MSA CH-105 User manual

Limited Liability Company
«NPK MORSVYAZAVTOMATICA»
AUTOMATIC BATTERY CHARGERS
CH-105, CH-105-24
Operating manual


Operating Manual
2
Table of contents
1DESCRIPTION AND OPERATION OF THE PRODUCT...............................................4
1.1 Description............................................................................................................................4
1.2 Main technical specifications................................................................................................4
1.3 Structure and operation of the Product..................................................................................6
1.4 Measurement instruments, tools and appliances.................................................................12
1.5 Marking and sealing............................................................................................................12
1.6 Packaging............................................................................................................................12
2INTENDED USE OF THE PRODUCT..............................................................................13
2.1 Operational constraints........................................................................................................13
2.2 Usage preparations..............................................................................................................13
2.3 Usage of the product ...........................................................................................................14
3TECHNICAL SERVICE OF THE PRODUCT.................................................................21
4CURRENT REPAIR OF THE PRODUCT........................................................................24
5STORAGE.............................................................................................................................26
6TRANSPORTATION...........................................................................................................27
7DISPOSAL.............................................................................................................................28
APPENDIX А(MANDATORY) OUTLINE AND INSTALLATION DIMENSIONS.........29
APPENDIX B (MANDATORY) DESCRIPTION AND PURPOSE OF PERIPHERAL
UNITS ....................................................................................................................................30

Automatic battery chargers
CH-105, CH-105-24
3
INTRODUCTION
This operating manual (hereinafter referred to as OM) is intended to describe the
structure, operating principles, technical specifications and service of Automatic battery
chargers CH-105 and CH-105-24 types (hereinafter referred to as –the Product, the
CH).
In addition to the instructions given in this document, the safety regulations and
rules applicable in the field shall be observed.
Only those who have read and understood this document and those who have
had special training shall be permitted to operate with the Product according to the ap-
plicable regulations.
Terms and abbreviations:
OM –operating manual;
SB –storage battery;
SC –short circuit;
TS –technical service;
CL –check list;
LCD –liquid-crystal display;
LFSG –large fine-pored silica gel granular;
AU-106 –remote alarm unit AU-106;
AU-206 –remote alarm unit AU-206;
DTS-135 –temperature sensor DTS-135;
BPC-136 –accumulator batteries control panel BPC-136 (BPC-136-01).

Operating Manual
4
1DESCRIPTION AND OPERATION OF THE PRODUCT
1.1 DESCRIPTION
The Product operates with AC single-phase mains 50 (60) Hz, volt-
age 110; 220 V or 24 V DC and automatically charges SBs of shipborne equipment,
communication systems and other industrial and transportation equipment.
1.2 MAIN TECHNICAL SPECIFICATIONS
1.2.1 The Product ensures:
a) SB charge;
b) Display of present current and voltage values both on local control panel and
on BPC-136;
c) Integrated alarms:
‒Main power failure;
‒SB reverse polarity connection;
‒Switching on the Product with disconnected SB (or SB circuit breakdown);
‒Overload or SC in SB circuit;
‒Excess of set limits for charge current or voltage;
d) Integrated protection against:
‒Reverse polarity power connection;
‒Overload or SC in load circuit;
‒Overcurrent in SB circuit (overload or SC);
e) The Product additionally provides:
‒SB deep discharge protection (function may be disabled);
‒SB overheating protection if DTS-135 is used;
f) Remote alarm signaling in case of input power failure if AU-106 (AU-206)
or BPC-136 are used.
Note –Peripheral equipment (BPC-136, DTS-135, AU-106 (AU-206)) is speci-
fied in the scope of supply.
1.2.2 Technical specifications of the Product are represented in Table 1.

Automatic battery chargers
CH-105, CH-105-24
5
Table 1 –General technical specifications of the Product’s types
Parameter
Value
CH-105
CH-105-24
Input voltage, V
AC, frequency 50 (60) Hz
110 (99…121)1);
220 (198…242) 1)
–
DC
–
24 (19...36)1)
Power consumption, W
690
Max. output power, W
600
500
Charge voltage DC, V
9…30
Charge current, А
0.2…20.0
0.2…16.0
Rated capacity of recharged batteries, А·h
Max. 200
Max.160
Max. charge time of SB, h
10
Measurement
error
current, А
±0.2, max.
voltage, V
±0.1, max.
Accuracy of
adjustment
current, А
0.1
voltage, V
0.1
Alarm signaling
Built-in: relay contacts, sound signaling, light signal-
ing;
External (connected) devices: AU-106 or AU-206,
BPC-136
Protection degree
IP22
Weight, kg
7
Operating temperature, °С
–15…+55
Limiting temperature, °С
–60…+70
Mounting
wall
1) Supply voltage range is given in parenthesis.

