PV = Process Value
SV = Set Value
ELR-19N
MECHANICAL INSTALLATION
TERMINAL CONNECTION
Page - 1
Earth Leakage Relay
96 52
92
92
3
96
Outline Dimension (mm) Panel Cutout
Dimension (mm)
R
Earth Leakage Relay
ENT
RST
SET
ELR 19N
Set Value (A)
Ampere
TEST
0
0
0
2
1
9
8
4
AUXILIARY SUPPLY :
Supply Voltage 100 To 250 V AC,50/60Hz
Power Consumption
(VA Rating) 4VA @ 230 VAC MAX
ENVIRONMENT CONDITION:
Relative Humidity
Protection Level
(As per request)
Operating Temp. 0°C to 55°C
UP to 95% RH
(non-condensing)
IP-65 (Front side) As per IS/IEC
60529 : 2001
Made in India
www.multispanindia.com
12347 8 9
12
1314
10
11
5
1617181920
6
15
NCCNO
LN
S1 S2
CBCT
L1
L2
L3
N
TO
LOAD
100-250V AC
50/60Hz, 4VA
!
Input :30 mA To 3.00 Amp AC
FEATURE
TECNICAL SPECIFICATION
Earth Leakage Current Monitoring In 1Ø - 2W, 3Ø-3W
And 3Ø-4W
System
Test Mode Available.
Auto/Manual Triping Reset Facility.
Test/Trip Reset Via Front Key
Input Current
Display Currant Range
Resolution
30 mA To 3.00 Amp AC
0.030 To 3.000 Amp AC
INPUT SPECIFICATION :
If Current in mA = 1 mA
If Current in Amp = 0.001A
Display
Keys
Upper: 4 Digit ,7 Seg., 0.56”, Red
Lower: 4 Digit ,7 Seg., 0.56”,Green
SET, INC, DEC, ENT/RST
Relay
Relay Type
Rating
1 Nos.
1 C/O (NO-C-NC)
10A,230V AC Resistive Load
DISPLAY & KEYS :
OUTPUT SPECIFICATION :
Size (mm)
Panel Cutout
96(H) X 96(W) X 52(D)
92(H) X 92(W)
DIMENSION :
WARNING GUIDELINES
KEY OPERATION
OPERATION MODE
For 2 sec
For 5 sec
PARAMETER SETTING MODE
FUNCTION KEY PRESS
To Enter in Parameter Setting
To Enter in Test Mode
To Reset the Relay Contact
Manually After Tripping
ENT
RST
TEST
SET
To set parameter value
To increment parameter value.
To decrement parameter value.
Set parameter to be save & exit.
SET
TEST
ENT
RST
SAFETY PRECAUTION
!
Read complete instructions prior to installation
and operation of the unit.
WARNING : Risk of electric shock.
All safety related codifications, symbols and instructions that
appear in this operating manual or on the equipment must be
strictly followed to ensure the safety of the operating personnel
as well as the instrument.
If all the equipment is not handled in a manner specified by
the manufacturer, it might impair the protection provided by the
equipment.
MAINTENANCE
1. The equipment should be cleaned regularly to avoid blockage
of ventilating parts.
2. Clean the equipment with a clean soft cloth. Do not use
isopropyl alcohol or any other cleaning agent.
3. Fusible resistor must not be replaced by operator.
WARNING : Risk of electric shock.
1. To prevent the risk of electric shock, power supply to the
equipment must be kept OFF while doing the wiring
arrangement. Do not touch the terminals while power is
being supplied.
2. To reduce electro magnetic interference, use wire with
adequate rating and twists of the same of equal size shall
be made with shortest connection.
3. Cable used for connection to power source, must have a
cross section of 1mm or greater. These wires should have
insulations capacity made of at least 1.5kV.
4. When extending the thermocouple lead wires, always use
thermocouple compensation wires for wiring for the RTD
type, use a wiring material with a small lead resistance
(5 max per line) and no resistance differentials among
three wires should be present.
5. A better anti-noise effect can be expected by using
standard power supply cable for the instrument.
Ω
INSTALLATION GUIDELINES
1. This equipment, being built-in-type, normally becomes a
part of main control panel and in such case the terminals
do not remain accessible to the end user after installation
and internal wiring.
2. Do not allow pieces of metal, wire clippings, or fine metallic
fillings from installation to enter the product or else it may
lead to a safety hazard that may in turn endanger life or
cause electrical shock to the operator.
3. Circuit breaker or mains switch must be installed between
power source and supply terminal to facilitate power ‘ON’
or ‘OFF’ function. However this mains switch or circuit
breaker must be installed at convenient place normally
accessible to the operator.
4. Use and store the instrument within the specified ambient
temperature and humidity ranges as mentioned in this
manual.
MECHANICAL INSTALLATION GUIDELINES
1. Prepare the panel cutout with proper dimensions as shown
above.
2. Fit the unit into the panel with the help of clamp given.
3. The equipment in its installed state must not come in close
proximity to any heating source, caustic vapors, oil steam,
or other unwanted process Byproducts.
4. Use the specified size of crimp terminal (M3.5 screws) to
wire the terminal block. Tightening the screws on the
terminal block using the tightening torque of the range of
1.2 N.m.
5. Do not connect anything to unused terminals.
RLY-ON
RLY-OFF
HYST
2.000
1.900
Time
RLY-ON
Earth Leakage Current
Tripping Setting
Set Point
To Reset the Relay Contact after tripping two modes are
given.
NOTE: When Leakage Current < Setpoint
1) Auto Reset
Healthy Condition relay mode = ON
Trip Set Point = 2.000 Amp
Hysteresis = 0.100 Amp
Press Key For 2 Sec.
2) Manual Reset
Amp
ENT
RST
To Enter In Test Mode
Press Key for 5 sec
- Display Shows
T e S T
2 0 0 0
Where Relay is ON
R
- To exit from test mode, Press key
ENT
RST
TEST
TEST MODE
PARAMETER SETTING
/
/
/
Delay time
Hysterisis
Healthy condition relay mode
Reset Mode
Password Enable/disable
(Auto/Manual)
(Enable/Disable)
ON/OFF
0.001 to 3.000 Amp
Set leakage current
00.00 to 10.00 sec
0.000 to 2.999 Amp
Enter password “123”
Password
O N
Press key
Long Press key
Press key
Press key
Press key
Press key
Press key
Press key to save parameter & exit.
0 0 2 0
p a s s
s e t
d e L y
H Y S
R L Y
M O D E
P A S S
1 2 3
2 0 0 0
0 0 0 0
0 1 0 0
O F F
A U T O A N L
E N B d I s
1 0 0 0
(Actual Value of Earth
Leakage Current)
(Set Value of Earth
Leakage Current)
SET
SET
SET
SET
SET
SET
SET
ENT
RST
RESET FUNCTION
Earth Leakage Current
Tripping Setting
Set Point
Time
TRIP
RLY-ON
Delay
Time
Delay
Time
TRIP FUNCTION
Healthy Condition relay mode = ON

