MTE dV E Series Product manual

dV E-Series
208V – 600V
TECHNICAL REFERENCE MANUAL
WARNING
High Voltage! Only a qualified electrician can carry out the electrical
installation of this filter.
Quick Reference
❶Performance Data Pages 9 – 12
❷Selection Guide Pages 13 – 18
❸Installation Guide Pages 19 – 24
❹Start-up/Troubleshooting Pages 25 – 27

This page intentionally left blank

dV E-Series Technical Reference Manual 208V – 600V
III Form: DVT-TRM-E December 2021 Rev. 001
TABLE OF CONTENTS
1. SAFETY..................................................................................................................................5
WARNINGS AND CAUTIONS ........................................................................................................5
PRODUCT SAFETY LABELING .....................................................................................................5
GENERAL SAFETY INSTRUCTIONS ..............................................................................................6
2. GENERAL INFORMATION ....................................................................................................7
RECEIPT &REPAIR STATEMENT.................................................................................................7
ENCLOSURES ...........................................................................................................................8
AGENCY APPROVALS ................................................................................................................8
WARRANTY ..............................................................................................................................8
3. DV E-SERIES PERFORMANCE DATA..................................................................................9
PERFORMANCE SPECIFICATIONS ...............................................................................................9
FILTER EFFICIENCY +WATT LOSS............................................................................................10
PERFORMANCE CHART ...........................................................................................................11
ALTITUDE DERATING ...............................................................................................................12
MOTOR FREQUENCY DERATING...............................................................................................12
4. HOW TO SELECT ................................................................................................................13
SELECTION GUIDE ..................................................................................................................13
UNDERSTANDING THE DVE-SERIES PART NUMBER: .................................................................14
PART NUMBER SELECTION TABLES..........................................................................................15
PART NUMBER SELECTION TABLES..........................................................................................16
5. HOW TO INSTALL ...............................................................................................................19
INSTALLATION CHECKLIST .......................................................................................................19
G
ROUNDING
..........................................................................................................................20
POWER WIRING CONNECTION .................................................................................................20
BASIC SCHEMATIC DIAGRAM ...................................................................................................21
INTERCONNECTION DIAGRAM –KIT ..........................................................................................22
INTERCONNECTION DIAGRAM –OPEN PANEL AND ENCLOSED....................................................23
TORQUE RATINGS...................................................................................................................24
6. START-UP............................................................................................................................25
S
AFETY
P
RECAUTIONS
..........................................................................................................25
7. TROUBLESHOOTING..........................................................................................................26

dV E-Series Technical Reference Manual 208V – 600V
Form: DVT-TRM-E December 2021 Rev. 001IV
List of Figures
Figure 3-1: Typical Performance Chart .....................................................................................11
Figure 3-2: Altitude Derating Curve...........................................................................................12
Figure 3-3: Current Derating for Drive Output Frequency..........................................................12
Figure 5-1: Basic Schematic Diagram .......................................................................................21
Figure 5-2: Kit Diagram .............................................................................................................22
Figure 5-3: Open Panel and Enclosed Diagram ........................................................................23
List of Tables
Table 3-1: Performance Specifications....................................................................................... 9
Table 3-2: Filter Efficiency & Watt Loss.....................................................................................10
Table 4-1: Kit Selection Table ...................................................................................................15
Table 4-2: Open Panel Selection Table.....................................................................................16
Table 4-3: Enclosed NEMA 1/2 Selection Table........................................................................17
Table 4-4: Enclosed NEMA 3R Selection Table ........................................................................18
Table 5-1: Torque Ratings ........................................................................................................24
Table 7-1: Troubleshooting Guide.............................................................................................27

dV E-Series Technical Reference Manual 208V – 600V
5 Form: DVT-TRM-E December 2021 Rev. 001
1. SAFETY
Warnings and Cautions
The following symbols are used in this manual:
Product Safety Labeling
The following labels are placed on the dV E-Series product:
WARNING
High Voltage Warning: warns of situations that dangerously
high voltage is involved. Failure to use proper precautions
may lead to serious injury or death.
WARNING
General Warning: warns of situations that can result in
serious injury or death if proper precautions are not used.
Caution
General Caution: identifies situations that could lead to
malfunction or possible equipment damage.
Label notes to installer to refer to instruction manual first before
installing.
High Voltage: surfaces on product can have high voltage which can
cause injury.
Hot Surfaces: surfaces of product can be hot at times and cause
burns.