Automatic battery chargers
CH-105, CH-105-24
7
For more information on the Product functional elements, controls, LCDs and
LEDs, see Table 2.
Table 2 –Functional elements, controls, LCDs and LEDs
№
Element
Type, size, identi-
fier
Description
1
LCD
«Voltage, V»
Displays current charge (discharge) voltage and
menu items: «U», «I», «t», «Pdd»; for more infor-
mation see 2.3.5
«Current, А»
Displays present charge (discharge) current, defined
values of current or charge, SB temperature and
deep discharge protection status «OFF» or «ON»;
for more information see 2.3.5
2
Operation mode
LEDs
«Power»
Glowing if power is available
«Normal»
Glowing during final stage of SB charge, i.e. when
charger is in voltage stabilization stage (the SB is
approaching values defined by user)
«Charging»
Glowing during main stage of SB charge, i.e. when
charger is in current stabilization stage
«Failure»
Glowing in case of SB discharge or the Product mal-
function or no input voltage
3
Controls
«SELECT»
Menu select button
Navigation buttons to set values of relevant menu
item
«SET
MUTE»
Switches on (off) alarm mute function. Button to
confirm (save) selected value and mute sound signal
while light alarm signaling is still working
4
Piano type switch
(on/off) with back-
light
–
Switches on (off) the charger
5
Stud
М5х15
Main grounding element of the Product
6
Cable gland
MG-16
Connect the Product to power mains and peripheral
equipment: DTS-135, BPC-136, AU-106 (AU-206)
7
Cable gland
MG-25
8
Cable gland
MG-32
9
Cable gland
MG-20
Note –Numbers are shown in Figures 1 and 2.
The Product includes visual, sound and relay alarm of abnormal situation, see
Table 3.

Operating Manual
8
Table 3 –Alarm conditions
Alarm condition
Alarm
Red LED
Built-in
buzzer
Relay alarm
The Product input power failure
+
+
Switching on the Product with disconnected SB
or SB rupture (switching on and off every
5 minutes)
+
+
SB reverse polarity connection
+
+
Current overload or SB short circuit
+
+
Overvoltage in SB circuit
(time of alarm operation until next check; check
every 5 sec)
+
+
Charge current exceeds set limits
+
+
Reverse polarity power connection
(only for CH-105-24)
+
+
Note –«+» light or sound signaling.
1.3.2 Connection of peripheral devices
1.3.2.1 DTS-135 is installed on rechargeable SB and controls its current tem-
perature. Use DTS-135 only with gel batteries in order to prevent them from «thermal
runaway» in case of their buffer connection. DTS-135 is connected to «TS» terminal,
see Figure 3.
1.3.2.2 AU-106 (AU-206) ensures visual and sound signaling in alarm mode.
AU-106 (AU-206) is used when charger is placed beyond line of sight, where the vessel
is typically controlled from; the units also ensure alarm in case of charger input power
failure.
AU-106 (AU-206) is connected to group of terminals «AU-106», see Figure 3.
Opening (closing) of special charger relay contacts ensures alarm switching on/off:
when alarm is switched on –«Alarm» contacts open, when alarm is switched off –
close.
1.3.2.3 BPC-136 ensures remote control of the Product, present charge or dis-
charge current and voltage, visual and sound signaling in case of transition to alarm
mode.

Automatic battery chargers
CH-105, CH-105-24
9
BPC-136 is connected via standard RS-422 interface; it is connected to «Re-
mote/Bat_control» charger terminal, see Figure 3.
Forced connection of SB to load circuit is carried out by closing contacts of
«Forced start key» terminal, see Figure 3.
Use «Forced start key» together with the Product operation mode №1, see 2.3.1,
and switched connection type, see Figure 5.
Note –If forced SB connection was activated, SB deep discharge protection is
switched off (not depending on the selected operation mode).

