Moore Industries SPA User manual

SPA
SPA
Site-Programmable AC
Current &Voltage Alarms
Site-Programmable AC
Current & Voltage Alarms
April 2016
224-770-00E
AC

Table of Contents
The SPA AC Input AlarmTrip.......................................................................................................3
Programmable Inputs ....................................................................................................3
Programmable Outputs .................................................................................................3
Programmable Input Failure Alarms ............................................................................3
Universal Mounting........................................................................................................3
Specifications...........................................................................................................4
Internal Settings ............................................................................................. 5
Programming the SPA AC Input AlarmTrip.................................................. 8
View Settings..................................................................................................................8
Password ......................................................................................................................10
Configure Options........................................................................................................10
Scaling Input“Smart Scaling”....................................................................................12
Applying Input“Bench Ranging”................................................................................14
Scaling the Display......................................................................................................16
Enter Curve...................................................................................................................17
Analog Output Scaling ................................................................................................18
Trim Analog Output......................................................................................................19
Configure Alarm...........................................................................................................20
Change the Password..................................................................................................22
Set the StartTimer .......................................................................................................22
Installation..................................................................................................... 23
Operation....................................................................................................... 24
Customer Service......................................................................................... 27
Guidelines & Certifications ......................................................................... 28

Site-Programmable AC
Current & Voltage Alarms
SPA
The Interface Solution Experts 3
The SPA AC Input AlarmTrip
This is the users’manual for Moore Industries’ family
of SPA Site-Programmable AC Current and Voltage
Alarms. The SPA monitors a process input or inputs
and provides user-configurable, contact closure
outputs whenever that input falls outside a user-set,
high or low trip point. SPAs are typically used to
activate a warning light, bell, or buzzer; or to initiate
a system shutdown, thus acting as a simple, but
highly reliable and effective means of safe-guarding a
process.
The following guidelines are used in this manual:
WARNING - Hazardous procedure or condition that
could injure the operator.
Caution - Hazardous procedure or condition that could
damage or destroy the unit.
Note - Information that is helpful for a procedure, con-
dition, or operation of the unit.
Programmable Inputs
The Programmable AC Current & Voltage unit, or
SPA AC, handles either current or voltage inputs in any
user set span in a 0-250VAC or 0-5AAC range.
Programmable Outputs
The SPA AC can be equipped with an analog output
option to provide either a 1-5V or 0-20mA output.
Analog output equipped units are set by the user to
provide either current (switchable between source or
sink modes), or voltage.
The source/sink setting for the optional analog output
is controlled by DIP switches that are located behind
an easy-to-remove access panel inside the unit’s
housing.
Programmable Input Failure Alarms
SPA alarm setup is quick, intuitive, and flexible. Most
unit operating parameters can be viewed and/or set
using push buttons and a series of simple, “plain
English” menu prompts displayed on the integrated
front panel LCD.
Failsafe or Non-failsafe alarm functioning and
source/sink settings for the optional analog output
are controlled by DIP switches that, together with
a security jumper, are located behind an easy-to-
use access panel inside the unit housing. Unit
disassembly is unnecessary.
Universal Mounting
The SPA is housed in a “universal” DIN case that can
be mounted on both 32mm G-type (EN50035) and
35mm Top Hat (EN50022) DIN-rail. The Installation
section of this manual gives the dimensions of the
housings for the various alarm configurations.