dV E-Series Technical Reference Manual 208V – 600V
Form: DVT-TRM-E December 2021 Rev. 0016
General Safety Instructions
WARNING
High Voltage! Only a qualified electrician can carry out the electrical
installation of this filter.
High voltage is used in the operation of this filter. Use Extreme caution to
avoid contact with high voltage when operating, installing or repairing
this filter.
Injury or death may result if safety precautions are not
observed.
WARNING
The opening of the branch circuit protective device may be an indication
that a fault current has been interrupted. To reduce the risk of fire or
electrical shock, current-carrying parts and other components of the filter
should be examined and replaced if damaged.
An upstream disconnect/protection device must be used as required by
the National Electrical Code (NEC) or governing authority.
Even if the upstream disconnect/protection device is open, the drive
down stream of the filter may feedback high voltage to the filter. The
drive safety instructions must be followed. Injury or death may result if
safety precautions are not observed.
The filter must be grounded with a grounding conductor connected to all
grounding terminals. Modular filters must have reactor grounded
through a 2”x2” area cleaned of paint and varnish on lower mounting
bracket.
Only spare parts obtained from MTE Corporation, or an authorized MTE
distributor can be used.
Caution
Loose or improperly secured connections may damage or degrade filter
performance. Visually inspect and secure all electrical connections
before power is applied to the filter.
Wiring should not be routed underneath panel in resistor housing. Doing
so could result in fire or damage to the product.
Product should not be mounted on wood or any other combustible
surface. Doing so could lead to fire or damage to the product.

dV E-Series Technical Reference Manual 208V – 600V
7 Form: DVT-TRM-E December 2021 Rev. 001
2. GENERAL INFORMATION
The purpose of the manual is to properly specify size, install, interconnect, and operate the dV
E-Series motor protection filter.
For most current information, please refer to website
https://www.mtecorp.com/products/dv-e-series/
This manual is intended for use by personnel experienced in the operation and maintenance of
inverters. Because of the high voltages required by the filter, inverter, and the potential dangers
presented by rotating machinery, it is essential that all personnel involved in the operation and
maintenance of this filter know and practice the necessary safety precautions for this type of
equipment. Personnel should read and understand the instructions contained in this manual
before installing, operating, or servicing the filter and inverter to which it is connected.
Receipt & Repair Statement
Upon Receipt of this Filter:
The dV E-Series motor protection filter has been subjected to demanding factory tests before
shipment. Carefully inspect the shipping container for damage that may have occurred in transit.
Then unpack the filter and carefully inspect for any signs of damage. Save the shipping
container for future transport of the filter.
In the event of damage, please contact and file a claim with the freight carrier involved
immediately.
If the equipment is not going to be put into service upon receipt, cover and store the filter in a
clean, dry location. After storage, ensure that the equipment is dry and that no condensation or
dirt has accumulated on the internal components of the filter before applying power.
Repair/Exchange Procedure:
MTE Corporation requires a Return Material Authorization Number and form before we can
accept any filters that qualify for return or repair. If problems or questions arise during
installation, setup, or operation of the filter, please contact MTE for assistance at:
Toll Free: 1-800-455-4MTE (1-800-455-4683)
International Tel: (+1) 262-253-8200
Fax: 262-253-8222

