Configuration
How to turn on the inverter and the Menu system
Press the ON/OFF buon to turn the
inverter on in auto mode. When the
inverter is ON or in AUTO mode, press
the ON/OFF buon again to turn it o.
Navigaon on the system menus are
achieved by using the direconal arrows
and the ENTER ( ) key. The EXIT
buon will return you to the previous
menu.
NOTE: The default password is 0001.
Battery Setup
MENU System Cong/Setup System Setup Baery Opons
Obtain the correct values from your baery manufacturer, and congure the follow-
ing Powerstar parameters (refer to secon 5. Baeries of the manual for more in-
fo):
Setpoint 071 Ba Float Cell Volts
Setpoint 072 Ba Bulk Cell Chg Volts
Setpoint 073 Ba Equ Cell Volts
Setpoint 077 Equ Enabled
Setpoint 090 Max Ba Chg Amps
NOTE: When an external Maximum Power Point Tracker (MPPT) is connected to the
baeries, the equalising charge must be disabled to ensure stable operaon of the
inverter. The MPPT bulk and oat voltages should also be set up to be around 0.3V
higher than the values used for the inverter.
Source Setup
MENU System Cong/Setup System Setup Source Opons
If an auto-start generator is connected to Source B, congure Setpoint 017 Src B
Type as generator (GEN).
If a manual start generator is connected to Source B, congure Setpoint 017 Src B
Type as ulity (UTIL).
Utility Setup
MENU System Cong/Setup System Setup Ulity Opons
Export of excess power back into the ulity is disabled by default. If required, enable
it through Setpoint 057 Export Enabled.
Power ratings
The maximum power that can be drawn from Source A and Source B is the power
rang of the Powerstar. The maximum connuous Output power is double the pow-
er rang while the ulity/ generator is available and the baeries have adequate
charge.
NOTE: Drawing more the rated power at the Output for more than a short me is
not recommended, as it discharges the baeries which lowers their lifespan, and
might cause the inverter to trip once the baeries are depleted while the grid is sll
connected.
Beeping
The inverter will beep when a fault occurred (long connuous beeps) or when the
Output power exceeds the power rang of the inverter (intermient short beeps).
Beeping during a fault cannot be disabled. To disable beeping when output power
exceeds the power rang, congure the Keypad Opon (MENU System Cong/
Setup Keypad Setup) Sounds to OFF.
Minimum battery size for an 18/24kVA inverter is 600Ah @ C20.
Incorrect battery setup may cause permanent damage to batteries.