PV = Process Value
SV = Set Value
CPR 126
CURRENT PROTECTION RELAY
TECHNICAL SPECIFICATION
MECHANICAL INSTALLATION
TERMINAL CONNECTION
FEATURES:
INPUT SPECIFICATION:
DISPLAY AND KEY:
OUTPUT SPECIFICATION:
AUXILIARY SUPPLY:
GENERAL SPECIFICATION:
Primary CT value
True RMS Measurement
Protection available
Over Load
Auto/Manual /ZVR (Zero Value Reset) reset option
Under Load
3 digit bright LED display
Current Asymmetry
Three phase current display with LED indication
Single phase prevention (i.e it can trip relay in case of
any phase current is become zero)
Auto save out feature
Time parameter : Power on delay
Trip delay
Initial time delay
Recovery time (Auto reset)
Secondary current AC
Resolution
5 to 999 Selectable
0.5 to 5 Amp AC
0.01A, 0.1A, 1A
Display
Relay
Supply voltage
Dimension (mm)
Keys
Relay Type
Power consumption
(VA RATING)
Rating
Trip Setting
Time parameter
3 digit, 1line, 7 seg, 0.4” RED LED
1 nos.
75 (H) x 45 (W) x 110 (D) mm
SET, INC, DEC/ RST
1 C/O (NO-C-NC)
3 VA @ 230V AC MAX
10A, 230V AC/28 V DC
Under current : 0.00 to 100% of
primary C.T value
Trip delay time : 0 to 999 sec
Power on time : 0 to 99 sec
Initial time delay : 0 to 99 sec
Over current : 0.00 - 125% of
primary C.T value
ENVIRONMENT CONDITION:
Relative Humidity
Operating Temp. 0°C to 55°C
UP to 95% RH
(non-condensing)
100 to 270V AC, 50-60Hz
Recovery time : 0 to 99 sec
110
Front View(mm)
A
SET
NO
LNCNC
CPR 126
A1
RA2 A3
40 0
75
Side View(mm)
75
45
NO
LNCNC
CPR 126
A1
RA2 A3
A
SET
L1
L2
L3
N
TO
LOAD
Class 1.0 (Standard)
ACCURACY
KEY OPERATION
Read complete instructions prior to installation
and operation of the unit.
WARNING : Risk of electric shock.
All safety related codifications, symbols and instructions that
appear in this operating manual or on the equipment must be
strictly followed to ensure the safety of the operating personnel
as well as the instrument.
If all the equipment is not handled in a manner specified by
the manufacturer, it might impair the protection provided by the
equipment.
MECHANICAL INSTALLATION GUIDELINES
MAINTENANCE
1. The equipment should be cleaned regularly to avoid
blockage of ventilating parts.
2. Clean the equipment with a clean soft cloth. Do not use
isopropyl alcohol or any other cleaning agent.
3. Fusible resistor must not be replaced by operator.
Page -1
To enter in parameter setting
OR
To view individual phase current
To reset the relay contact in
manual mode after tripping
PRESS KEYFUNCTION
OPERATOR MODE
PARAMETER SETTING MODE
It is used to set parameter value
and to be save & exit from menu
To increment value in parameter
setting
To decrement value in parameter
setting
For 5 sec
SET
SET
To Scroll & Hold Page SET +
R Phase current
Y Phase current
B Phase current
Relay
A1
A2
A3
R
ØLED INDICATION
DISPLAY PAGE
1) R-Phase current
2) Y- Phase current
3) B-Phase current
4. 2 5
4. 3 0
4. 2 0
A2
A2
A2
A3
A3
A3
R
R
R
A1
A1
A1
1) To install the instrument on a DIN rail, raise the clamp at
the back of the instrument and place it on the rail. Now
release the clamp, so the instrument fits on the DIN rail.
2) Ensure proper fitting of the instrument by pulling it
outwards.
3) To remove the instrument raise the clamp to release it
from the DIN rail.
4) The equipment in its installed state must not come in
close proximity to any heating source, caustic vapors, oil
steam, or other unwanted process byproducts.
5) Do not connect anything to unused terminals.
INSTALLATION GUIDELINES
1) Do not allow pieces of metal, wire clippings, or fine
metallic fillings from installation to enter the product or
else it may lead to a safety hazard that may in turn
endanger life or cause electrical shock to the operator.
2) Circuit breaker or mains switch must be installed
between power source and supply terminal to facilitate
power ‘ON’ or ‘OFF’ function. However this mains switch
or circuit breaker must be installed at convenient place
normally accessible to the operator.
3) Use and store the instrument within the specified ambient
temperature and humidity ranges as mentioned in this
manual.
SAFETY PRECAUTION