Operating Manual
10
Figure 3 –The Product’s connection diagram
1.3.2.4 Load may have direct and switched connection to SB, see Figures 4–5,
respectively.
Direct type of connection is used for loads with consumption current more than
30 А, i.e., power exceeds maximum permissible for the Product.
Switched connection is used for loads with max. consumption current 30 А.
Switched type of connection allows for using SB deep discharge protection
function, see. 2.3.7. Enable (disable) this function in the Product menu, see 2.3.2.
Selected type of connection (direct or switched), as well as switching of connec-
tion type may lead to the limited use of some functions or change the Product’s opera-
tion.
Note –Voltage of the Product «Output 12/24 VDC» terminal, see Figures 3–6,
is directly connected to voltage of SB connected to Product «BATTERY» terminal, see
Figures 3–6; thus, if SB with voltage 12 V is connected to charger, voltage of «Out-
put 12/24 VDC» terminal is 12 V; if SB with voltage 24 V is connected to charger,
voltage of «Output 12/24 VDC» terminal is 24 V.
Figure 4 –Diagram of load to SB direct connection

Automatic battery chargers
CH-105, CH-105-24
11
Figure 5 –Diagram of load to SB switched connection
Do not use the Product with connected SB to power the load (i.e., in buffer
mode), because the load connected to SB circuit may be limited in power output by the
Product (e.g., in case of SC in SB circuit or in case of high drop in charge voltage in
case of deeply discharged SB connection). To provide reliable power supply, power the
load from separate PSU (see Figure 6).
Figure 6 –Load connection using separate PSU

Operating Manual
12
1.4 MEASUREMENT INSTRUMENTS,TOOLS AND APPLIANCES
Consumables required for the TS are represented in Table 4.
Table 4 –Consumables required for the TS
Name and identifier
of consumables
Amount of
consumables
Note
Cleaning cloth
0.10 kg
To clean contamination from the surfaces
Rectified hydrolytic
technical ethyl alcohol
0.01 l
1 To remove severe contamination
2 To clean the Products surface in case of coating damage
Varnish
0.05 kg
To cover surfaces of the Product in case of paint coating dam-
age
Abrasive cloth
0.06 х 0.06 m
To polish surfaces of the Product in case of paint coating dam-
age
1.5 MARKING AND SEALING
The Product has a nameplate indicating name, serial number, date of manufac-
turing, weight, protection degree, input voltage, charge voltage, charge current and max.
output power.
The sealing of the Product is not provided.
1.6 PACKAGING
At the time of delivery the Product is packed in a corrugated board box and in-
ner packaging (air bubble film) ensuring its transportation and storage at the warehouse.
Transport packaging is also used as a returnable packaging for transportation of
the Product to the repair location and back.
The sealing of transport packaging is not provided.

Automatic battery chargers
CH-105, CH-105-24
13
2INTENDED USE OF THE PRODUCT
2.1 OPERATIONAL CONSTRAINTS
Select an installation place in compliance with operational constraints (operating
temperature and protection degree).
It is prohibited to stretch cables connected to Product!
Caution! Distance between the installation site and magnetic compass shall
not be less than 1 m!
2.2 USAGE PREPARATIONS
2.2.1 Safety features
While preparing the Product for operation, check it visually after unpacking;
mechanical damage shall be absent.
Connection to power mains shall be provided only in compliance with input
power requirements.
Before connecting the Product shall be switched off and have a proper grounding.
While using the Product the staff shall follow “The technical rules for operation
of electric installation” and “Safety rules for operation of electric installation” while
testing electrical circuits and insulation resistance.
2.2.2 Visual check procedure
Before switching the Product on:
–observe visually integrity and initial position of the controls on the front pan-
els;
–check the absence of dust and dirt on the Product casing; clean with a soft
cloth if necessary;
–check that cable connectors are securely connected to the Product, and it has a
reliable grounding.
2.2.3 Switching on instructions
While connecting the Product and preparing it for operation follow the steps be-
low:
‒transfer circuit breakers of main power switchboard to «ON» position»;