This manual suits for next models

3

Other MULTISPAN Relay manuals

MULTISPAN VPR-126-2R User manual

MULTISPAN

MULTISPAN VPR-126-2R User manual

MULTISPAN VTR-632 User manual

MULTISPAN

MULTISPAN VTR-632 User manual

MULTISPAN MI-632-24 User manual

MULTISPAN

MULTISPAN MI-632-24 User manual

MULTISPAN VMR 13 User manual

MULTISPAN

MULTISPAN VMR 13 User manual

MULTISPAN EN-19N User manual

MULTISPAN

MULTISPAN EN-19N User manual

MULTISPAN ELR 19N-M1 User manual

MULTISPAN

MULTISPAN ELR 19N-M1 User manual

MULTISPAN VPR-22 Instruction sheet

MULTISPAN

MULTISPAN VPR-22 Instruction sheet

MULTISPAN VPR 3P User manual

MULTISPAN

MULTISPAN VPR 3P User manual

MULTISPAN ELR-19N-M1 Instruction sheet

MULTISPAN

MULTISPAN ELR-19N-M1 Instruction sheet

MULTISPAN MI-631-24 Instruction sheet

MULTISPAN

MULTISPAN MI-631-24 Instruction sheet

MULTISPAN MI-632 Instruction sheet

MULTISPAN

MULTISPAN MI-632 Instruction sheet

MULTISPAN VR-3KN User manual

MULTISPAN

MULTISPAN VR-3KN User manual

MULTISPAN VPR-22U User manual

MULTISPAN

MULTISPAN VPR-22U User manual

MULTISPAN SVR-22 Instruction sheet

MULTISPAN

MULTISPAN SVR-22 Instruction sheet

MULTISPAN MI-532P User manual

MULTISPAN

MULTISPAN MI-532P User manual

MULTISPAN VMR 23 Instruction sheet

MULTISPAN

MULTISPAN VMR 23 Instruction sheet

MULTISPAN ELR-63 User manual

MULTISPAN

MULTISPAN ELR-63 User manual

MULTISPAN CR-3K User manual

MULTISPAN

MULTISPAN CR-3K User manual

MULTISPAN VPR 3P User manual

MULTISPAN

MULTISPAN VPR 3P User manual

MULTISPAN CPR 126 User manual

MULTISPAN

MULTISPAN CPR 126 User manual

MULTISPAN ELR-19N User manual

MULTISPAN

MULTISPAN ELR-19N User manual

MULTISPAN CPR 126-1C User manual

MULTISPAN

MULTISPAN CPR 126-1C User manual

MULTISPAN VPR 126 User manual

MULTISPAN

MULTISPAN VPR 126 User manual

Popular Relay manuals by other brands

Kemo Electronic B197 quick guide

Kemo Electronic

Kemo Electronic B197 quick guide

Eaton easyE4 series Application note

Eaton

Eaton easyE4 series Application note

Leuze MSI-SR5B Original operating instructions

Leuze

Leuze MSI-SR5B Original operating instructions

Omron ZEN Operation manual

Omron

Omron ZEN Operation manual

Circutor WRU-10 RAL manual

Circutor

Circutor WRU-10 RAL manual

Pilz PNOZ 16SP operating manual

Pilz

Pilz PNOZ 16SP operating manual

Eaton EMT6-K Instruction leaflet

Eaton

Eaton EMT6-K Instruction leaflet

Basler BE1-79A instruction manual

Basler

Basler BE1-79A instruction manual

Allen-Bradley Guardmaster 440R-S35011 installation instructions

Allen-Bradley

Allen-Bradley Guardmaster 440R-S35011 installation instructions

Littelfuse AF0100 instruction manual

Littelfuse

Littelfuse AF0100 instruction manual

Idem SCR-73-i manual

Idem

Idem SCR-73-i manual

Autonics SRH1 Series quick start guide

Autonics

Autonics SRH1 Series quick start guide

BEA LO-21K user guide

BEA

BEA LO-21K user guide

Pilz PNOZ s7 operating manual

Pilz

Pilz PNOZ s7 operating manual

GE CEY52B instructions

GE

GE CEY52B instructions

GE SPA11A instructions

GE

GE SPA11A instructions

Eaton ESR5-VE3-42 manual

Eaton

Eaton ESR5-VE3-42 manual

Eltako MFZ12DBT-UC manual

Eltako

Eltako MFZ12DBT-UC manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.