!
WARNING GUIDELINES
WARNING : Risk of electric shock.
1) To prevent the risk of electric shock, power supply to the
equipment must be kept OFF while doing the wiring
arrangement. Do not touch the terminals while power is
being supplied.
2) To reduce electro magnetic interference, use wire with
adequate rating and twists of the same of equal size shall
be made with shortest connection.
3. Cable used for connection to power source, must have a
cross section of 1mm or greater. These wires should have
insulations capacity made of at least 1.5kV.
4) A better anti-noise effect can be expected by using
standard power supply cable for the instrument.
Password
Over current
(Enable/Disable)
(Enable/Disable)
(Enable/Disable)
(Enable/Disable)
Press key for save & exit
Press key for save & exit
(Single Phase
Prevention)
(Under Current)
(Asymmetry)
Press key
Press key
Press key
Press key
Press key
Press key
Press key
Press key
Press key
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
SET
p a s
1 1
O C
e n b
u C
e n b
a s
e n b
e n b
s p p
Password
If over current is enable
If under current is enable
If Asymmetry
is enable
If over current
is disable
If under
current
is disable
If Asymmetry
is disable
Over current
(Over current value)
(0.00 - 125% of
primary C.T Value)
(0.00 - 100% of
primary C.T Value)
(Under current value)
(Asymmetry percentage)
(2 - 30%)
(Under Current)
(Asymmetry)
Press key
Press key
Press key
Press key
Press key
SET
Press key
p a s
7 3
O C
5 0 0
5 0 0
u C
a s
2 0
Enter password 73
Enter password 11
Press key
for 5 sec
SET
Press key
for 5 sec
NOTE :-
- If Auxiliary supply cut out without fault Reset, Then
fault will be display at next power on.
- If Reset Mode Selected As ZVR (Zero Value Reset),
then the Relay will be reset after Selected Reset time
once the healthy condition achieved OR Zero Value
reached.
SET
- To Reset fault press key.
O C O C
A2 A3R A1
3 4 5
A2 A3R A1
Scroll
Over current in R - Phase
Over current
Value = 34.5 A
◘
◘
U C
A2 A3R A1
1 0 0
A2 A3R A1
Scroll
Under current in Y - Phase
Under current
Value = 10.0 A
◘
◘
A S
A2 A3R A1
2 0
A2 A3R A1
Scroll
Asymmetry current
between R & Y Phase
Asymmetry
percentage=20%
◘
◘
S P P
A2 A3R A1
Single phase prevention
fault occurred in B - Phase
◘
Password 11 : To Enable / Disable trip parameter
(Over current, Under current,
Asymmetry, Single phase prevention)
Password 73 : To set trip value of Over current,
Under current, Asymmetry percentage
Password 37 : To set Power on time, ITD, Trip delay time,
reset Mode,Relay Fault mode ,C.T ratio
SET
Press key
SET
Press key
1 1
Note : LED Status- blinking LED LED on LED off
FAULT MESSAGE
PARAMETER SETTING
CONTROL FUNCTION
Password
Power on time
(0-99 sec)
(0-99 sec)
(0-999 sec)
(Relay fault mode)
Primary C.T ratio
Power Fault Memory
(On/Off)
(5-999 AmP)
Yes / No
Press key for save & exit
(Initial time delay)
(Trip delay time)
Press key
Press key
Press key
Press key
Press key
Press key
Press key
SET
SET
SET
SET
SET
SET
SET
SET
p a s
3 7
P O N
2 0
I T D
2 5
T D L
2
R F m
C T R
P F M
O N
5
Y E S
Enter password 37
Press key
for 5 sec
SET
Press key
Press key
SET
SET
Press key
SET
Press key
Press key
Press key
Press key
SET
SET
SET
SET
a u t
r S t
r C t
5
(Auto / Manual / ZVR)
(Reset mode)
(Recovery time)
Press key
Press key
Press key
SET
SET
SET
If
manual reset
mode select
(0 to 99 sec.)
If Auto/ZVR reset mode select
Under Current Under Current - Enable
RLY fault - OFF
Power on time = 5 sec Initial time delay = 5 sec
Trip delay time = 5 sec
Current
U.C Set point
OFF
TRP
Time
ON
5 10 15 20
Power
On ITD
TRP
Delay
OFF
R
Y
B
Reset mode = Manual
Page - 2
Asymmetry Current
Over Current
Current
SPP - Enable
Asymmetry
current - Enable
OFF
20%
Over Current - Enable
RLY fault - Off
RLY fault -
Asymmetry
percentage -
RLY fault - OFF
Time
Single Phase Prevention
Power
On ITD
TRP
Delay
OFF
TRP
ON
5 10 15 20 25
Current
Power
On ITD
TRP
Delay
OFF
TRP
ON
5 10 15
OFF
OFF
Current
O.C Set point
Time
5 10 15 20
Power
On ITD
OFF
TRP
ON
OFF
R
Y
B
TRP
Delay
R
Y
B
20 % asymmetry
current
20
R
Y
B
Time

