Moore Industries SPA2 TPRG User manual

SPA2
Programmable Current/Voltage
Limit Alarm Trips
All product names are registered trademarks of their respective companies.
SPA2
Programmable Current/Voltage
Limit Alarm Trips
June 2004
224-790-00A
HLPRG

ENTER
PASS
Enter the password
code to enable
settings changes.
(Default = 55)
Scale Input "Smart Scaling":
Set the values to be displayed
at zero and full scale without
calibration equipment.
Trim Analog Output:
Connect the SPA into a calibration
set-up as shown in the manual and
trim the analog output.
(Requires -AO Option)
Configure Input:
Select volt or current input.
Defaults to mA.
Password:
View or change password.
Apply Input (Bench Scaling):
Using calibration equipment,
capture the zero and full scale
values.
Exit Configuration Menu:
Return to process display.
Configure Options:
Set engineering units, decimal
places, 50/60Hz filter, broken wire
detection and scaling.
Security Jumper
installed in OFF position.
Security Jumper
installed in ON position.
Front Panel
Pushbuttons
Use the UP and DOWN pushbuttons
to scroll through menus and sub-menus.
Use the SELECT pushbutton to access
menus and/or make a choice.
CONFG
INPUT
CONFG
OPTNS
SCALE
INPUT
APPLY
INPUT
TRIM
AOUT
CONFG
EXIT
CONFG
ALARM
Configure Alarm:
Set trip point, dead band,
high/low trip, delay, and
latching/non-latching.
CONFG
PASWD
TRIM
INPUT
Trim Input:
Match the actual reading of your
SPA to a calibrated or known
value.
CONFG
AOUT
Scale Analog Output:
Connect the SPA into a calibration
set-up as shown in the manual
and scale the analog output.
(Requires -AO Option)
SCALE
AOUT
SELECT
DOWN
UP
D
D
D
D
D
D
D
D
D
D
U
U
U
U
U
U
U
U
U
U
2
2
2
Configure Analog Output:
Select volt or current output.
Choose damping value and fail mode.
SPA2(HLPRG) Quickstart Guide
Use the front pushbuttons to quickly and easily set-
up the SPA2for your application. After programming
your alarm using the diagram below, install the unit
into your application using the connection diagrams
and terminal designation table located in this
manual.

Table of Contents
Introduction ....................................................................................................5
About This Manual .......................................................................................................... 5
Model and Serial Numbers ............................................................................................. 5
Inputs .............................................................................................................................. 5
Outputs............................................................................................................................ 5
Options............................................................................................................................ 5
Internal Settings .............................................................................................................. 5
Specifications ................................................................................................6
Dimensions ..................................................................................................................... 7
SPA2Configuration: Front Panel Pushbuttons ...................................... 10
Main Menu/View Menu ................................................................................................. 10
Password ...................................................................................................................... 10
Configuring the Input ..................................................................................................... 13
Configuring the Options ................................................................................................ 14
Scaling the Input ........................................................................................................... 16
Applying Input (Bench Scaling)..................................................................................... 17
Input Trimming .............................................................................................................. 17
Configuring the Analog Output (-AO Option) ................................................................. 19
Scaling the Analog Output (-AO Option) ....................................................................... 20
Trimming the Analog Output (-AO Option) .................................................................... 21
Configuring the Alarm(s) ............................................................................................... 23
Password Configuration ................................................................................................ 29

SPA2Configuration: PC Configuration Software ................................... 30
Installing the Configuration Software ............................................................................ 30
Connecting the SPA2to the PC..................................................................................... 30
PC Configuration Software Summary ...................................................... 32
Status and Tool Bar Legend ......................................................................................... 33
Configuration Screens............................................................................... 33
Input .............................................................................................................................. 33
Display .......................................................................................................................... 34
Alarms........................................................................................................................... 35
Analog Output ............................................................................................................... 37
Scaling .......................................................................................................................... 40
Custom Curve ............................................................................................................... 40
Error Codes ................................................................................................. 42
Installation ................................................................................................... 43
Mounting ....................................................................................................................... 43
Making the Electrical Connections ................................................................................ 43
Recommended Gound Wiring Practices ....................................................................... 43
CE Conformity............................................................................................................... 43
Operation..................................................................................................... 43
Maintenance ................................................................................................................. 43
Customer Support ...................................................................................... 43