dV E-Series Technical Reference Manual 208V – 600V
Form: DVT-TRM-E December 2021 Rev. 0018
Enclosures
MTE enclosures are designed to provide a degree of protection for electrical components and
prevent incidental personnel contact with the enclosed equipment. Depending on the enclosure
selected, these enclosures meet the requirements of NEMA 1/2 or 3R.
An approximate cross reference guide between NEMA, UL, CSA and IEC enclosure follows:
Type 1 NEMA / IEC IP20 Enclosure:
Are designed for indoor use and will provide protection against contact with the enclosed
equipment.
Type 2 NEMA / IEC IP20 Enclosure:
Are designed for indoor use and will provide protection against contact with the enclosed
equipment and provide a degree of protection against limited amounts of falling water
and dirt.
Type 3R NEMA / IEC IP23 Enclosure:
Are designed for outdoor use primarily to provide protection against contact with the
enclosed equipment and provide a degree of protection against falling rain sleet and
external ice formation.
Agency Approvals
UL and cUL listed to UL508 Type MX and CSA-C22.2 No 14-95
File E180243
CE Marked
Warranty
Three years from the date of shipment. See http://www.mtecorp.com/industry-leading-warranty/
for details.

dV E-Series Technical Reference Manual 208V – 600V
9 Form: DVT-TRM-E December 2021 Rev. 001
3. dV E-SERIES PERFORMANCE DATA
Performance Specifications
Table 3-1: Performance Specifications
Service Load Condition Invertor Duty Three Phase Motors
Voltage 208 – 600 VAC +/- 10%, 60Hz
Input Voltage Wave Form Pulse Width Modulation (PWM)
Inverter Switching Frequency 2kHz – 4kHz (3A – 750A)
Inverter Operating Frequency 0 – 60 Hz without derating
Maximum Ambient
Temperature
-40C to +60C Modular Filter
-40C to +50C Enclosed Filter
-40C to +90C Storage
Insulation System Class N (200° C)
Insertion Loss (Voltage) 1.7% at 60 Hz
Efficiency >99%
Current range 3A – 750A
Available form factors Kit, Open Panel, NEMA 1/2, NEMA 3R
Altitude without derating 6,600 feet above sea level
Maximum Motor Lead Length 1,000 feet (VFD rated cable recommended)
Relative Humidity 0% to 99% non-condensing
Current Rating
100% RMS Continuous
150% for 1 minute
200% for 10 sec
*Operating in overload will result in increased proportional
voltage drop
Audible Noise <65db at 1 meter
Rise Time Greater than 0.1 uS
Peak Voltage @ Motor 150% of DC bus voltage up to 1,000 feet

dV E-Series Technical Reference Manual 208V – 600V
Form: DVT-TRM-E December 2021 Rev. 00110
Filter Efficiency + Watt loss
Table 3-2: Filter Efficiency & Watt Loss
Maximum
Output Amps
RMS/Filter Current
Rating Amps RMS
Efficiency
(%)
Typical Power
Dissipation
(Watts*)
3
99.0%
51
4
99.0%
54
7
99.0%
64
9
99.0%
70
12
99.0%
86
17
99.0%
111
22
99.0%
97
27
99.0%
95
35
99.0%
91
45
99.0%
76
55
99.0%
102
65
99.0%
152
80
99.0%
122
110
99.0%
92
130
99.0%
113
160
99.0%
148
200
99.0%
175
250
99.0%
207
305
99.0%
205
365
99.0%
239
415
99.0%
330
515
99.0%
381
600
99.0%
350
750
99.0%
411
*Based on a typical 480V, 60Hz output frequency, 1,000 feet of drive cable, 2kHz carrier
frequency at full load application.