Operating Manual
14
‒transfer a piano type switch on the Product’s casing to «ON»position.
To switch The Product off:
‒transfer a piano type switch on the Product’s casing to «Off»position;
‒transfer circuit breakers of main power switchboard to «Off»position.
2.3 USAGE OF THE PRODUCT
2.3.1 The Product operation modes
Set operation modes in the Product menu «Pdd»using «Forced Start Key»ter-
minal depending on the selected load connection type, see Figures 4–5.
Table 5 –The Product operation modes
Operation
modes
Menu settings
Status of «Forced Start Key»terminal
contacts
№1
«Pdd»value «OFF»*
opened
№2
«Pdd»value «OFF»*
closed by jumper
№3
«Pdd»value «ON»*
opened
Note –«*»means enabling (disabling) deep discharge protection function.
Operation mode №1 –in case of power failure the Product disconnects SB cir-
cuit (load from SB, external signaling units AU-106 (AU-206) and BPC-136, and then
disconnects itself). As the Product shuts off completely integrated alarm is not activat-
ed.
Note –connect AU-106 (AU-206) power directly to SB or separate PSU (if
AU-106 (AU-206) are used together with the Product in this mode).
Operation mode №2 –in case of power failure the Product is still connected to
SB, power, loads and external signaling units AUС-106 (AUС-206) and BPC-136 are
switched to SB power supply. SB deep discharge protection is not active in this mode.
Operation mode №3 –in case of power failure the Product is still connected to
SB, power, loads and external signaling units AUС-106 (AUС-206) and BPC-136 are
switched to SB power supply. SB deep discharge protection is active in this mode.
The Product is delivered from the Manufacturer’s plant with set operation mode
№ 3.
For more information on operation modes at direct and switched connection
types, see Table 6.

Automatic battery chargers
CH-105, CH-105-24
15
Table 6 –Description of the Product operation depending on the selected operation
mode and connection diagram
Connection
type
Opera-
tion
mode №
The Product status in case of power mains fail-
ure
Deep discharge
protection
Direct
1
1 The Product is disconnected from SB circuit;
2 SB charge is not controlled; display of current
voltage is not available;
3 SB is discharged by load (uncontrolled);
4 Integrated alarm is not active
Not active
2
1 The Product is powered from SB;
2 SB discharge is not controlled; display of current
voltage is available;
3 SB is discharged by load (uncontrolled);
4 Integrated alarm is active
Not active
3
1 The Product is powered from SB;
2 SB discharge is not controlled; display of current
voltage is available;
3 Integrated alarm is active
Not active
Switched
1
1 The Product is disconnected from SB circuit;
2 SB is disconnected from load;
3 Integrated alarm is not active
Not active
2
1 The Product is powered from SB;
2 SB discharge is controlled; display of present
voltage and current is available;
3 Integrated alarm is active
Not active
3
1 The Product is powered from SB;
2 SB discharge is controlled; display of present
voltage and current is available;
3 Integrated alarm is active
Active
Recommendations on operation modes:
use operation mode №1 in case of direct connection. Use operation
mode №2 to observe current voltage on SB and ensure active alarm of power supply
failure;
use operation mode №3 in case of switched connection. Use operation mode
№1 to save SB capacity and use manual load connection to SB.

Operating Manual
16
2.3.2 Menu structure
Menu of automatic chargers CH-105 and CH-105-24 has the following struc-
ture, see Figure 7 and Table 7.
Figure 7 –the Product’s menu structure
Table 7 –Description of the Product’s menu items
Menu item
Description
Charge current «I»
To select SB charge current value within the range:
‒0.2…20.0 А for CH-105;
‒0.2…16.0 А for CH-105-24
Charge voltage
«U»
To select SB charge voltage value within the range 9…30 V
Operation mode
«Pdd»
To activate SB deep discharge protection:
‒To switch on - «ON»;
‒To switch off - «OFF»
2.3.3 Protection
The Product ensures the following protection:
a) Inductive-capacitive filters (built-in) ensure protection against transient pro-
cesses in power circuit. The filters suppress interference in power circuit ensuring unin-
terruptible operation;
b)Electronic lock of power output ensures protection against current overload
and SC in SB circuit. Once SC or overload occurs, the Product registers the rise of out-
put current and cuts off the power from power output, activating alarm signaling (sound