SPA
Site-Programmable AC
Current & Voltage Alarms
4 The Interface Solution Experts
Specifications and information subject to change without notice.
Specifications
Repeatability:
Trip point repeats within
±0.1% of input span
Display Accuracy:
±1 digit;When scaling the
display (in Custom Mode),
high input-to-display span
ratios decrease display
accuracy
Input Accuracy:
Current input, ±5.0mAac;
Voltage input, ±0.25Vac
(±0.1% of max. span)
Stability: ±0.1% of
calibrated span, maximum,
over 6 months
Deadband: 250V or 7.5A,
maximum in Linear Mode;
equivalent of maximum
input range in user-set
engineering units in Custom
Mode
ResponseTime:
600 milliseconds (defined
as time from step change
on input to alarm state
change when alarm is set
to trip mid-point)
AlarmTrip Delay: Pro-
grammable from 0-60
seconds
Isolation: 1000Vrms
between case, input, output
(units with -AO option) and
power, continuous, and will
withstand a 1500Vac di-
electric strength test for one
minute without breakdown
LineVoltage Effect:
±0.005% of span for a 1%
change in line voltage (ac
or dc)
Performance
Ambient
Conditions
Ambient
Conditions
(continued)
Adjustments
Indicators
Weight
Power Consumption:
2-4W, nominal;
6W, maximum
Input Impedance: 160KΩ
for voltage inputs; 0.002Ω
for current inputs
Input Over-Range Protec-
tion: Current: 7.5A rms
continuous, 10A rms for
<1.0sec;Voltage: 264Vac
WITH ANALOG OUTPUT
Output Accuracy: ±0.03%
of output span (includes the
combined effects of linear-
ity, hysteresis, repeatability,
and adjustment
resolution)
ResponseTime: 250
msec maximum time for
output to go from 10% to
90% for step change on
input
Ripple (up to 120Hz): Cur-
rent output, 10mV peak-to-
peak max. when measured
across a 250Ωresistor;
Voltage output, 50mV peak-
to-peak max.
Output Limiting:
117% of span max.,
115% of span typical
Load Effect: ±0.01% of
span from 0 to maximum
load resistance on current
output
Operating Range:
–25°C to +70°C
(–13°F to +158°F)
Storage Range:
–40°C to +85°C
(–40°F to +185°F)
AmbientTemperature
Effect: ±0.015% of output
span per °C maximum;
Relative Humidity:
0–95% non-condensing
RFI/EMI Protection:
10V/m, 20 to 1000MHz, as
per SAMA 33.1 - ABC with
0.5% of span or less error
Digital Filter: 50 or 60Hz
(user selectable)
Common Mode Rejection:
100dB @ 50/60Hz
Front panel push buttons
control settings for zero, span,
alarm trip points,
high/low alarms, etc.; Easy
access internal settings select
current (source or sink) or
voltage output, and failsafe or
non-failsafe alarm functions;
Internal jumper and menu
password protect parameter
settings
LCD: 2x4 character, backlit,
alphanumeric readout accu-
rate to the nearest digit
Range: -9999 to 9999;
Decimal point can be user-set
when in Custom Mode
LED’s: Dual-colorTRIP light
(one for each relay) shows
green for non-alarm, red for
alarm; READY light indicates
normal operation, extin-
guishes in the event of any
internal failure; INPUT light is
always green
510 g (18 ounces)
Performance
(continued)
Performance
with Analog
Output
(-AO Option)

Site-Programmable AC
Current & Voltage Alarms
SPA
The Interface Solution Experts 5
Internal Settings
The Failsafe/Non-failsafe relay and the password
security functions are controlled by means of simple
DIP switches and a single jumper inside the unit
housing.
If the unit is equipped with the –AO option, voltage and
current sink/source selection is also inside.
The SPA housing is fitted with a sliding access door in
its bottom panel. Figures 1, 2, and 3 show the panel
and the location of each of the controls for setting:
• PasswordSecurityON/OFF(Figure 1)
• Failsafe/Non-failsafeAlarmFunction (Figure 2)
• CurrentSource/SinkorVoltage(Figure 3)
(Available in AO-equipped SPA only)
NOTE:
SPAs equipped with the –DPDT option make
use of switches 1 and 2 only (see Figure 2).
Figure 1. Setting the Internal Jumper for Password Security ON or OFF
SLIDING PANEL
SPA UNDERSIDE SET PASSWORD SECURITY
PASSWORD SECURITY
IS ON. PASSWORD
REQUIRED.
PASSWORD SECURITY
IS OFF. PASSWORD
NOT REQUIRED.
NOTE: THE THREE PINS TOWARD THE LEFT SIDE OF THE COMPARTMENT
ARE FOR FACTORY TESTING ONLY.
DO NOT INSTALL JUMPERS ON THESE PINS!
BACK
NO1
CM1
NC1
NO2
CM2
NC2
GND
RELAY 1 RELAY 2
POWER
AC OR DC