dV E-Series Technical Reference Manual 208V – 600V
11 Form: DVT-TRM-E December 2021 Rev. 001
Performance Chart
Figure 3-1: Typical Performance Chart

dV E-Series Technical Reference Manual 208V – 600V
Form: DVT-TRM-E December 2021 Rev. 00112
Altitude Derating
Figure 3-2: Altitude Derating Curve
Motor Frequency Derating
Figure 3-3: Current Derating for Drive Output Frequency

dV E-Series Technical Reference Manual 208V – 600V
13 Form: DVT-TRM-E December 2021 Rev. 001
4. HOW TO SELECT
Selection Guide
The dV E-Series motor protection filter is intended for use on inverter duty motors. It will
typically be used with lead lengths up to 1,000 feet. The dV E-Series motor protection filter
eliminates reflective wave, provides peak voltage protection, and rise time reduction.
The suitability of this filter for a specific application must therefore be determined by the
customer. In no event, will MTE Corporation assume responsibility or liability for any direct or
consequential damages resulting from the use or application of this filter. Nor will MTE
Corporation assume patent liability with respect to the use of information, circuits or equipment
described in this instruction manual.
NOTE: For non-inverter duty motors, please refer to MTE’s SineWave Guardian filter.
The dV E-Series motor protection filters are available in Kit, Open Panel, NEMA 1/2, and 3R
mechanical configurations.
Please verify information below for proper selection:
Lead Length: This product is suitable for applications with motor leads up to 1,000 ft.
Contact MTE Application Engineering for possible longer applications.
Voltage: Input voltage from 208V – 600V. See Table 3-1: Performance Specifications
(p9) for specification.
*Current Rating: Support for 3 Amps – 750 Amps.
Switching Frequency: Support for carrier frequency of 2kHz – 4kHz.See Table 3-1:
Performance Specifications (p9).
Drive Output Frequency: Support for 0Hz to 60Hz without derating. See
Figure 3-3: Current Derating for Drive Output Frequency (p12) for derating curve.
Temperature: Maximum ambient temperature, 60C (open), 50C (enclosed). See
Table 3-1: Performance Specifications (p9) for specification.
Altitude: 3,300 feet above sea level without derating. See Figure 3-2: Altitude Derating
Curve (p12) for derating curve.
Enclosure Type: NEMA 1/2 & NEMA 3R – see Enclosures (p8) for enclosure
descriptions.
Motor Insulation Class: Verify motor meets inverter duty standards per NEMA MG1
Section 31.
* NOTE: dV E-Series filters can be paralleled for higher current ratings. Contact MTE
Application Engineering for more information.

dV E-Series Technical Reference Manual 208V – 600V
Form: DVT-TRM-E December 2021 Rev. 00114
Understanding the dV E-Series Part Number:
DVTX_ _ _ _ E
dV E-Series Filter
Type
K = Kit
P = Open Panel
G = General Purpose (NEMA 1/2)
W = Weather (NEMA 3R)
Current Rating
(i.e., 0003 is 3 Amps, 0045 is 45 Amps, 0600 is 600 Amps)
Voltage Rating
(208V – 600V)