The Interface Solution Experts 5
SPA2
Programmable Current/Voltage
Limit Alarm Trips
Introduction
This is the user’s manual for Moore Industries’ SPA2
(HLPRG): Programmable Current/Voltage Limit Alarm.
The instrument is configured using a combination of
front panel pushbuttons and a dedicated PC Configura-
tion Program. The SPA2monitors a process variable
and provides up to four, fully user-configurable contact
closure outputs that can be individually programmed to
trip whenever the input falls outside a user-set, high or
low trip point. The SPA2is typically used to activate a
warning light, bell or buzzer; or to initiate a system
shutdown. Thus, the instrument acts as a simple, but
highly reliable and effective means of monitoring and
safe-guarding a process.
About this Manual
Wherever you see a “
Note
”, “
Caution
” or “
WARNING
”
pay particular attention.
WARNING
- Hazardous procedure or condition that
could injure the operator.
Caution
- Hazardous procedure or condition that could
damage or destroy the unit.
Note
- Information that is helpful for a procedure,
condition, or operation of the unit.
Model and Serial Numbers
Moore Industries uses a system of model and serial
numbers to keep track of all of the information on
every unit it sells and services. If a problem occurs
with your SPA2, check for a tag affixed to the unit list-
ing these numbers. Supply the Customer Support rep-
resentative with this information when calling.
Inputs
The SPA2
(HLPRG )(“High Level” Programmable input),
handles either current inputs from 0-50mA (1mA
minimum span) or voltage inputs from 0-10V (250mV
minimum span).
Outputs
Alarms
The SPA2can be ordered with two (-2PRG) or four
(-4PRG) contact closure alarms. Each alarm can be
individually programmed.
2PRG
This is a two relay output with 5A@250Vac or 24Vdc,
50/60Hz non-inductive contact rating. The contact
arrangement is SPDT; however, the -2PRG output is
also available in a DPDT contact arrangement. All
relay contacts (NO, NC and COM) are available for
use. No jumpers are required.
4PRG
This is a four relay output with 5A@250Vac or 24Vdc,
50/60Hz non-inductive contact rating. The contact
arrangement is SPDT. All relay contacts (NO, NC and
COM) are available for use. No jumpers are required.
TX Power
A transmitter excitation power supply (24Vdc
±10%@24mA) is standard on the SPA2 (HLPRG). You
may access this externally at the terminals shown in
Figure 3.
Options
Analog Output (-AO)
The SPA2can be equipped with a scaleable output
option to provide a 0-20mA or 0-10V output. -AO
equipped units are set by the user to provide either
current (user-configurable between source or sink) or
voltage.
Internal Settings
The password security function of the SPA2is con-
trolled by a single jumper inside the top of the unit
housing. You will need to remove the top cover in
order to access the jumper. Refer to Figure 2 for
location and jumper settings.

6 The Interface Solution Experts
SPA2
Programmable Current/Voltage
Limit Alarm Trips
Table 1. Long-Term Stability
Input-to-Output
(Years)
Input-to-Relay
(Years)
Stability
(% of maximum
span)
Current Inputs
Voltage Inputs
1
0.081
0.093
3
0.14
0.16
5
0.18
0.21
1
0.047
0.066
3
0.81
0.114
5
0.105
0.147
Specifications
Alarm Trip Repeatability:
Current inputs, ±2
microamps (0.01% of
20mA span); Voltage
inputs, ±1mV (0.01% of
max. span)
Display Accuracy: ±1
digit; when scaling the
display (or in Custom
Mode), high input-to-
display span ratios
decrease display accuracy
Input Accuracy:
Current inputs, ±2
microamps (0.01% of
20mA span); Voltage
inputs, ±1mV (0.01% of
max. span)
Stability: Refer to
Table 1
Dead Band: 11.5V or
50mA, maximum in Linear
Mode; equivalent of
maximum input range in
user-set engineering units
in Scaling/Custom Mode
Response Time:
256msec maximum
(Defined as the time from
step change on input to
alarm state change when
alarm is set to trip at
mid-point)
Alarm Trip Delay:
Programmable from
0-120 seconds
Line Voltage Effect:
±0.002% of span for a
1% change in line voltage
(AC or DC)
Isolation: 1000Vrms
between case, input,
output (units with -AO
option) and power,
continuous. Will withstand
a 1200Vac dielectric
strength test for one
minute (with no
breakdown)
WITH -RF OPTION:
500Vrms between case,
input, output and power
Power Supply:
24DC range, 18-30Vdc;
UAC range, 90-260Vac;
110DC range, 75-150Vdc
Performance Performance
(continued)
Ambient
Conditions
(continued)
Adjustments
Weight
Power Consumption:
3.5W max. (24DC supply);
4W max. (UAC supply);
6W max. (110DC supply)
Input Impedance:
Current inputs, 20ohms;
Voltage inputs, 1Mohm
Input Over-Range
Protection: Voltage
inputs, ±30Vdc of max.
input span; Current inputs,
±100mA of max. input
span
WITH ANALOG OUTPUT
Output Accuracy:
Current, ±0.01% of max.
span (±2 microamps);
Voltage, ±0.01% of max.
span (±1mV)
Response Time:
256msec maximum
(128msec typical) for the
output to change from
10% to 90% of its scale
for an input step change of
0 to 100%
Ripple (up to 120Hz):
Current output, 10mVp-p
when measured across a
250ohm resistor; Voltage
output, 50mVp-p max.
Output Limiting:
Current outputs,
Voltage output, -0.5-11V
Load Effect (current
outputs): ±0.01% of
span from 0 to maximum
load resistance on current
output
Operating Range:
-40°C to +85°C
(-40°F to +185°F)
Relay Range:
-25°C to +70°C
(-13°F to +104°F)
Storage Range:
-40°C to +85°C
(-40°F to +185°F)
Ambient Temperature
Effect: Current, 2
microamps/°C; Voltage,
1mV/°C; Output, ±0.009%
of max. span/°C
Relative Humidity:
0-95% non-condensing
RFI/EMI Protection:
80-1000MHz, 1kHz AM,
when tested to IEC61326
with 0.5% of span or less
error
WITH -RF OPTION:
20V/m@80-1000MHz,
1kHz AM, when tested to
IEC61326 with 0.5% of
span or less error
Noise Rejection:
Common Mode,
100dB@50/60Hz
Normal Mode,
Current Input, 70dB
typical@50mAp-p@
50/60Hz; Voltage Input,
70dB typical@1Vp-p@
50/60Hz
Front panel pushbuttons
control settings for zero,
span, alarm trip points,
high/low alarms, etc.;
Internal jumper and menu
password protect
parameter settings
LCD: 2x5 14-segment
characters, backlit,
alphanumeric readout
accurate to the nearest
digit.
Range: -99999 to 99999;
Decimal point can be
user-set
LED Type: INPUT LED:
Dual color LED indicates
input failure
READY LED: Green LED
indicates unit is operating
properly
ALARM 1, 2, 3 and 4 LED:
Dual color LED per relay
indicates alarm status
544 g to 601 g
(19.2 oz to 21.2 oz)
Ambient
Conditions
Indicators
Performance
with Analog
Output (-AO
Option)
Specifications and information subject to change without notice.
0-20mA 0, 23.6mA
4-20mA 3.6, 23.6mA
X-20mA (90% of X), 23.6mA
Output Failure Limits