Other MULTISPAN Relay manuals

MULTISPAN MI-532P User manual

MULTISPAN

MULTISPAN MI-532P User manual

MULTISPAN VPR 3P User manual

MULTISPAN

MULTISPAN VPR 3P User manual

MULTISPAN VMR 13 User manual

MULTISPAN

MULTISPAN VMR 13 User manual

MULTISPAN ELR-19N User manual

MULTISPAN

MULTISPAN ELR-19N User manual

MULTISPAN CPR 126-1C User manual

MULTISPAN

MULTISPAN CPR 126-1C User manual

MULTISPAN VPR 126 User manual

MULTISPAN

MULTISPAN VPR 126 User manual

MULTISPAN EN-19N User manual

MULTISPAN

MULTISPAN EN-19N User manual

MULTISPAN ELR-19N User manual

MULTISPAN

MULTISPAN ELR-19N User manual

MULTISPAN VMR 23 Instruction sheet

MULTISPAN

MULTISPAN VMR 23 Instruction sheet

MULTISPAN ELR-63 User manual

MULTISPAN

MULTISPAN ELR-63 User manual

MULTISPAN VPR-126-2R User manual

MULTISPAN

MULTISPAN VPR-126-2R User manual

MULTISPAN VR-3KN User manual

MULTISPAN

MULTISPAN VR-3KN User manual

MULTISPAN MI-632 Instruction sheet

MULTISPAN

MULTISPAN MI-632 Instruction sheet

MULTISPAN VTR-632 User manual

MULTISPAN

MULTISPAN VTR-632 User manual

MULTISPAN VPR 3P User manual

MULTISPAN

MULTISPAN VPR 3P User manual

MULTISPAN ELR-19N-M1 Instruction sheet

MULTISPAN

MULTISPAN ELR-19N-M1 Instruction sheet

MULTISPAN CR-3K User manual

MULTISPAN

MULTISPAN CR-3K User manual

MULTISPAN ELR 19N-M1 User manual

MULTISPAN

MULTISPAN ELR 19N-M1 User manual

MULTISPAN SVR-22 Instruction sheet

MULTISPAN

MULTISPAN SVR-22 Instruction sheet

MULTISPAN VPR-22 Instruction sheet

MULTISPAN

MULTISPAN VPR-22 Instruction sheet

MULTISPAN MI-632-24 User manual

MULTISPAN

MULTISPAN MI-632-24 User manual

MULTISPAN VPR-22U User manual

MULTISPAN

MULTISPAN VPR-22U User manual

MULTISPAN MI-631-24 Instruction sheet

MULTISPAN

MULTISPAN MI-631-24 Instruction sheet

Popular Relay manuals by other brands

GMI D5000 Series Safety instructions

GMI

GMI D5000 Series Safety instructions

CNC4PC C15 manual

CNC4PC

CNC4PC C15 manual

Freelap Relay Coach BLE quick start guide

Freelap

Freelap Relay Coach BLE quick start guide

Rockwell Automation Allen-Bradley 193-T1D P Series Installation instruction

Rockwell Automation

Rockwell Automation Allen-Bradley 193-T1D P Series Installation instruction

ZIEHL MS220VA operating manual

ZIEHL

ZIEHL MS220VA operating manual

Sven RN-16D user manual

Sven

Sven RN-16D user manual

Pickering 4-781A Series user manual

Pickering

Pickering 4-781A Series user manual

Schweitzer Engineering Laboratories SEL-751 instruction manual

Schweitzer Engineering Laboratories

Schweitzer Engineering Laboratories SEL-751 instruction manual

ASO ELMON rail 32-242 operating manual

ASO

ASO ELMON rail 32-242 operating manual

GRUP ARGE ZMN32 user manual

GRUP ARGE

GRUP ARGE ZMN32 user manual

KUSSMAUL 091-63-OV instruction manual

KUSSMAUL

KUSSMAUL 091-63-OV instruction manual

Eaton Cutler-Hammer D64 Series instruction manual

Eaton

Eaton Cutler-Hammer D64 Series instruction manual

Pepperl+Fuchs LB6101H instruction manual

Pepperl+Fuchs

Pepperl+Fuchs LB6101H instruction manual

Pilz PNOZ X11P operating manual

Pilz

Pilz PNOZ X11P operating manual

ROOTECH ACCURA 7500 user manual

ROOTECH

ROOTECH ACCURA 7500 user manual

ABB REJ 527 Technical reference manual

ABB

ABB REJ 527 Technical reference manual

Allen-Bradley GUARDMASTER MINOTAURMSR125H manual

Allen-Bradley

Allen-Bradley GUARDMASTER MINOTAURMSR125H manual

LOVATO ELECTRIC PMF20 quick start guide

LOVATO ELECTRIC

LOVATO ELECTRIC PMF20 quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.