dV E-Series Technical Reference Manual 208V – 600V
15 Form: DVT-TRM-E December 2021 Rev. 001
Part Number Selection Tables
Table 4-1: Kit Selection Table
* Kits are supplied with Reactor and Resistor only. They are not preassembled or prewired.
208V
Motor
HP
240V
Motor
HP
380V
Motor
KW
480V
Motor
HP
550V-
600V
Motor
HP
Filter
Amp
Rating
Part
Number
App.
Wt.
(lbs.)
Reactor
Dimensions
(in.)
(H x W x D)
Resistor
Dimensions
(in.)
(H x W x D)
0.5 .75 0.5- 1.1 0.5-1.5 0.5 - 2 3 DVTK0003E 3 3.7 x 4.5 x 1.5 5.0 x 8.1 x 0.75
0.75 1 1.5 2 3 4 DVTK0004E 3 3.7 x 4.5 x 1.5 5.0 x 8.1 x 0.75
1.5 2 2.2 - 3 3 5 7 DVTK0007E 3 3.7 x 4.5 x 1.5 5.0 x 8.1 x 0.75
2 3 4 5 7.5 9 DVTK0009E 3 3.7 x 4.5 x 1.5 5.0 x 8.1 x 0.75
3 4 5.5 7.5 10 12 DVTK0012E 3 3.7 x 4.5 x 1.5 5.0 x 8.1 x 0.75
5 5.5 7.5 10 15 17 DVTK0017E4 4.0 x 4.2 x 4.0 5.0 x 8.1 x 0.75
5.5 7.5 11 15 20 22 DVTK0022E 4 4.0 x 4.2 x 4.0 5.0 x 8.1 x 0.75
7.5 10 - 20 25 27 DVTK0027E 4 4.0 x 4.2 x 4.0 5.0 x 8.1 x 0.75
10 12.5 15 25 30 35 DVTK0035E 4 4.0 x 4.2 x 4.0 5.0 x 8.1 x 0.75
12.5 15 18.5-22 30 40 45 DVTK0045E 6 4.4 x 4.2 x 4.0 5.0 x 8.1 x 0.75
15 20 - 40 50 55 DVTK0055E 8 5.0 x 5.9 x 4.3 5.0 x 8.1 x 0.75
20 25 30 50 60 65 DVTK0065E 10 5.0 x 5.9 x 4.7 5.0 x 8.1 x 0.75
25 30 37 60 75 80 DVTK0080E 11 5.0 x 5.9 x 4.9 5.0 x 8.1 x 0.75
30 40 45 - 55 75 100 110 DVTK0110E 15 5.5 x 7.1 x 5.1 6.3 x 10.3 x 1.25
40 50 - 100 125 130 DVTK0130E 13 5.5 x 7.1 x 5.1 6.3 x 10.3 x 1.25
50 60 75 - 90 125 150 160 DVTK0160E 22 5.5 x 7.1 x 5.8 6.3 x 10.3 x 1.25
60 75 110 150 200 200 DVTK0200E 29 6.9 x 8.9 x 6.1 6.3 x 10.3 x 1.25
75 100 132 200 250 250 DVTK0250E 29 6.9 x 8.9 x 6.1 6.3 x 10.3 x 1.25
100 125 160 250 300 305 DVTK0305E 30 7.0 x 8.9 x 6.6 6.3 x 10.3 x 1.25
125 150 185-200 300 350 365 DVTK0365E 41 7.3 x 8.9 x 7.2 6.3 x 10.3 x 1.25
150 175 - 350 450 415 DVTK0415E 49 7.4 x 9.6 x 8.1 6.3 x 10.3 x 1.25
175 225 250
400–
450
500 -
550 515 DVTK0515E 62 8.3 x 10.8 x 7.9 (2) 6.3 x 10.3 x 1.25
200 250 315 500 600 600 DVTK0600E 71 8.4 x 10.8 x 8.6 (2) 6.3 x 10.3 x 1.25
250 300 375
600-
605
700 750 DVTK0750E 113 11.1 x 14.3 x 9.5 (2) 6.3 x 10.3 x 1.25

