source capacity is inadequate or electric work is performed improperly, electric shock and fire may result.
Keep the electric parts away from any water - washing water etc…
Contact may result in electric shock, fire or smoke.
After completing installation work, make sure that refrigerant gas is not leaking.
If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or other heat source, it may generate noxious gases.
Do not reconstruct or change the settings of the protection devices.
If the pressure switch, thermal switch, or other protection device is shorted or operated forcibly, or parts other than those specified by
Mitsubishi Electric are used, fire or explosion may result.
To dispose of this product, consult your dealer. Do not use a leak detection additive.
Precautions for devices that use R410A refrigerant
Before installation and electric work
3
KSGD-01W/S Semi Conductor Standalone Refrigerant Leak Detector
Caution:
Do not install the unit where combustible gas may leak.
If the gas leaks and accumulates around the unit, an explosion may result.
Caution:
Ground the unit.
Do not connect the ground wire to gas or water pipes, lightning rods, or telephone ground lines. Improper grounding may result in
electric shock.
Install the power cable so that tension is not applied to the cable.
Tension may cause the cable to break and generate heat which may, in turn, cause fire.
Install a leak circuit breaker, as required.
If a leak circuit breaker is not installed, electric shock may result.
Use power line cables of sufficient current carrying capacity and rating.
Cables that are too small may leak, generate heat, and cause a fire.
Use only a circuit breaker and fuse of the specified capacity.
A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire.
Be very careful regarding product transportation.
Two people should be used to carry products of 20kg or more.
Some products use PP bands for packaging. Do not use any PP bands for a means of transportation.
Safely dispose of the packing materials.
Packing materials, such as nails and other metal or wooden parts, may cause stabs or other injuries.
Tear apart and throw away plastic packaging bags so that children will not play with them - If children play with a plastic bag which has
not been torn apart, they face the risk of suffocation.
Safety precautions
Before installation
Before starting the test run
Caution:
Do not touch the switches with wet fingers.
Touching a switch with wet fingers can cause electric shock.
Do not touch the refrigerant pipes during and immediately after operation.
During and immediately after operation, the refrigerant pipes may be hot or cold, depending on the condition of the refrigerant flowing through the
refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant
pipes.
Do not operate the air conditioner with the panels and guards removed.
Rotating, hot, or high-voltage parts can cause injuries.
Do not turn off the power immediately after stopping operation.
Always wait at least five minutes before turning off the power. Otherwise, water leakage and other problems may occur.
Disclaimer
Warranty:
All products manufactured on behalf of Mitsubishi Electric UK are warranted against defective materials for a period of three years from the
date of delivery to the original purchaser.
Warning:
Mitsubishi Electric UK assumes no liability for damages consequent to the user of this product. We reserve the right to change this manual at
any time without notice. The information furnished by us is believed to be accurate and reliable. However, no responsibility is assumed by us
for its use, nor for any infringements of patents or other rights of third parties resulting from its use.
4
KSGD-01W/S Semi Conductor Standalone Refrigerant Leak Detector
General
KSGD-01 STAND ALONE (SEMI-CONDUCTOR)
The detector is a microprocessor based refrigerant leak detector for air conditioning systems designed
primarily for use in offices, and residential properties. Not recommended for use in hotel or bedroom
applications when connected and used in conjunction with pump down system.
The compact size and design enable it to be easily fitted into room without being intrusive.
Detects R410a HFC refrigerant.
Healthy, fault and leak LED indication
Audible leak alarm
Factory calibrated
Easily installed
12-24 V AC/DC supply - (supplied separately - 12VDC order ref KSTR12, 10100230)
Features
KSGD‐01S
KSGD‐01W
CAUTION
Mount the sensor unit as close as practical from the floor or ground (150mm - 250mm), preferably directly
beneath the air conditioning unit.
The sensor unit should be installed in a location where it is easily accessible for repairs.
Mount the sensor unit in a position that minimises the risk of mechanical damage.
5
KSGD-01W/S Semi Conductor Standalone Refrigerant Leak Detector
Installation Instructions
Wiring sensor to fan coil using the supplied 5-wire adapter (PAC-SA88HA) if operated with VRF system pump down.
(Example shown for 1000ppm see Aspirated KS8-IR8/16C Infra-Red Aspirated Refrigerant Gas Detector and VRF Refrigerant Pump
Down Package manuals for detail)
Cable can be extended to a max of 10 metres.
5wireadaptorPAC‐SA88HAtobeonlyusedin
conjunconwithVRFpumpdownsystem
Standalonepowersupplyrequired
12VDCKSTR12
Pins
12345Note:
Please see Operation Matrix table in Aspirated
KS8-IR8/16C Infra-Red Aspirated Refrigerant
Gas Detector and VRF Refrigerant Pump
Down Package manuals for detail
Typical connections used 3 & 4
6
KSGD-01W/S Semi Conductor Standalone Refrigerant Leak Detector
Operation
When the power supply is applied, a green LED will flash to indicate power “ON.” After approximately 5 minutes, the
green LED will be illuminated permanently and the detector is operational. At alarm the LED will flash red/amber, the
buzzer will start and the relay will change status. In case of sensor fault, the LED will flash red with an amber pulse, the
relay will change status, and the buzzer will give a sound every minute.
Housing White plastic (KSGD-01W) or Silver Facia (KSGD-01S)
Power 12-24V AC/DC 12-24V AC/DC
Visual indication 3-coloured LED 3-coloured LED
Output Relay 125VAC, 15VA Relay 125VAC, 15VA
Buzzer 85 dB 2300Hz (+/-300Hz) 85 dB 2300Hz (+/-300Hz)
Screw Terminal Connections Terminal 5 x 2.5mm Terminal 5 x 2.5mm
Size 85 x 85 x 32 mm 86 x 86 x 50 mm
Weight 85 grams 160 grams
Power consumption Max 2.5VA, normal 1VA Max 2.5VA, normal 1VA
Technical Specification
Operation Matrix
Status Relay contacts LED Buzzer
Power off 4 & 5 Closed Off Off
Warm-up (5 minutes) 3 & 4 Closed Green/Red (1 Hz) Flashing Off
Normal operation 3 & 4 Closed Constant Green Off
Sensor fault 4 & 5 Closed Flashing red (1 Hz) + one (1)
Amber flash per minute Pulses 1/minute
Indications and alarms as gas concentrations increase:
B) ≥1000ppm & >2 seconds &
<30 minutes 3 & 4 Closed Flashing Red (2 Hz) Off
B)≥1000ppm & >30 minutes 4 & 5 Closed Flashing Red/Amber (2 Hz) Pulses (2 Hz)
A)≥4000ppm & > 30 seconds 4 & 5 Closed Flashing Red/Amber (4 Hz) Pulses ( 4 Hz)
Auto Reset
After 60 seconds delay 3 & 4 Closed Constant Green Off
Power Supply 12/24V AC/DC 1 & 2 Constant Green Off
7
KSGD-01W/S Semi Conductor Standalone Refrigerant Leak Detector
Please be sure to put the contact address/telephone number
on this manual before handing it to the customer.
MITSUBISHI ELECTRIC UK
MITSUBISHI ELECTRIC UK, TRAVELLERS LANE, HATFIELD, HERTFORDSHIRE, AL10 8XB
8