SPA
Site-Programmable AC
Current & Voltage Alarms
6 The Interface Solution Experts
Figure 2. Setting the Internal DIP Switches for Failsafe or Non-Failsafe Alarm Function
FAILSAFE
=
NON-FAILSAFE
=
SET FAILSAFE/NON-FAILSAFE
1na 2na
EXAMPLE:
ALARM 1 = NON-FAILSAFE
ALARM 2 = FAILSAFE
BACK
NO1
CM1
NC1
NO2
CM2
NC2
GND
RELAY 1 RELAY 2
POWER
AC OR DC
FRONT
SPA UNDERSIDE
NOTE: THIS 4-POSITION SIP SWITCH MAY VARY IN LOCATION BASED ON THETYPE OF SPA USED
SLIDING
PANEL

Site-Programmable AC
Current & Voltage Alarms
SPA
The Interface Solution Experts 7
Figure 3. Setting the Internal DIP Switches for Current Source/Sink or Voltage (AO-equipped SPAs only)
FRONT
SPA UNDERSIDE
GND
POWER
AC OR DC
(terminal
labeling)
BACK
SOURCE
CURRENT SINK
CURRENT VOLTAGE
SLIDING
PANEL
SET CURRENT-SOURCE/SINK OR VOLTAGE

SPA
Site-Programmable AC
Current & Voltage Alarms
8 The Interface Solution Experts
Programming the SPA
AC Input AlarmTrips
The SPA operating parameters are set, and the set-
tings are stored in on-board, non-volatile EEPROM.
There are four push buttons on the unit front panel;
VIEW, SELECT, an UP arrow, and a DOWN arrow.
Together with the prompting messages displayed on
the LCD, these are used to access menus, and view/
change the settings for:
• Select Functional Setting (Linear Mode or Cus-
tom Mode) and, if selected, set Custom Mode
Engineering units.
• ScaleInput—SmartScaling
• ApplyInput—BenchScaling
• ScaleDisplayReadout
• SetLinearizationCurve(CustomModeonly)
• ScaleAnalogOutput(AO-equippedunitsonly)
•Trim Actual Output (AO-equipped units only)
•Configure Alarm Functions (Trip points, etc.)
•Change/View Password
• SettheStartTimer(SW-equippedunitsonly)
Main Menu: View Settings
Figure 4 gives an overview of the first level of menus
used to configure the SPA.
On power-up, the AC-input SPA defaults to a display of
the measured value. Pressing the VIEW button ac-
cesses a series of displays that show, in succession,
the settings currently stored in unit memory.
Depending upon whether or not the Security Jumper
has been installed (see Figure 1), SELECT will access
either the first screen in the main configuration menu,
“CONF OPTS”, or the password code query screen,
“ENTR PASS”.
Once the Main Menu has been accessed, the up and
down arrow buttons are used to move through all of
the sub-menus in a loop. Pressing the SELECT button
accesses the screen of the sub-menu currently shown
on the LCD.