dV E-Series Technical Reference Manual 208V – 600V
Form: DVT-TRM-E December 2021 Rev. 00116
Part Number Selection Tables
Table 4-2: Open Panel Selection Table
208V
Motor
HP
240V
Motor
HP
380V
Motor
KW
480V
Motor
HP
550V-
600V
Motor
HP
Filter
Amp
Rating
Part
Number
App.
Wt.
(lbs.)
Filter Dimensions
(in.)
(H x W x D)
0.5 .75 0.5- 1.1 0.5-1.5 0.5 - 2 3 DVTP0003E 6 8.9 x 5.5 x 7.7
0.75 1 1.5 2 3 4 DVTP0004E 6 8.9 x 5.5 x 7.7
1.5 2 2.2 - 3 3 5 7 DVTP0007E 6 8.9 x 5.5 x 7.7
2 3 4 5 7.5 9 DVTP0009E 6 8.9 x 5.5 x 7.7
3 4 5.5 7.5 10 12 DVTP0012E 6 8.9 x 5.5 x 7.7
5 5.5 7.5 10 15 17 DVTP0017E7 8.9 x 5.5 x 8.0
5.5 7.5 11 15 20 22 DVTP0022E 7 8.9 x 5.5 x 8.0
7.5 10 - 20 25 27 DVTP0027E 7 8.9 x 5.5 x 8.0
10 12.5 15 25 30 35 DVTP0035E 9 12.0 x 8.0 x 8.1
12.5 15 18.5-22 30 40 45 DVTP0045E 11 12.0 x 8.0 x 8.1
15 20 - 40 50 55 DVTP0055E 12 12.0 x 8.0 x 9.0
20 25 30 50 60 65 DVTP0065E 14 12.0 x 8.0 x 9.0
25 30 37 60 75 80 DVTP0080E 16 12.0 x 8.0 x 9.0
30 40 45 - 55 75 100 110 DVTP0110E 19 12.0 x 8.0 x 9.5
40 50 - 100 125 130 DVTP0130E 15 6.4 x 10.5 x 8.6
50 60 75 - 90 125 150 160 DVTP0160E 24 6.4 x 10.5 x 9.9
60 75 110 150 200 200 DVTP0200E 32 6.9 x 11.0 x 9.5
75 100 132 200 250 250 DVTP0250E 32 7.0 x 11.0 x 9.5
100 125 160 250 300 305 DVTP0305E 35 7.3 x 11.5 x 11.0
125 150 185-200 300 350 365 DVTP0365E 45 7.3 x 11.5 x 11.6
150 175 - 350 450 415 DVTP0415E 57 7.3 x 11.5 x 13.0
175 225 250
400–
450
500 -
550 515 DVTP0515E 72 8.4 x 12.3 x 14.8
200 250 315 500 600 600 DVTP0600E 82 8.4 x 12.3 x 16.4
250 300 375
600-
605
700 750 DVTP0750E 129 11.4 x 15.0 x 18.0

dV E-Series Technical Reference Manual 208V – 600V
17 Form: DVT-TRM-E December 2021 Rev. 001
Part Number Selection Tables
Table 4-3: Enclosed NEMA 1/2 Selection Table
208V
Motor
HP
240V
Motor
HP
380V
Motor
KW
480V
Motor
HP
550V-
600V
Motor
HP
Filter
Amp
Rating
Part
Number
App.
Wt.
(lbs.)
NEMA 1/2
Enclosure
(in.) (H x W x D)
0.5 .75
0.5 –
1.1
0.5 –
1.5 0.5 - 2 3 DVTG0003E 20 13.2 x 13.0 x 13.1
0.75 1 1.5 2 3 4 DVTG0004E 20 13.2 x 13.0 x 13.1
1.5 2 2.2 - 3 3 5 7 DVTG0007E 20 13.2 x 13.0 x 13.1
2 3 4 5 7.5 9 DVTG0009E 20 13.2 x 13.0 x 13.1
3 4 5.5 7.5 10 12 DVTG0012E 20 13.2 x 13.0 x 13.1
5 5.5 7.5 10 15 17 DVTG0017E 21 13.2 x 13.0 x 13.1
5.5 7.5 11 15 20 22 DVTG0022E 21 13.2 x 13.0 x 13.1
7.5 10 - 20 25 27 DVTG0027E 21 13.2 x 13.0 x 13.1
10 12.5 15 25 30 35 DVTG0035E 21 13.2 x 13.0 x 13.1
12.5 15
18.5 -
22 30 40 45 DVTG0045E 23 13.2 x 13.0 x 13.1
15 20 - 40 50 55 DVTG0055E 25 13.2 x 13.0 x 13.1
20 25 30 50 60 65 DVTG0065E 27 13.2 x 13.0 x 13.1
25 30 37 60 75 80 DVTG0080E 29 13.2 x 13.0 x 13.1
30 40 45 - 55 75 100 110 DVTG0110E 32 13.2 x 13.0 x 13.1
40 50 - 100 125 130 DVTG0130E 64 33.9 x 18.3 x 20.9
50 60 75 - 90 125 150 160 DVTG0160E 73 33.9 x 18.3 x 20.9
60 75 110 150 200 200 DVTG0200E 107 33.9 x 18.3 x 20.9
75 100 132 200 250 250 DVTG0250E 107 33.9 x 18.3 x 20.9
100 125 160 250 300 305 DVTG0305E 110 33.9 x 18.3 x 20.9
125 150
185 -
200 300 350 365 DVTG0365E 120 33.9 x 18.3 x 20.9
150 175 - 350 450 415 DVTG0415E 128 33.9 x 18.3 x 20.9
175 225 250
400 –
450
500 -
550 515 DVTG0515E 240 51.3 x 27.7 x 24.9
200 250 315 500 600 600 DVTG0600E 249 51.3 x 27.7 x 24.9
250 300 375
600-
605 700 750 DVTG0750E 296 51.3 x 27.7 x 24.9