This manual suits for next models

1

Other Mitsubishi Electric Security Sensor manuals

Mitsubishi Electric k-con KSGD-01WS-B User manual

Mitsubishi Electric

Mitsubishi Electric k-con KSGD-01WS-B User manual

Mitsubishi Electric MP-EG-TS-V2 User manual

Mitsubishi Electric

Mitsubishi Electric MP-EG-TS-V2 User manual

Mitsubishi Electric PAC-USSEN002-FM-1 User manual

Mitsubishi Electric

Mitsubishi Electric PAC-USSEN002-FM-1 User manual

Mitsubishi Electric PZ-70CSD-E Quick guide

Mitsubishi Electric

Mitsubishi Electric PZ-70CSD-E Quick guide

Mitsubishi Electric LX-005TD User manual

Mitsubishi Electric

Mitsubishi Electric LX-005TD User manual

Mitsubishi Electric PAC-USSEN001-FM-1 Service manual

Mitsubishi Electric

Mitsubishi Electric PAC-USSEN001-FM-1 Service manual

Popular Security Sensor manuals by other brands

MSA Chillgard VRF operating manual

MSA

MSA Chillgard VRF operating manual

Agilent Technologies 1260 Infinity user manual

Agilent Technologies

Agilent Technologies 1260 Infinity user manual

Patlite LR6-IL Operation manual

Patlite

Patlite LR6-IL Operation manual

Moeller CBMA-02/01 Assembly instructions

Moeller

Moeller CBMA-02/01 Assembly instructions

BEMKO SES15BL instructions

BEMKO

BEMKO SES15BL instructions

Siemens SICAM V01.00 manual

Siemens

Siemens SICAM V01.00 manual

Optex OA-PRESENCE TN quick start guide

Optex

Optex OA-PRESENCE TN quick start guide

Alanco Technologies, Inc. TSI PRISM PASS2M user guide

Alanco Technologies, Inc.

Alanco Technologies, Inc. TSI PRISM PASS2M user guide

Sensitron SMART S-MS MED instruction manual

Sensitron

Sensitron SMART S-MS MED instruction manual

Protekt CRW 300  Series instruction manual

Protekt

Protekt CRW 300 Series instruction manual

PCB Piezotronics 132B38/010PH Installation and operating manual

PCB Piezotronics

PCB Piezotronics 132B38/010PH Installation and operating manual

Micropack FDS300 installation guide

Micropack

Micropack FDS300 installation guide

Omron K2CU - manual

Omron

Omron K2CU - manual

Ecolink Firefly WST-602 user manual

Ecolink

Ecolink Firefly WST-602 user manual

Niko 351-0314 Series manual

Niko

Niko 351-0314 Series manual

schmersal RSS 36-D-ST-DU manual

schmersal

schmersal RSS 36-D-ST-DU manual

PNI A005 user manual

PNI

PNI A005 user manual

PGST PA-92R Manual instruction

PGST

PGST PA-92R Manual instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.