manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. MULTISPAN
  6. •
  7. Measuring Instrument
  8. •
  9. MULTISPAN AVF-19N User manual

MULTISPAN AVF-19N User manual

Other MULTISPAN Measuring Instrument manuals

MULTISPAN VOLT-19N User manual

MULTISPAN

MULTISPAN VOLT-19N User manual

MULTISPAN MFM 13-M1 User manual

MULTISPAN

MULTISPAN MFM 13-M1 User manual

MULTISPAN AVF-19N User manual

MULTISPAN

MULTISPAN AVF-19N User manual

MULTISPAN MPD-19N User manual

MULTISPAN

MULTISPAN MPD-19N User manual

MULTISPAN AMP 13 User manual

MULTISPAN

MULTISPAN AMP 13 User manual

MULTISPAN EM-10 User manual

MULTISPAN

MULTISPAN EM-10 User manual

MULTISPAN AMP-19 User manual

MULTISPAN

MULTISPAN AMP-19 User manual

MULTISPAN RPM-1201 User manual

MULTISPAN

MULTISPAN RPM-1201 User manual

MULTISPAN AV-11A User manual

MULTISPAN

MULTISPAN AV-11A User manual

MULTISPAN MI-631P User manual

MULTISPAN

MULTISPAN MI-631P User manual

MULTISPAN AVH-14 User manual

MULTISPAN

MULTISPAN AVH-14 User manual

MULTISPAN LC-3006 User manual

MULTISPAN

MULTISPAN LC-3006 User manual

MULTISPAN EPM-13N User manual

MULTISPAN

MULTISPAN EPM-13N User manual

MULTISPAN AVF-19N User manual

MULTISPAN

MULTISPAN AVF-19N User manual

MULTISPAN AV-14DA User manual

MULTISPAN

MULTISPAN AV-14DA User manual

MULTISPAN AVH-14N User manual

MULTISPAN

MULTISPAN AVH-14N User manual

MULTISPAN AVH 14N-M1 User manual

MULTISPAN

MULTISPAN AVH 14N-M1 User manual

MULTISPAN PI 38 User manual

MULTISPAN

MULTISPAN PI 38 User manual

MULTISPAN PIC-38 User manual

MULTISPAN

MULTISPAN PIC-38 User manual

MULTISPAN MVC-72N User manual

MULTISPAN

MULTISPAN MVC-72N User manual

MULTISPAN AVH-133 Manual User manual

MULTISPAN

MULTISPAN AVH-133 Manual User manual

MULTISPAN AVH 13N User manual

MULTISPAN

MULTISPAN AVH 13N User manual

MULTISPAN AVF-133 User manual

MULTISPAN

MULTISPAN AVF-133 User manual

MULTISPAN AVH-14N User manual

MULTISPAN

MULTISPAN AVH-14N User manual

Popular Measuring Instrument manuals by other brands

Powerfix Profi 278296 Operation and safety notes

Powerfix Profi

Powerfix Profi 278296 Operation and safety notes

Test Equipment Depot GVT-427B user manual

Test Equipment Depot

Test Equipment Depot GVT-427B user manual

Fieldpiece ACH Operator's manual

Fieldpiece

Fieldpiece ACH Operator's manual

FLYSURFER VIRON3 user manual

FLYSURFER

FLYSURFER VIRON3 user manual

GMW TG uni 1 operating manual

GMW

GMW TG uni 1 operating manual

Downeaster Wind & Weather Medallion Series instruction manual

Downeaster

Downeaster Wind & Weather Medallion Series instruction manual

Hanna Instruments HI96725C instruction manual

Hanna Instruments

Hanna Instruments HI96725C instruction manual

Nokeval KMR260 quick guide

Nokeval

Nokeval KMR260 quick guide

HOKUYO AUTOMATIC UBG-05LN instruction manual

HOKUYO AUTOMATIC

HOKUYO AUTOMATIC UBG-05LN instruction manual

Fluke 96000 Series Operator's manual

Fluke

Fluke 96000 Series Operator's manual

Test Products International SP565 user manual

Test Products International

Test Products International SP565 user manual

General Sleep Zmachine Insight+ DT-200 Service manual

General Sleep

General Sleep Zmachine Insight+ DT-200 Service manual

Sensa Core Lacto Spark user manual

Sensa Core

Sensa Core Lacto Spark user manual

VOLTCRAFT UTS-1980 operating instructions

VOLTCRAFT

VOLTCRAFT UTS-1980 operating instructions

EBCHQ 94915 Operation manual

EBCHQ

EBCHQ 94915 Operation manual

Balluff BIP LD2-T017-01-EP-S4 Series user guide

Balluff

Balluff BIP LD2-T017-01-EP-S4 Series user guide

Pulsar IMP Lite Series instruction manual

Pulsar

Pulsar IMP Lite Series instruction manual

ETCR 6800 user manual

ETCR

ETCR 6800 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

3) In CT Ratio parameter setting if primary C.T is
greater than 999 Amp. Then display will shown
as below.
20 to 300V (L - N)
35 to 520V (L - L)
Up to 9999 Hr 59 min
230V AC,50Hz ± 20%
4VA
12347 8 9
12
1314
10
11
5
1617181920
6
15
S1
S1
S1 S2 S2 S2
LN
230V AC
50 , 4HZ VA !
Range
Current: 0.5 To 5A AC
Voltage(L-L) : 35-520V AC
(L-N) : 20-300V AC Accuracy Class: 0.5
System:
3Ph-4W/3Ph-3W/