Site-Programmable AC
Current & Voltage Alarms
SPA
The Interface Solution Experts 9
Figure 4. The SPA ACIPRG & ACVPRG Main Menu
ENTR
PASS
Enter the password
code to enable
settings changes.
Scale Display:
This menu is only available in units
with the "Cust Func" selection made.
It allows you to set the engineering
units in custom mode.
Scaling the Analog Output:
"Smart Scaling" allows you to config-
ure the zero and full scale analog
output without connecting the SPA to
a calibration setup.
(Requires SPA with the –AO Option)
Configure Options:
Set the desired Linearization Function.
(Either standard LINR or custom CUST)
Applying the Input:
Adjust the input by applying the
input and capturing the actual
input.
Entering Segment Endpoints:
In custom mode, and with Linearity set
to ON, program up to 20 linearization
points into non-volatile memory.
Trim Analog Output:
Connect the SPA into a calibration
setup as shown in the manual and
trim the analog output.
Scaling the Input:
Select the zero and full input values.
(Either between 0-5AAC or 0-250VAC)
Password Jumper
installed in OFF position. Password Jumper
installed in ON position.
VIEW current settings
Front Panel
Push Buttons
Inactive during operation.
Inactive during operation.
SELECT
Use or push buttons to scroll
through menus and sub-menus.
Use SELECT push button to access
menu and/or make a choice.
VIEW
CONF
OPTS
SCLE
INPT
APLY
INPT
SCLE
DSPL
ENTR
CURV
SCLE
AO
TRIM
OUT
CONF
ALRM
Configure Alarm:
Trip Point
Deadband
Trip Delay
High or Low Alarm
Latching or Non-Latching
Start Timer:
Set timer delay from 0-60 seconds
to give motor time to start-up without
tripping alarm.
(Requires SPA with the -SW Option)
Password:
View or Change password
in SPA memory.
PASS
WORD
STRT
TIMR
Configure Exit:
Exit the configuration menus and
return to real-time display of
selected process variable.
CONF
EXIT

SPA
Site-Programmable AC
Current & Voltage Alarms
10 The Interface Solution Experts
Main Menu: Password
This menu is bypassed if the Password Security
Jumper is not installed (see Figure 1). If the jumper
is installed, the menu comes up when SELECT is
pressed from the display of the process variable input.
Main Menu: Configure Options
The Configure Options menu allows the user to
choose between Linear and Custom modes of
functioning.
Linear Function. In its Linear Mode (LINR), the SPA
behaves much like a simple input meter. The display
shows the input in either AAC or VAC, depending on
the type of SPA. Its scaling is tied to any input scaling
performed (set in another menu). If equipped with the
–AO option, SPA output can be scaled independently
with respect to the input.
Custom Function. The Custom Mode sets the unit up
for independent programming of input scaling, display
scaling, and, if equipped with the –AO option, output
scaling. In Custom Mode, the user can select °C, °F,
% of scale, Blank (for raw display); or a user-specified,
4-place engineering unit, set at the factory.
Also, if Custom Mode is selected, the user can select
either linear or non-linear display scaling, which
enables a user-programmed, 20-point linearization
curve set in a separate menu.
NOTE:
The SPA’s Linear Mode and its linearizing
of the Custom Mode functioning are not the
same.
Follow the instructions below to select the correct
function. See Figure 5 for details.
1. SELECT the “CONF OPTS”, then with
“SET FUNC”showing on the LCD, use the
arrow buttons to toggle between“CUST FUNC”
and “LINR FUNC”. Refer to the explanation
above for information about each of the
operating modes.
2. Press SELECT to choose the desired mode.
If you selected“LINR FUNC”, the LCD will
prompt you to exit this menu;if you selected
“CUST FUNC”, continue to step 3 to set up the
custom linearization curve.
3. Press SELECT to begin the process of setting
the desired engineering units to be displayed
during SPA operation. Select the appropriate
engineering units with the SELECT button.
This brings up a sub-menu that allows the
user to choose between a linearized or non-
linearized display of the selected, custom
engineering units.
6. Use the arrow buttons to toggle linearization
on or off, then press SELECT to go to “EXIT
OPTS”.
7. Press SELECT again (from “EXIT OPTS”) to
return to the Main Menu.