The Interface Solution Experts 7
SPA2
Programmable Current/Voltage
Limit Alarm Trips
Figure 2. Setting the Internal Jumper for Password Security ON or OFF
SPA
READY INPUT TRIP 1 TRIP 2 TRIP 3 TRIP 4
SELECT
DOWN
UP
COM
2
SITE
PROGRAMMABLE
ALARM
C
L
WHEN INSTALLED
WHEN INSTALLED
100mm
(3.94 in)
52mm
(2.05 in)
48mm
(1.89 in)
138mm
(5.43 in) 133mm
(5.24 in) 126mm
(4.97 in)
100mm
(3.94 in)
137mm
(5.39 in)
55mm
(2.17 in)
REMOVE PANEL
BY UNSCREWING
TOP FOUR SCREWS
SET PASSWORD SECURITY
PASSWORD SECURITY
IS OFF. NO PASSWORD
REQUIRED.
PASSWORD SECURITY
IS ON. PASSWORD
REQUIRED.
BACK
TX
+I
COM
+V
-lo Source
+lo Sink
+lo Source
+Vo
-Vo
-lo Sink
INPUT
A OUT
2
SPA TOPSIDE
FRONT
MR
Figure 1. SPA
2
(HLPRG) Dimensions

8 The Interface Solution Experts
SPA2
Programmable Current/Voltage
Limit Alarm Trips
Table 2. SPA
2
(HLPRG) Terminal Designations
Input Type
Current Input
Voltage Input
Top Terminals (Left to Right)
T1 T2 T3 T4 T5 T6 T7 T8 T9 T10
KEY:
AC/DC = Power Input
ACC/DCC = Power Input
CM = Relay Common
COM = Analog Common
DPDT = Double-Pole/Double-Throw
GND = Ground
NOTES:
1. Terminal blocks can accommodate 14-22 AWG
solid wiring.
2. ±Io/±Vo labeling is present only when the unit is
equipped with the Analog Output (-AO) option.
3. Your input power requirement (AC or DC / ACC
or DCC) will depend upon your unit’s power need.
Tx +I COM Not
Used MR MR -Io Source
+Io Sink +Vo -Vo
-Io Sink
MR -Io Source
+Io Sink +Vo
MR
Tx COM
Not
Used +V
I = Current Input
Io = Current Output
MR = Manual Reset
NO = Normally Open
NC = Normally Closed
Sink = Current Sink
Source = Current Source
SPDT = Single-Pole/Double-Throw
TX = Power for 2-wire transmitter
V = Voltage Input
Vo = Voltage Output
-Vo
-Io Sink
+Io Source
+Io Source
Output Type
2PRG
(SPDT Relays)
4PRG
(SPDT Relays)
2 DPDT Relays
Middle Terminals (Left to Right)
11 12 13 14 15 16
NO3 CM3 NC3 NO4 CM4 NC4
Relay 2
CM1
Relay 2
NC1
Relay 2
NO2
Relay 2
CM2
Relay 2
NC2
Output/Power Type
2PRG
(SPDT Relays)
4PRG
(SPDT Relays)
2 DPDT Relays
Bottom Terminals (Left to Right)
B1 B2 B3 B4 B5 B6 B7 B8 B9 B10
Not
Used
AC
or
DC
ACC
or
DCC
GND
GND
N/A N/A N/A N/A N/A N/A
NO1 CM1 NC1 NO2 CM2 NC2 Not
Used
Relay 2
NO1
Not
Used GND
Relay 1
CM1
Relay 1
NC1
Relay 1
NO2
Relay 1
CM2
Relay 1
NC2
Relay 1
NO1
NO1 CM1 NC1 NO2 CM2 NC2
AC
or
DC
AC
or
DC
ACC
or
DCC
ACC
or
DCC