dV E-Series Technical Reference Manual 208V – 600V
Form: DVT-TRM-E December 2021 Rev. 00118
Part Number Selection Tables
Table 4-4: Enclosed NEMA 3R Selection Table
208V
Motor
HP
240V
Motor
HP
380V
Motor
KW
480V
Motor
HP
550V-
600V
Motor
HP
Filter
Amp
Rating
Part
Number
App.
Wt.
(lbs.)
NEMA 3R
Enclosure
(in.)
(H x W x D)
.5 .75
0.5 –
1.1
0.5 –
1.5 0.5 - 2 3 DVTW0003E 30 15.5 x 11.0 x 12.0
.75 1 1.5 2 3 4 DVTW0004E 30 15.5 x 11.0 x 12.0
1.5 2 2.2 - 3 3 5 7 DVTW0007E 30 15.5 x 11.0 x 12.0
2 3 4 5 7.5 9 DVTW0009E 30 15.5 x 11.0 x 12.0
3 4 5.5 7.5 10 12 DVTW0012E 30 15.5 x 11.0 x 12.0
5 5.5 7.5 10 15 17 DVTW0017E 31 15.5 x 11.0 x 12.0
5.5 7.5 11 15 20 22 DVTW0022E 31 15.5 x 11.0 x 12.0
7.5 10 - 20 25 27 DVTW0027E 31 15.5 x 11.0 x 12.0
10 12.5 15 25 30 35 DVTW0035E 31 15.5 x 11.0 x 12.0
12.5 15
18.5 -
22 30 40 45 DVTW0045E 33 15.5 x 11.0 x 12.0
15 20 - 40 50 55 DVTW0055E 66 24.0 x 12.5 x 23.0
20 25 30 50 60 65 DVTW0065E 68 24.0 x 12.5 x 23.0
25 30 37 60 75 80 DVTW0080E 70 24.0 x 12.5 x 23.0
30 40 45 - 55 75 100 110 DVTW0110E 73 24.0 x 12.5 x 23.0
40 50 - 100 125 130 DVTW0130E 72 24.0 x 12.5 x 23.0
50 60 75 - 90 125 150 160 DVTW0160E 80 24.0 x 12.5 x 23.0
60 75 110 150 200 200 DVTW0200E 118 33.9 x 18.3 x 26.0
75 100 132 200 250 250 DVTW0250E 118 33.9 x 18.3 x 26.0
100 125 160 250 300 305 DVTW0305E 120 33.9 x 18.3 x 26.0
125 150
185 -
200
300 350 365 DVTW0365E 131 33.9 x 18.3 x 26.0
150 175 - 350 450 415 DVTW0415E 139 33.9 x 18.3 x 26.0
175 225 250
400 –
450
500 -
550 515 DVTW0515E 253 51.3 x 27.7 x 30.0
200 250 315 500 600 600 DVTW0600E 262 51.3 x 27.7 x 30.0
250 300 375
600-
605 700 750 DVTW0750E 309 51.3 x 27.7 x 30.0