1Ph-2W
CT Selection up to 6000/5 Amp AC
L1
L2
L3
VL1VL2VL3N
CAT III
Made in India
www.multispanindia.com
FRONT PANEL DESCRIPTION
4) If CT Ratio is greater than 999 Amp. then ‘‘KA’’ LED
will be turn on and Amp page will be shown as below.
KA
Page 2
FRONT PANEL DESCRIPTION
SYMBOLFUNCTION
Operator mode:
Parameter setting mode:
To decrement value in Parameter
Setting Mode
To save and exit from menu
To change page
To increment value
Scroll & hold
PARAMETER SETTING
for 5 sec
p a s
1 9
C T R
Press + key for 3 Second.
Press key to save & exit
Press key to save & exit
Press key to save & exit
SET
ENT
SET
ENT
SET
ENT
SET
ENT
CT Ratio
(5-6000Amp
N E T
4 W
3 P
(3Ø-3W, 3Ø-4W,1Ø-2W)
Selectable)
p a s
3 9
Press + key For 3 Second. Press + key For 3 Second.
SET
ENT
L D H
y e s
r s t
(Yes /No)
p a s
2 9
L D H
L O D
r p m
E N B
5
e n b
Press + key For 3 Second.
SET
ENT
Load Hour
(Enable/Disable)
P E R
IF Disable
IF Enable
IF Enable
(5-50%)
p O L
4
IF Disable
(1-28)
(Enable/Disable)
-
s
To Reset Load Hour
To Load Hour & RPM Enable/Disable
To CT Ratio & Network selection
2) VLN Page :-
1) VLL Page :-
3) Amp Page :-
4) V Avg Page :-
LL
5) V Avg Page :-
LN
3Ø-3W NETWORK CONNECTION
1) VLL Page :-
2) Amp Page :-
6) Load Hour Page :-
7) RPM Page :-
3) V Avg Page :-
LL
Page 2
1. Prepare the panel cutout with proper dimensions as shown
above.
2. Fit the unit into the panel with the help of clamp given.
3. The equipment in its installed state must not come in close
proximity to any heating source, caustic vapors, oil steam,
or other unwanted process byproducts.
4. Use the specified size of crimp terminal (M3.5 screws) to
wire the terminal block. Tightening the screws on the
terminal block using the tightening torque of the range of
1.2 N.m.
5. Do not connect anything to unused terminals.
1. This equipment, being built-in-type, normally becomes a
part of main control panel and in such case the terminals
do not remain accessible to the end user after installation
and internal wiring.
INSTALLATION GUIDELINES
2. Do not allow pieces of metal, wire clippings, or fine metallic
fillings from installation to enter the product or else it may
lead to a safety hazard that may in turn endanger life or
cause electrical shock to the operator.
3. Circuit breaker or mains switch must be installed between
power source and supply terminal to facilitate power ‘ON’
or ‘OFF’ function. However this mains switch or circuit
breaker must be installed at convenient place normally
accessible to the operator.
4. Use and store the instrument within the specified ambient
temperature and humidity ranges as mentioned in this
manual.
1. The equipment should be cleaned regularly to avoid
blockage of ventilating parts.
2. Clean the equipment with a clean soft cloth. Do not use
isopropyl alcohol or any other cleaning agent.
3. Fusible resistor must not be replaced by operator.
Read complete instructions prior to installation
and operation of the unit.
WARNING : Risk of electric shock.
All safety related codifications, symbols and instructions
that appear in this operating manual or on the equipment must
be strictly followed to ensure the safety of the operating
personnel as well as the instrument.
If all the equipment is not handled in a manner specified
by the manufacturer, it might impair the protection provided
by the equipment.
WARNING : Risk of electric shock.
MAINTENANCE
SAFETY PRECAUTION
!
WARNING GUIDELINES
MECHANICAL INSTALLATION
1. To prevent the risk of electric shock, power supply to the
equipment must be kept OFF while doing the wiring
arrangement. Do not touch the terminals while power is
being supplied.
2. To reduce electro magnetic interference, use wire with
adequate rating and twists of the same of equal size shall
be made with shortest connection.
3. Cable used for connection to power source, must have a
cross section of 1mm or greater. These wires should have
insulations capacity made of at least 1.5kV.
4. A better anti-noise effect can be expected by using
standard power supply cable for the instrument.
1Ø-2W NETWORK CONNECTION
1) Volt, Amp & Freq. Page :-
4) Load Hour Page :-
2) Load Hour Page :-
3) RPM Page :-
5) RPM Page :-