The Interface Solution Experts 9
SPA2
Programmable Current/Voltage
Limit Alarm Trips
Figure 3. SPA
2
(HLPRG) Hook-Up Diagram For Front Panel Configuration
SPA
READY INPUT TRIP 1 TRIP 2 TRIP 3 TRIP 4
SELECT
DOWN
UP
COM
2
SITE
PROGRAMMABLE
ALARM
VOLTAGE
SOURCE
_
+
CURRENT
SOURCE
_
+
2-WIRE
TRANSMITTER
_
+
AC OR DC
POWER
SUPPLY
GND

10 The Interface Solution Experts
SPA2
Programmable Current/Voltage
Limit Alarm Trips
SPA2Configuration:
Front Panel Pushbuttons
The SPA2 (HLPRG) operating parameters may be set
using front panel pushbuttons and/or Moore
Industries’ PC Configuration Software. This section
describes configuration via the front panel
pushbuttons.
There are three pushbuttons on the unit’s front
panel;
UP
,
DOWN
and
SELECT
. Together with the
prompting messages displayed on the LCD, these
are used to access menus, and to view and change
the settings.
Use
SELECT
as your “Enter” button, to make your
selections.
Use the
UP
and
DOWN
buttons to navigate within
the menus.
Note:
All parameters, except the Custom Curve feature,
can be configured using the front panel pushbuttons.
The Custom Curve table can only be configured
using the PC Configuration Software Program.
Main Menu/View Settings
Figure 4 gives an overview of the Main menu; the
View menu is shown in Figure 5.
Upon power-up, the SPA2defaults to a display of the
measured value. Pressing the
DOWN
button ac-
cesses a series of displays that show, in succession,
the settings currently stored in unit memory.
Depending upon whether or not the Security Jumper
has been installed (Figure 2), pressing
SELECT
will
access either the first screen in the main configuration
menu, “CONFG INPUT”, or the password code query
screen, “ENTER PASS”.
Once the Main Menu has been accessed, the
DOWN
button is used to move through all of the sub-menus in
a loop. Pressing the
SELECT
button accesses the
first screen of the sub-menu shown on the LCD.
Password
This menu is bypassed if the Password Security
Jumper is not installed. If the jumper is installed, the
menu comes up when
SELECT
is pressed from the
display of the process variable input. To access the
security jumpers, you must remove the top cover
(refer to Figure 2). The menu is shown as part of
Figure 4. Refer to the
Password Configuration
section
of this manual for a more detailed description of the
password feature.
1. If the jumper is installed, pressing
SELECT
from the display of the process variable input
will bring up the “ENTER PASS” screen.
2. Press
SELECT
again to enter the “PASS”
screen. Use the
UP
and
DOWN
buttons to
enter “55”, the default screen for this point in
the menu.
3. If a password has been set (four characters,
maximum), use the
UP
or
DOWN
buttons to
display the correct password.
When the correct password number is
displayed, press
SELECT
.
Note:
If the correct password is not known, the unit
settings can be viewed, but not changed.
4. If you have entered the correct password, the
input configuration menu, “CONFG INPUT”, will
be accessed. If not, the display will show a
“VIEW ONLY” message.
5. From “VIEW ONLY”, press
SELECT
to go back
to the process variable input. Use the
UP
and
DOWN
buttons to view the settings in the
various menus. The “VIEW ONLY” mode locks
out any attempt to make changes to the
settings.
Note:
The menu to set or change the password stored in
SPA
2
memory is presented in the Password
Configuration section of the manual.

The Interface Solution Experts 11
SPA2
Programmable Current/Voltage
Limit Alarm Trips
PROCESS VALUE
DISPLAY
U/D VIEW MENU
If no PW jumper
SEL If PW jumper fitted ENTER
PASS
U/D
SEL
0
PASS
U = Inc. count
D = Dec. count
VIEW
ONLY
U/D
SEL (if correct PW)
SEL (if incorrect PW)
SEL
CONFG
INPUT
CONFG
OPTNS
SCALE
INPUT
APPLY
INPUT
SEL
SEL
SEL
SEL
CONFG INPUT
menu
CONFG OPTNS
menu
SCALE INPUT
menu
APPLY INPUT
menu
D
D
D
D
U
U
U
U
TRIM
INPUT
SEL TRIM INPUT
menu
CONFG
AOUT
SCALE
AOUT
TRIM
AOUT
SEL
SEL
SEL
CONFG AOUT
menu
SCALE AOUT
menu
TRIM AOUT
menu
D
D
U
U
CONFG
ALARM
CONFG
PASWD
CONFG
EXIT
SEL
SEL
SEL
CONFG ALARM
menu
PASSWORD
menu
CONFG EXIT
menu
D
D
U
U
If no
-AO option
If no
-AO option
D
U
D
U
SEL
D
U
U = UP Key
D = DOWN Key
SEL = SELECT Key
U = No action
D = No action
PW = Password
SPA
READY INPUT TRIP 1 TRIP 2 TRIP 3 TRIP 4
SELECT
DOWN
UP
COM
2
SITE
PROGRAMMABLE
ALARM
Figure 4. Main Menu and Password Menu