Site-Programmable AC
Current & Voltage Alarms
SPA
The Interface Solution Experts 11
SCLE
INPT
EXIT
OPT
LINR
FUNC CUST
FUNC
CUST
FUNC LINR
FUNC
CUST
FUNC
LINR
FUNC
EXIT
OPTS
CUST
EXIT
OPTS
SET
FUNC
CONF
OPTS
CONF
OPTS
LIN
OFF LIN
ON
LIN
ON LIN
OFF
DEGC
ENTR
PASS
CONF
OPTS SET
FUNC CUST
FUNC LINR
FUNC
SET
EGU
DEGC
DEGF
PCT
BLNK
CSTM
EXIT
OPTS
LIN
OFF
LIN
ON
EXIT
OPTS
SET
LIN
CUST
FUNC
LINR
FUNC
WHAT IS THE
CONFIGURATION
OF THE UNIT?
RETURN TO
THE MAIN MENU
OR "CONF EXIT" IF
PASSWORD JUMPER
IS NOT INSTALLED
VIEW
SELECT
VIEW
SELECT VIEW
SELECT VIEW
SELECT
?
VIEW
SELECT
VIEW
SELECT
SELECT
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
Figure 5. The Configure Options Menu

SPA
Site-Programmable AC
Current & Voltage Alarms
12 The Interface Solution Experts
Main Menu: Scaling Input “Smart Scaling”
This feature of the SPA allows users to set the zero
and full scale values of the input from the intended
application without having to connect the unit to any
calibration equipment.
Once the Zero and Full values are set, the SPA auto-
matically routes the user to the next appropriate menu;
Scale the Display, for Custom Mode users; Scale the
Output, for Linear Mode users (with AO-equipped
SPAs); or Configure Alarms, for Linear Mode users
whose units are not equipped with analog output.
Follow the directions below to scale the input.
1. SELECT the “SCLE INPT” menu.
2. SELECT the “SET ZERO”menu, and use
the arrow buttons to set the display to show
the known zero scale input from the intended
application. Holding the button accelerates the
display change. Press SELECT.
3. SELECT the “SET FULL” menu, and use
the arrow buttons to set the display to show
the known full scale input from the intended
application. Holding the button accelerates the
display change. Press SELECT.
4. Scroll to “EXIT SCLE”, and press SELECT.
If the SPA Custom Mode was selected in the
Configure Options menu, the next menu shown
will be Scale the Display, since in Custom
Mode the input, display, and output (if present)
are independent.
If the SPA Linear Mode was selected in the
Configure Options menu, the next menu shown
will either be Scale Analog Output, for units
equipped with an –AO option, or Configure
Alarms.

Site-Programmable AC
Current & Voltage Alarms
SPA
The Interface Solution Experts 13
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT VIEW
SELECT
APLY
INPT
EXIT
SCLE
SCLE
INPT
CUST
FUNC
CONF
OPT
SCLE
DSPL SCLE
AO
WAS
SELECTED
IN ?
YES NO
CONF
OPT
SCLE
INPT
SET
ZERO
SET
FULL
EXIT
SCLE
XXXX
AXXXX
V
XXXX
AXXXX
V
INCREMENT
XXXX (ZERO)
DEPENDING ON
TYPE OF SPA
DECREMENT
XXXX (ZERO)
INCREMENT
XXXX (FULL)
DECREMENT
XXXX (FULL)
DEPENDING ON
TYPE OF SPA
EXIT INPUT SCALING
AND RETURN TO
MAIN MENU
SET LINEAR
OR CUSTOM
ENGINEERING UNITS
FROMTHE
MAIN MENU:
Figure 6. The Input Scaling Menu

SPA
Site-Programmable AC
Current & Voltage Alarms
14 The Interface Solution Experts
Figure 7. The SPA Bench Scaling Setup
INPUT
SOURCE
_
+
AC POWER
SUPPLY
GND
VIEW
SELECT
SITE-PROGRAMMABLE
ALARM
SPA
Main Menu: Applying Input“Bench Ranging”
With this method of calibrating input to the SPA, the
SPA is hooked into a calibration setup and inputs are
“captured” at their zero and full scale values.
Figure 7 shows the setup required for applying and
capturing input scaling for the SPA. After the connec-
tions shown in the diagram have been made, apply
appropriate power and allow 5 minutes for unit warm-
up/stabilization.
Figure 8 shows the SPA menu used in this procedure.
Follow the directions below to complete bench ranging.
1. SELECT the “APLY INPT” menu.
2. SELECT the “SAVE ZERO”menu, and vary
the input to the zero level of the intended
application. When the display shows the
appropriate readout, press SELECT to capture
the value in memory.
3. SELECT the “SAVE FULL”menu, and vary the
input to the full level of the intended application.
When the display shows the appropriate
readout, press SELECT to capture the value in
memory.
4. Use the arrow buttons to bring up the “EXIT
INPT”display, and press SELECT to return to
the Main Menu.