Automatic battery chargers
CH-105, CH-105-24
17
signal switches on; LED is glowing red; relay contacts open). Power output is switched
off until the reason of overload or SC is removed; once it is done, the lock is automati-
cally released; the Product starts operation and SB is charged in standard mode;
c) Product’s electromechanical switch off from SB ensures protection against
SB reverse polarity connection with alarm signaling (sound signal activates; LED «Er-
ror»is glowing red; relay contacts open). After connection with relevant polarity the
Product automatically connects to SB and continues charging in standard mode;
d)The Product software protects SB against overheating by choosing a charging
mode. To activate this protection, use DTS-135 fastened directly on the SB side.
DTS-135 transmits current SB temperature via communication cable. Once the tempera-
ture increases, the Product automatically decreases charge voltage and current to pre-
vent SB from heating. Alarm is not activated, because charge parameters are changed in
dynamic mode;
e) Order of power phase connection is not essential; the Product will operate
without malfunctions at any order. This type of protection is not supported by alarm and
applied only to CH-105 type.
2.3.4 AU-106 (AU-206) or BPC-136 connection
To ensure alarm signaling, use AU-106 (AU-206) or BPC-136; the units provide
sound and visual signaling of no input power or transition to emergency operation
mode.
Alarm activation of AU-106 (AU-206) is based on dry contacts closing (open-
ing), see 1.3.2.
BPC-136 receives alarm signal from the Product in digital form via RS-422
channel, see 1.3.2.
AU-106 (AU-206) and BPC-136 are powered from rechargeable SB, or, if nec-
essary, from other independent power sources.
2.3.5 The Product’s settings
2.3.5.1 To set charge current, use built-in keyboard and provide the following
steps:
Press and hold «SELECT» button on the casing until character «I» appears on
the left LCD. The right LCD displays the charge current which was set before;
using ▲ and ▼set the charge current value;

Operating Manual
18
press «SET. MUTE» to confirm the choice and record it in the non-volatile
memory.
2.3.5.2 To set charge voltage, use built-in keyboard and provide the following
steps:
Press and hold «SELECT» button on the casing until character «U» appears
on the left LCD. The right LCD displays the charge voltage which was set before;
using ▲ and ▼set the charge voltage value;
press «SET. MUTE» to confirm the choice and record it in the non-volatile
memory.
2.3.5.3 To switch on / off SB deep discharge protection function, use built-in
keyboard and provide the following steps:
press and hold «SELECT»on the casing until the left LCD displays charac-
ters «Pdd». The right LCD displays current function status «OFF» or «ON»;
using ▲ and ▼set status «ON»–or «OFF»;
press «SET. MUTE» to confirm the set status and record it in the non-volatile
memory.
CAUTION! Observe 2.3.1 before switching on SB deep discharge protection.
2.3.6 Display of current SB temperature
The Product may display temperature of rechargeable SB. SB heating is con-
trolled by DTS-135 which is fastened directly on SB.
To activate this function:
In standard operation mode press ▼, the left LCD displays character «t», the
right one –current SB temperature (if DTS-135 is not used, the right LCD
shows «– ––»);
in 10 sec the Product will transfer to main operation mode and LCDs will
display present charge voltage and current strength (press ▼again during displaying
data on SB temperature and the Product will return to standard operation mode).
Note –This function is available if DTS-135 is included in the scope of supply.
2.3.7 SB deep discharge protection
Function of deep discharge protection allows for the most efficient use of SB
capacitive characteristics and prolongs its lifetime. To activate the function, select menu

Automatic battery chargers
CH-105, CH-105-24
19
item «Pdd» and set «ON»status. If «OFF» status is selected, the function is switched
off.
SB deep discharge protection may be used only if load switched connection is
used, see Figure 5.
If direct connection is used, see Figure 4, protection function shall be switched
off.
SB deep discharge protection activates at residual voltage 19.2 V –for SB 24 V
and 9.6 V –for SB 12 V.
2.3.8 Energy saving mode
Energy saving mode enables to prolong time of load powering from SB. Digital
LCDs (to display present values of charge current and voltage) are switched off in this
mode.
Energy saving mode is activated automatically in case of power mains failure.
To activate LCDs, press «SELECT»button on the casing; they will start dis-
playing within 3 sec.
In case of main power recovery energy saving mode is switched off.
2.3.9 Recommendations on charge current values
To recharge SB, set the current values in compliance with the Manufacturer’s
recommendations (factory parameters) given in SB certificate.
If, for any reason, it is impossible, the Manufacturer recommends to set charge
current values not more than 10 % from SB capacity.
Sample calculation:
At SB capacity (С) –150 А·h, charge current equals С150 * 0.1 = 15 А.
Note –This current value prevents SB from damage in case of overcurrent.
2.3.10 Recommendations on charge voltage values
SB charge voltage shall be set in compliance with SB documentation (factory
charge voltage parameters).
If, for any reason, it is impossible, the Manufacturer recommends to set charge
voltage values 28.4 V for SB with voltage 24.0 V, and 14.2 V for SB with volt-
This manual suits for next models