12 The Interface Solution Experts
SPA2
Programmable Current/Voltage
Limit Alarm Trips
Figure 5. View Menu
PROCESS VALUE
DISPLAY
D
D
D
D
U
U
U
U
D
U
If no AOUT
XXXXX
ZERO
(IF AOUT)
XXXXX
FULL
(IF AOUT)
*XXXXX
AL1
*XXXXX
AL2
*XXXXX
AL3
*XXXXX
AL4
U/D
U
If no AOUT
If 2 alarms
D
U
*If set as a:
• TRIP alarm, trip point value is displayed along
with an "H" (high alarm) or an "L" (low alarm),
depending upon configuration
• FAULT alarm, "FAULT" is displayed
• ROC (Rate of Change) alarm,
"ROC" is displayed
• If no button is pressed for 10 seconds, the
display returns to the Process Value reading
SPA
READY INPUT TRIP 1 TRIP 2 TRIP 3 TRIP 4
SELECT
DOWN
UP
COM
2
SITE
PROGRAMMABLE
ALARM

The Interface Solution Experts 13
SPA2
Programmable Current/Voltage
Limit Alarm Trips
Configuring the Input
Figure 6 gives an overview of the Input Configuration
menu.
If the Password Jumper is not installed, the password
sub-menu is bypassed, and the “CONFG INPUT”
menu is accessed by pressing
SELECT
from the
process variable display.
1. From the “CONFG INPUT” display, press
SELECT
.
2. At “INPUT TYPE” press
SELECT
. The display
shows, “CURNT” or “VOLTS” (current or
voltage parameter). Use the
UP
or
DOWN
arrow buttons to scroll through the two options
for input type. The default display for this
menu is always the last setting.
3. When the display shows the type of input,
current or voltage, that you choose to use,
press
SELECT
.
4. Next, the available input values are displayed.
Use the
UP
or
DOWN
buttons to scroll through
the selections, choose a value that is greater
than or equal to the maximum value for the
input you will be monitoring and press
SELECT
when the value has been displayed.
5. “EXIT INPUT” appears. If all values in this
parameter have been set, press
SELECT.
If
not, return to the menu and set your values.
6. The next display is the menu for the selection
of functional options, ”CONFG OPTNS”. To
skip the rest of the configuration menus and
return to the process variable display, press
the
UP
button twice (to “CONFG EXIT”), and
press
SELECT
.
Figure 6. CONFG INPUT Menu
SEL
SEL
SEL
TOGGLE
CURRENT/
VOLTS
CONFG
INPUT
INPUT
TYPE
D
U
EXIT
INPUT
U
D
Volt List:
10V
5V
2.5V
1.25V
Current List:
50mA
25mA
12.5mA
6.25mA
CONFG OPTNS menu
SEL
SEL
SEL
Use the
UP
and
Down
buttons
to cycle through
the lists