Site-Programmable AC
Current & Voltage Alarms
SPA
The Interface Solution Experts 15
SCLE
INPT
APLY
INPT
SAVE
ZERO
SAVE
FULL
EXIT
INPT
XXXX
AXXXX
V
XXXX
AXXXX
V
WHAT IS THE
CONFIGURATION
OF THE UNIT? WAS SELECTED IN
WAS SELECTED IN
AND
UNIT IS EQUIPPED
WITH AO
WAS SELECTED IN
EXIT APPLY INPUT
AND RETURN TO
THE MAIN MENU
"SMART" SCALING
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT VIEW
SELECT
VIEW
SELECT
CONF
OPTS
SCLE
DSPL
EXIT
INPT
SCLE
INPT
LINR CONF
OPTS
CONF
ALRM LINR
SCLE
AO
CONF
OPTS
SCLE
DSPL
CSTM CONF
OPTS
CAPTURES
INPUT
FROMTHE
MAIN MENU:
DEPENDING ON
TYPE OF SPA
DEPENDING ON
TYPE OF SPA
Figure 8. The Applying Input Menu

SPA
Site-Programmable AC
Current & Voltage Alarms
16 The Interface Solution Experts
FROMTHE
MAIN MENU:
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
SCLE
AO
EXIT
DSPL
SET
DP
CNFG
OPTS
CNFG
OPTS
CONF
ALRM
SCLE
AO
IS THE
AO OPTION
INSTALLED?
NO
YES
XXXX
EGU
XXXX
EGU
XXXX
EGU
SET
DP
DSPL
ZERO
DSPL
FULL
EXIT
DSPL
APLY
INPT
SCLE
DSPL
SMART SCALING
SHIFTS DECIMAL TO THE RIGHT
SHIFTS DECIMAL TO THE LEFT
SETS
DECIMAL
POSITION
INCREMENTS SCALED
ZERO DISPLAY
USES THE
UNITS CHOSEN
IN
USES THE
UNITS CHOSEN
IN
DECREMENTS SCALED
ZERO DISPLAY
DECREMENTS SCALED
FULL DISPLAY
INCREMENTS SCALED
FULL DISPLAY
EXIT
SCALE DISPLAY
AND RETURN TO
THE MAIN MENU
NOTE: MAXIMUM DISPLAY RANGE* = INPUT RANGE
INPUT ACCURACY
(0.25V FOR VOLTAGE INPUTS
5mA FOR CURRENT INPUTS)
*DISPLAY FULL SETTING – DISPLAY ZERO SETTING
Main Menu: Scaling the Display
(Setting the Engineering Units
in Custom Mode)
This is the menu with which the SPA user can further
“customize” unit operations. This menu is available
only in units where the “CUST FUNC” Custom Mode
selection has been made in the Configure Options
menu, earlier.
NOTE:
The settings for decimal place and zero and full scale
display that are entered into SPA memory are saved
as numeric values as opposed to percentages.
They are independent of settings for input scaling
and trip points.
If changes are made to the Input Scaling or Trip Points
(in the Configure Alarms menu), this menu must be
accessed and the values changed appropriately in
order to carry any scaling changes through to
the display.
Use this menu to set the decimal point, the displayed
zero, and the displayed full values.
Figure 9 shows the menu for this procedure.
Figure 9. The Display Scaling Menu