dV E-Series Technical Reference Manual 208V – 600V
19 Form: DVT-TRM-E December 2021 Rev. 001
5. HOW TO INSTALL
Installation Checklist
WARNING
Prior to installation, please review the safety instructions on pages 1 & 2.
Failure to practice this can result in body injury!
Input and output wiring to the filter should be performed by authorized personnel
in accordance with NEC and all local electrical codes and regulations.
WARNING
The filter is designed for use with copper conductors with a minimum
temperature rating of 75 degrees C.
The dV E-Series filters are supplied in the following mechanical configurations:
•Kits (3A-750A): Reactor and resistor are provided separately and are not preassembled or
pre-wired.
•Open Panel assemblies (3A-750A): Reactor and resistor are assembled on a panel and pre-
wired together.
•Floor mounted general purpose NEMA 1/2 & 3R cabinets (3A - 750A): Reactor and
resistor/resistor panel are supplied in a cabinet with all items pre-wired together.
Minimum Required Space:
When determining the internal temperature rise and cooling requirements of the enclosure,
include the power dissipation of the filter along with all the other components located in the panel.
A general guideline is to allow a side clearance of four (4) inches and a vertical clearance of six
(6) inches for proper heat dissipation and access within the enclosure. Clearances may be less if
proper ventilation exists. Filter components must operate within temperatures specified in this
manual or filter operating life will be compromised. Also, be aware of minimum electrical
clearances as defined by the appropriate system safety standard(s). The Kit and Open panel
versions of the dV E-Series filters generate heat and should be positioned away from heat
sensitive components. Avoid locations where the filter would be subjected to excessive vibrations.
Locate the filter as close to the inverter as possible.
General purpose NEMA 1/2 and 3R enclosed filters are designed for floor mounting in an
environment suitable for the enclosure type. Do not install in or near a corrosive environment.
Avoid locations where the filter would be subjected to excessive vibrations. Allow a minimum side
and back clearance of eight (8) inches and front clearance of thirty-six (36) inches for proper heat
dissipation and access.

dV E-Series Technical Reference Manual 208V – 600V
Form: DVT-TRM-E December 2021 Rev. 00120
Grounding
NOTE: For cable shield grounding follow the drive manufacturer’s recommendations.
Power Wiring Connection
Verify that the power source to which the filter is to be connected is in agreement with the
nameplate data on the filter. A fused disconnect switch or circuit breaker should be installed
between the filter and its source of power in accordance with the requirements of the NEC and
all local electrical codes and regulations. Refer to the drive user manual for selection of the
correct fuse rating and class.
For part numbers starting with DVTK, interconnection between the reactor, resistor, drive, and
motor is shown in Figure 5-2: Kit Diagram (p22).
For part numbers starting with DVTP, DVTG, or DVTW, interconnection between the filter, drive,
and motor is shown in Figure 5-3: Open Panel and Enclosed Diagram (p23).
Wire gauge range and terminal torque requirements for the dV E-Series are shown in Table 5-1:
Torque Ratings (p24).
Refer to the drive user manual for instructions on interconnecting the drive and motor and the
correct start-up procedures for the drive.
The filter is designed for use with copper conductors with a minimum temperature rating of 75
degrees C.
WARNING
The filter must always be grounded with a grounding conductor connected to
ground terminals.
For panel mounted units, ensure a 2” x 2” area is cleaned of paint and varnish
on lower mounting bracket for ground connection.
WARNING
Input and output power wiring to the filter should be performed by authorized
personnel in accordance with the NEC and all local electrical codes and
regulations.
Cable lugs and mounting hardware are provided by the customer.
Any extremely low or high resistance readings indicate miswiring and may result
in damage to filter components if not corrected.
On NEMA 3R enclosures, CAB-26AP and larger, no live parts shall be mounted
below 8 inches from the bottom of the enclosure.
Table of contents
Other MTE Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Bosch
Bosch Rexroth BS 2/C Series Assembly instructions

MIYAWAKI
MIYAWAKI RE3 Installation, operation & maintenance manual

BONFIGLIOLI
BONFIGLIOLI 700C Series Installation and service manual

ABB
ABB HT570859 Operation manual

TE Connectivity
TE Connectivity AMP-O-LECTRIC G Customer's manual

HEIDENHAIN
HEIDENHAIN LIP 2x1 Mounting instructions