14 The Interface Solution Experts
SPA2
Programmable Current/Voltage
Limit Alarm Trips
Configuring the Options
Figure 7 gives an overview of the Options
Configuration menu.
You may configure the process variable display,
decimal places, 50/60Hz filter selection, broken wire
detection and the scaling mode from this menu.
To configure the options of the the SPA2:
1. At the “CONFG OPTNS” screen, press
SELECT.
2. “DSPLY MODE” appears. Press
SELECT
to
enter the menu. Choose between “NORM
MODE” and “TOGLE MODE” by using the
UP
and
DOWN
buttons. Press
SELECT.
NORM MODE– Displays only your PV or
AOUT value, whichever you select.
TOGLE MODE– Every four seconds your
display will toggle between two displays that
you choose.
3. Next, “DSPLY SRC 1” appears. Press
SELECT
and choose between “AOUT” (if your
unit is equipped with the -AO option) or “PV” by
using the
UP
and
DOWN
buttons. Press
SELECT.
If you selected “TOGLE MODE”, you will next
be asked to enter your “DSPLY SRC 2” value.
4.
The “DSPLY EGU 1” prompt is brought up.
Press
SELECT
and choose the desired
appearance of your display. Press
SELECT.
If you selected “TOGLE MODE”, you will next
be asked to enter your “DSPLY EGU 2” value.
5. Next, the “SET DPS” display appears. Press
SELECT.
Scroll through the available choices
by using the
UP
and
DOWN
buttons and press
SELECT
once you have made your selection.
6. “SET FILTR” appears; press
SELECT
. Here,
you must select the proper line frequency of
your AC source–50Hz or 60Hz; press
SELECT
.
7
.
When “SET BWIRE” appears, press
SELECT
to enter the menu. You must choose whether
or not to enable Broken Wire Detection. Press
SELECT.
Broken Wire Detection– The SPA2monitors
your process variable. If the monitored value
falls equal to or below a set value, then a state
of Broken Wire is declared.
Caution:
Moore Industries does not recommend use of
broken wire detecton if using a voltage input on the
SPA
2
. Various factors may hinder the unit’s
performance and greatly slow the broken wire
response time. If broken wire detection is used on a
voltage input, testing must be done on a regularly
scheduled basis, both with near-end and far-end
open circuits on each of the wires.
Leakage current into a broken wire can prevent the
voltage from dropping to the broken wire threshold.
For example, on a 1-5V input, with a broken wire
threshold of 0.6V, a leakage current of 1microamp
into the broken wire will hold the input voltage at
approximately 1.1V indefinitely. No alarm results
under these conditions.
If the external wiring is long and has significant
capacitance, broken wire response time is slowed
by the RC time constant of the SPA
2
input
resistance and the external wire capacitance. For
example, 1 km of wire with 100pf/m capacitance and
a far-end break, has a capacitance of 0.1microfarad.
The time constant will be 0.11 seconds. Using a
starting voltage of 3V and a broken wire threshold of
0.6V, the threshold is reached in approximately 0.18
seconds. The instrument response time must be
added to this time.
If both leakage and capacitance exist, the time to
threshold can extend greatly. Using a 5V starting
voltage, 0.6V threshold voltage, 1 km of wire and
0.5 microamps leakage current, the threshold is
reached in 0.42 seconds. The instrument response
time must then be added to this time.
8. “SCALE MODE” appears; press
SELECT
.
Choose whether or not to enable scaling. This
will be configured in the next menu. Select
“SCALE OFF” or “SCALE ON” and press
SELECT.
Scale Mode– This allows you to customize
your display for your application. By example:
if your process is sending a 4-20mA signal to
the SPA2and you wish to view the input as
0-100% then this can be accomplished with the
Scale Mode feature.
9. “EXIT OPTNS” appears. Press
SELECT
.
Proceed to the “SCALE INPUT” menu.

The Interface Solution Experts 15
SPA2
Programmable Current/Voltage
Limit Alarm Trips
Figure 7. CONFG OPTNS Menu
CONFG
OPTNS
D
D
D
D
U
U
U
U
D
U
DSPLY
MODE
DSPLY
SRC1
*DSPLY
SRC2
DSPLY
EGU1
*DSPLY
EGU2
SET
DPS
SEL
D
D
D
U
U
U
D
U
SET
FILTR
SET
BWIRE
SCALE
MODE
EXIT
OPTNS
*DSPLY SRC2 and DSPLY EGU2
are skipped if display is in Normal Mode.
SCALE INPUT menu
D
U
TOGGLE
*NORM/
TOGLE
PV
AOUT
SEL
SEL
SEL
SEL
SEL
PV
AOUT
SEL
SEL
SEE EGU
SELECTION
LIST
SEL
SEL
SEE EGU
SELECTION
LIST
SEL
SEL
AUTO
XXXXX
XXXX.X
XXX.XX
XX.XXX
U
D
SEL
SEL
TOGGLE
60 HZ/
50HZ
SEL
SEL
TOGGLE
BWIRE
ON/OFF
BWIRE
LEVEL
U/D
SEL if
BWIRE ON
X.X
EGU
SEL
TOGGLE
SCALE
ON/OFF
SEL
SEL if BWIRE OFF
SEL
SEL
EGU SELECTION LIST
AUTO MODE
**FROM PC
DEG C
DEG F
KELVN
DEG R
MA
MV
OHMS
PCT
PSI
PSIG
VOLTS
**When FROM PC is selected,
the actual text is input from the
PC Configuration Program.
The display shows the PC default
("*****") until the proper EGU is
downloaded from the PC program.
U
D
U
D
U
D