Site-Programmable AC
Current & Voltage Alarms
SPA
The Interface Solution Experts 17
SCLE
DSPL
ENTR
CURV EXIT
CURV
NUMB
PNTS
ENTR
PNT
##
PNTS
PNT
## ####
A/V ####
------
RETURN TO
MAIN MENU
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT VIEW
SELECT VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
SCALE THE LCD
READOUT OF THE
INPUT
MORE
POINTS?
NEXT POINT
NEXT POINT INCREMENT INPUT VALUE
DECREMENT INPUT VALUE
INCREMENT DISPLAY
VALUE IN ENGINEERING
UNITS
DECREMENT DISPLAY
VALUE IN ENGINEERING
UNITS
YES
NO
DECREASE # OF
POINTS TO BE USED
IN CURVE (1-20)
INCREASE # OF
POINTS TO BE USED
IN CURVE (1-20)
SCLE
AO
CONF
ALRM
OR
ENTR
PNT
APLY
INPT
FROM THE
MAIN MENU:
SCLE
AO
OR
CONF
ALRM
EXIT
CURV
Figure 10. The Enter Custom Curve (Custom Linearization) Menu
Main Menu: Enter Curve
(Entering Segment Endpoints
in Custom Mode)
Using this menu the user can program up to 20 lin-
earization points into non-volatile SPA memory. This
capability works exclusively with the unit’s Custom
Mode to make the SPA display linear with respect to
its scaled input. When enabled (in the “CONF OPTS”
menu, discussed earlier), the SPA’s Custom Mode
sets the unit to display the linearized input value in the
user-set engineering units.
As mentioned, the “ENTR CURV” menu is active only
when the SPA’s “CUST FUNC” selection has been
made in the Configure Options menu.
IMPORTANT:
Input zero and full scale as well as display
zero and full scale must be programmed prior
to programming the linearization curve.
The procedure consists of defining the number of
points that are to constitute the linearization curve,
then specifying first the input, then its corresponding
display value at each point.
The “rules” for entering points are:
• Xz<Xn<Xn+1<Xn+2<...<Xn+19<Xf
Where Xz=Input zero, in this case, 0A;
and Xf=Input full scale, in this case, 5A;
Xn, Xn+1 through Xn+19 = Input curve
• Yz<Yn<Yn+1<Yn+2<...<Yn+19<Yf
WhereYz=Display zero, in this case, 0%:
andYf=Display full scale, in this case, 100%;
Yn,Yn+1 throughYn+19 = Display curve
NOTE:
The endpoints of the curve must
fall within a range defined by the zero and full
scale values for both the input and the display.
Figure 10 shows the menu.

SPA
Site-Programmable AC
Current & Voltage Alarms
18 The Interface Solution Experts
FROM THE
MAIN MENU:
APLY
INPT
TRIM
OUT
EXIT
Z/FS
SET
ZERO
SCLE
DSPL
SCLE
AO
SET
ZERO
SET
FULL
EXIT
Z/FS
XXXX
MA XXXX
VOLT
XXXX
MA XXXX
VOLT
"SMART" SCALING
DEFAULTS TO
LAST SELECTED
INCREMENTS
OUTPUT ZERO
DECREMENTS
OUTPUT ZERO
INCREMENTS
OUTPUT FULL SCALE
DECREMENTS
OUTPUT FULL
SCALE
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT VIEW
SELECT
VIEW
SELECT
EXIT
SCALE OUTPUT
AND RETURN TO
THE MAIN MENU
NOTE: RE-RANGING THE UNIT NULLIFIES ANY OUTPUT TRIM. RE-TRIM AFTER ANY RE-RANGING.
Main Menu: Analog Output Scaling
(For SPA’s with –AO option)
This menu is only applicable to those SPA’s equipped
with an analog output option. Scaling for the analog
output of the SPA is stored as numerical values in unit
memory. They are not stored as percentages of scale.
Figure 11. The Analog Output Menu
NOTE:
If either Input Scaling or Display Scaling is changed,
any existing scaling operating on the analog output
(if present) must also be changed.
Figure 11 shows the menu for this procedure.

