7
Control commands
The following control commands can be triggered with the
remote control:
Control
command
Description Can be trigge-
red by Sendo-
Pro / theSenda
B (app)
Can be trigge-
red theSenda
P
Programming
mode
Activation of pro-
gramming mode
x x
Teach-in chan-
nel C1
x x
Master/Slave
query
Master/Slave x
Switching light All lighting groups
can be switched on
and off.
x x
Presence test On/Off x x
Test light On/Off x
Restart Restart detector x x
Teach-in
The currently measured brightness value will be accepted
as the brightness set point value. Transfer is made to the
currently active brightness setpoint value. That is, if the alter-
native brightness set point value is switched to, the currently
measured brightness value [lux] is transferred to the alter-
native brightness set point value via the teach-in command.
Values outside the permitted range will automatically be set
to the appropriate limit value.
Test mode
The theRonda S360 KNX has two test modes.
•Presence test
•Light test
1. Presence test
The presence test is used for checking the detection area and
the parallel switching.
Activation Presence test control command "On" with "SendoPro
868-A" management remote control or with "theSenda B"
app remote control (with "theSenda Plug" app). On "the-
Senda P" installation remote control with the button..
ON telegram via bus object (51).
The presence test can be activated anytime.
End With subsequent restart:
Presence test control command "Off" with "SendoPro
868-A" management remote control or with "theSenda
B" app remote control (with "theSenda Plug" app). On
"theSenda P" installation remote control with the button
(reset).
OFF telegram via bus object (51)
Mains failure and thus power up
Automatically according to the time set in the ETS
Without restart:
Activation of light test with "SendoPro 868-A" management
remote control or with "theSenda B" app remote control
(with "theSenda Plug" app).
Indication of
LED status
channels
Description
On When movement occurs, the LED goes on and channels C1,
C2 switch on.
Off After the movement stops, the LED is off and the channels
C1, C2 switch after approx. 10 s.
Test response
•Deactivated brightness measurement, light output does
not react to brightness
•The detector reacts as in conguration type fully auto-
matic, even if semi-automatic is set.
•The control type changes to switching if the control type
is set to constant light control. The light is not controlled.
•Light «On» during motion; light «Off» during absence
•Channels C1 and C2 light have a xed time delay of 10 s.
•The presence channels react unchanged as in normal
operation.
Commands and adjustable parameters
In the presence test, the following commands are possible
with «SendoPro 868-A» management remote control and
«theSenda B» app remote control (with «theSenda Plug»
app):
•Ending the presence test
•Activating the light test
•Changing detection sensitivity
The selected detection sensitivity (1 . . 5) is unchanged on
activation of the presence test. The sensitivity can be adjusted
during the test and will remain unchanged after completion
of the presence test. The presence detector performs a restart
after the end of the test mode.
2. Light test
The light test is used to check the brightness switching
value/set point value.
Activation Presence test control command "On" with "SendoPro
868-A" management remote control or with "theSenda B"
app remote control (with "theSenda Plug" app).
ON telegram via bus object (52)
The light test mode can be activated anytime.
End With subsequent restart:
Light test control command "Off" with "SendoPro 868-A"
management remote control or with "theSenda B" app
remote control (with "theSenda Plug" app). On "the-
Senda P" installation remote control with the button
(reset).
OFF telegram via bus object (52)
Mains failure and thus power up
Automatically according to the time set with the ETS
Without restart:
Activation of presence test with "SendoPro 868-A" manage-
ment remote control, "theSenda B" app remote control
(with "theSenda Plug" app), or "theSenda P" installation
remote control using the "test" button.
LED display Description
Flashing,
5 s On
0.3 s Off
The LED ashes as long as the light test is active.
Test response
The presence detector responds 100 % like in normal ope-
ration, only the reaction to bright/dark is faster. This makes
it possible to test the brightness threshold and the adaptive
response. The control is also faster. All selected functions and
parameters remain unchanged.
Commands and adjustable parameters
In the light test mode, the following commands are possible
with «SendoPro 868-A» management remote control and