16 The Interface Solution Experts
SPA2
Programmable Current/Voltage
Limit Alarm Trips
D
D
D
D
U
U
U
U
INPUT
ZERO
INPUT
FULL
SCALE
ZERO
SCALE
FULL
EXIT
SCALE
SCALE
INPUT
SEL
D
SEL TRIM INPUT menu
If Scale Mode OFF
XXXXX
EGU
XXXXX
EGU
XXXXX
EGU
XXXXX
EGU
U
D
SEL
U
SEL
SEL
SEL
If Scale
Mode OFF
SEL
If Scale
Mode ON
SEL
SEL
SEL
1. When scaling the input, the value
displayed represents the actual input.
2. When the SCALE INPUT menu is
accessed, the APPLY INPUT menu
is skipped and the TRIM INPUT menu
appears.
NOTES:
U
D
U
D
U
D
Scaling the Input
Figure 8 gives an overview of the Input Scaling menu.
Scaling allows you to take your PV (Process Variable)
reading and manipulate it to a more customized dis-
play range. PV is the unit read after selecting your
input type. For example, choosing a Current input
would then produce a PV displayed in mA.
Also known as “Smart Ranging”, scaling of the SPA2
(HLPRG) allows the user to set the zero and full scale
values of the input from the intended application, with-
out having to connect the unit to any calibration equip-
ment.
Continue with the “SCALE INPUT” if you enabled
scaling in the previous menu. To proceed, follow the
steps below.
Note:
When using the front panel push buttons to enter
your scaling values, you may enter only whole
number increments. To adjust your value past the
decimal point, you must use the PC Configuration
Program.
1. At the “SCALE INPUT” display, press
SELECT
.
2. Press
SELECT
at the “INPUT ZERO”
parameter and enter the value you want
displayed when your input is at zero. Press
SELECT.
3. Press
SELECT
at the “INPUT FULL” screen.
Enter the value you wish displayed when your
input is at full scale. Press
SELECT.
If you selected “SCALE OFF” in the “CONFG
OPTNS” menu, the menu skips to Step 6. If
you selected “SCALE ON”, proceed to Step 4.
4. Next, “SCALE ZERO” is displayed. Use the
UP
and
DOWN
buttons to adjust your scaled
zero value. This is the value that will be
displayed when you are at the zero end of your
display range. Press
SELECT.
5. “SCALE FULL” appears. Press
SELECT
to
enter the menu. Enter the value you wish as
your full scaled range– the value displayed
when you are at the full end of
your range.
Press
SELECT.
6. “EXIT SCALE” appears. If all scaling
parameters have been set, press
SELECT.
The next menu selection to appear is “TRIM
INPUT”.
Figure 8. SCALE INPUT Menu

The Interface Solution Experts 17
SPA2
Programmable Current/Voltage
Limit Alarm Trips
D
D
D
U
U
APPLY
ZERO
APPLY
FULL
EXIT
APPLY
APPLY
INPUT
SEL
U
TRIM INPUT menu
SEL
XXXXX
EGU
U
D
XXXXX
EGU
U
D
SEL
SEL
SEL
SEL
Applying Input (Bench Scaling)
Figure 9 gives an overview of the Apply Input menu.
With Bench Scaling, also called “Standard Ranging”,
inputs are “captured” at their zero and full scale levels
using external, calibrated equipment.
1. At the “APPLY INPUT” screen, press
SELECT.
2. “APPLY ZERO” appears. Apply the input you
wish as your zero and press
SELECT
. Wait
until it is flashed on the display and press
SELECT
to capture.
3. Next, “APPLY FULL” is displayed. Apply the
value of your full range and press
SELECT
.
When this is flashed, press
SELECT
to
capture.
4. Press
SELECT
at “EXIT APPLY” and exit the
menu.
Input Trimming
Figure 10 gives an overview of the Input Trimming
menu.
Input trimming increases the measurement accuracy
of the parameter you are trimming by matching the
reading of its actual input to its scaling. The SPA2
offers the use of a factory-configured trimming feature
(“FCTRY TRIM“) or user-set, one-point or two-point
(“USER 1PNT” OR “USER 2PNT”) trimming.
Unit default is “FCTRY TRIM”. If another trimming
selection had been made and you wish to return to the
“FCTRY TRIM” feature, follow the instructions below.
1. Press
SELECT
at the “TRIM INPUT” SCREEN.
Once the “TRIM MODE” appears, press
SELECT
.
2. “FCTRY TRIM” is displayed, press
SELECT.
This takes you to the “EXIT TRIM” screen.
3. To exit, press
SELECT
.
To input user-specific trim values, perform the
following steps:
1. At the “TRIM INPUT” display, press
SELECT
.
When “TRIM MODE” appears, press
SELECT
again. Use the
UP
and
DOWN
buttons to reach
the user-set trimming menus. Press
SELECT
once the desired parameter is displayed–
“USER 1PNT” or “USER 2PNT”.
2. “TRIM ZERO” appears. To program, press
SELECT
. Your present zero scaling value is
shown and prompts you to “APPLY” your value.
Press
SELECT,
once your value is present and
flashing at the appropriate input terminals,
press
SELECT
again
.
If you selected “USER
1PNT” trimming, “EXIT TRIM” appears. Press
SELECT
to reach the “CONFG AOUT” menu (or
“CONFG ALARM” menu if the -AO option is not
enabled). Proceed to Step 3 for “USER 2PNT”
trimming.
3. If you selected “USER 2PNT” trimming, repeat
the instructions in Step 2 for the “TRIM FULL”
setting. Press
SELECT
when “EXIT TRIM” is
displayed to reach the “CONFG AOUT” menu
(or “CONFG ALARM” menu if the -AO option is
not enabled).
Note:
Trim only the zero and full values entered in the
“SCALE INPUT” menu through the front panel
pushbuttons. To trim values other than those
specified in the “SCALE INPUT” menu, you must
use the PC Configuration Software program.
Figure 9. APPLY INPUT Menu