Site-Programmable AC
Current & Voltage Alarms
SPA
The Interface Solution Experts 19
TRIM
OUT
TRIM
ZERO
TRIM
ZERO
TRIM
FULL
TRIM
FULL
EXIT
OUT
CONF
ALRM
TRIM
ZERO
TRIM
FULL
TRIM
ZERO
EXIT
OUT
EXIT
OUT
TRIM
FULL
SCLE
AO
CONF
ALRM
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
VIEW
SELECT
FLASHING
FLASHING
INCREMENT
DECREMENT
INCREMENT
DECREMENT
MAIN MENU
Main Menu:Trim Analog Output
This procedure is only required on those SPAs
equipped with the –AO option. Figure 12 shows the
setup needed. Figure 13 shows the menu.
Connect the unit as shown, apply the appropriate
power, and allow 5 minutes for stabilization/warm-up.
1. SELECT the “TRIM OUT” menu.
2. Use the arrow buttons to choose the level, zero
or full scale, that is to be trimmed.
3. Press SELECT to begin the trim process. The
display will begin to flash the “TRIM ZERO”
or “TRIM FULL” screen, depending upon the
option chosen in step 2.
4. While monitoring the reading on the meter, use
the arrow buttons to adjust the output to the
desired level. Use the meter in the setup to
monitor the output as the output is adjusted.
5. When the output is set as desired, press
SELECT. This sets the adjustment into SPA
memory, and brings up either the next output
level to be adjusted (repeat steps 3, 4, and 5),
or “EXIT OUT” if both zero and full scale output
have been adjusted.
Figure 12. Connections for Trimming SPA Analog Output
INPUT
SOURCE
_
+
MULTIMETER
OR
MILLIAMETER
+_
+_
AC POWER
SUPPLY
GND
VIEW
SELECT
SPA
SITE-PROGRAMMABLE
ALARM
READY
INPUT
TRIP 1
TRIP 2
Figure 13. The Trim Output Menu

SPA
Site-Programmable AC
Current & Voltage Alarms
20 The Interface Solution Experts
Main Menu: Configure Alarm
The Configure Alarm menu sets the trip point(s),
Deadband, Trip Delay, High or Low Alarm function, and
Latching or Non-Latching operation.
After selecting the “CONF ALRM” menu, use the
arrow buttons to scroll through the alarm operation
parameters. Press SELECT to access the settings for
the displayed parameter.
Trip Point(s)
There are two options for setting the trip points of the
installed alarms,“ENTR TRIP” and “APLY TRIP”.
In the “ENTR TRIP” menu, the user employs the Smart
Ranging feature of the SPA, entering the desired trip
point with the front panel push buttons.
In the “APLY TRIP” menu, the SPA must be set up with
calibration equipment (see Figure 7, page 12).
The unit then “captures” its trip point from the input of
an adjustable source. The process for this is similar to
capturing the input: hookup the SPA into a calibration
setup, set the SPA’s menu appropriately, apply the
amount of power that you would like the trip point set
at, and press SELECT.
Other Configuration Options
Setting the deadband, delay, high/low trip, and latching
or non-latching options is a simple matter of using the
front-panel buttons to select the appropriate values.
Table of contents
Other Moore Industries Security System manuals

Moore Industries
Moore Industries STA HLPRG User manual

Moore Industries
Moore Industries SPA TPRG User manual

Moore Industries
Moore Industries CPA User manual

Moore Industries
Moore Industries DDA Series User manual

Moore Industries
Moore Industries SPA2 TPRG User manual

Moore Industries
Moore Industries DCA S User manual

Moore Industries
Moore Industries SPA HLPRG User manual
Popular Security System manuals by other brands

Visonic
Visonic MCS-700 installation instructions

Polaroid
Polaroid ID-3000 operating instructions

HYDRO-RAIN
HYDRO-RAIN HRL-100-MS instruction manual

Ecco
Ecco B200 R65 Installation & operating instructions

Wisenet
Wisenet SDH-B84045BF quick start guide

Unitronics
Unitronics Jazz Micro-OPLC JZ10-11-T17 installation guide