18 The Interface Solution Experts
SPA2
Programmable Current/Voltage
Limit Alarm Trips
D
D
U
TRIM
MODE
EXIT
TRIM
TRIM
INPUT
SEL
U
SEL
SEL
SEL
FCTRY TRIM
USER 1 PNT
USER 2 PNT
U/D
TRIM
ZERO
XXXXX
APPLY
(ZERO)
XXXXX
EGU
TRIM
FULL
XXXXX
APPLY
FULL
XXXXX
EGU
U
D
U/D
If USER 1
or 2 PNT
If Factory Trim
CONFG AOUT menu
CONFG ALARM menu
(
If no AOUT
)
SEL SEL
U/D
U
If USER 2PNT
If USER 1PNT
D
U
D
U/D
SEL
If USER 2PNT
SEL
SEL
If USER 1PNT
SEL
Figure 10. TRIM INPUT Menu

The Interface Solution Experts 19
SPA2
Programmable Current/Voltage
Limit Alarm Trips
Configuring the Analog Output
(-AO Option)
Figure 11 gives an overview of the Analog Output
Configuration menu.
If your unit is equipped with the -AO option, use this
menu for configuration.
1. Press
SELECT
at the “CONFG AOUT” display.
This sends you to the “SEL AOUT” section.
Press
SELECT
and use the
UP
and
DOWN
buttons to toggle between current and voltage.
When the selction you desire is displayed,
press
SELECT.
2. Once you reach the “SET DAMP” field, you
may skip the damping parameter, by using the
Down
button to reach the next field. To set
damping, proceed to Step 3.
Damping– Output Damping allows you to
introduce a delay (0-30sec) into the response
of your unit in order to stop momentary input
variations from setting off alarms.
3. To set damping, press
SELECT
at the “SET
DAMP” display. Use the
UP
and
DOWN
buttons to enter a value between 0 and 30
seconds; press
SELECT.
4. Press
SELECT
at “FAIL MODE” to program
the setting. Choose “FAIL HIGH” or FAIL
LOW”. This sends you to “EXIT AOUT”.
HIGH/LOW– Choosing either of these options
will send the output to a High (23.6mA for
current; 11.0V for voltage) or Low (3.6mA for
current; -0.5V for voltage), respectively.
Figure 11. CONFG AOUT Menu
CONFG
AOUT
D
D
D
U
U
U
SEL
AOUT
SET
DAMP
FAIL
MODE
EXIT
AOUT
SEL
U
TOGGLE
VOLT/
CURRENT
SEL
SEL
D
SCALE AOUT menu
SEL
XX
SEC
(XX = 0-30)
SEL
U
D
SEL
FAIL LOW
FAIL HIGH
SEL
U/D
SEL

20 The Interface Solution Experts
SPA2
Programmable Current/Voltage
Limit Alarm Trips
Scaling the Analog Output
(-AO Option)
Figure 12 gives an overview of the Analog Output
Scaling menu.
Follow these instructions to scale the analog output
after you have performed the configuration.
Note:
When using the front panel pushbuttons to enter
your scaling values, you may enter only values to
one decimal place (tenths). To adjust your value
past one decimal place, you must use the PC
Configuration Program.
1. At the “SCALE AOUT” display, press
SELECT
.
2. Press
SELECT
at the “AOUT ZERO”
parameter and enter the value you want to
output when your input is at zero. Press
SELECT.
3. Press
SELECT
at the “AOUT FULL” screen.
Enter the value you want to output when your
input is at full scale. Press
SELECT.
4. “EXIT SCALE” appears. If all scaling
parameters have been set, press
SELECT.
Figure 12. SCALE AOUT Menu
SCALE
AOUT
D
D
D
U
U
AOUT
ZERO
AOUT
FULL
EXIT
SCALE
SEL
U
SEL
SEL
TRIM AOUT menu
XXXXX
MA/VOLT
U
D
SEL
XXXXX
MA/VOLT
U
D
SEL
SEL
1. When setting zero and full values,
the values displayed are the analog output.
Zero and full in mA or Volts (depending upon
the output configuration).
2. Update your analog output during -AO scaling.
3. Rearranging values nulls your trim value.
4. Implement "auto increment" when incrementing
and decrementing zero and full counts.
NOTES:
Other manuals for SPA2 TPRG
1
This manual suits for next models
1
Table of contents
Other Moore Industries Security System manuals

Moore Industries
Moore Industries CPA User manual

Moore Industries
Moore Industries DCA S User manual

Moore Industries
Moore Industries SPA TPRG User manual

Moore Industries
Moore Industries SPA HLPRG User manual

Moore Industries
Moore Industries SPA User manual

Moore Industries
Moore Industries STA HLPRG User manual

Moore Industries
Moore Industries DDA Series User manual