7
W415-1337 / 06.23.14
2.3 GENERAL INFORMATION
* When the appliance is installed at elevations above 4,500ft (1372m), and in the absence of specific
recommendations from the local authority having jurisdiction, the certified high altitude input rating shall be
reduced at the rate of 4% for each additional 1,000ft (305m).
This appliance is approved for bathroom, bedroom and bed-sitting room
installations and is suitable for mobile home installation. The natural
gas model can only be installed in a mobile home that is permanently
positioned on its site and fueled with natural gas. This appliance may be
installed in an aftermarket permanently located, manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating
plate. This appliance is not convertible for use with other gases, unless a
certified kit is used.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the
appliance and must be installed.
Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected.
2.4 RATING PLATE INFORMATION
65.2%
WHD31
EN
RATES AND EFFICIENCIES
NATURAL GAS PROPANE GAS
Altitude 0 - 4,500* 0 - 4,500*
Maximum Input 20,000 BTU/hr 16,000 BTU/hr
Maximum Output 13,780 BTU/hr 11,136 BTU/hr
Efficiency 68.9% 69.6%
Minimum Inlet Gas Supply Pressure 4.5” (11mb) Water Column 11” (27mb) Water Column
Maximum Inlet Gas Supply Pressure 7” (17mb) Water Column 13” (32mb) Water Column
Manifold Pressure Under Flow Conditions 3.5” (9mb) Water Column 10” (25mb) Water Column
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION
AND QUALITY!
For rating plate location, see “INSTALLATION
OVERVIEW” section.
This illustration is for reference only. Refer to the
rating plate on the appliance for accurate information.
NOTE: The rating plate must remain with the
appliance at all times. It must not be removed.
CONFORMS TO / CONFORMEAUX: ANSI Z21.50-2014, CERTIFIED TO / CERTIFIE
CSA 2.22-2014 VENTED GAS FIREPLACE / FOYER À GAZ VENTILÉ.
DIRECT VENT VENTED GAS FIREPLACE
APPROVED FOR BEDROOM, BATHROOM &
BEDSITTING ROOM INSTALLATION.
SUITABLE FOR MOBILE HOME
INSTALLATION IF INSTALLED IN
ACCORDANCE WITH THE CURRENT
STANDARD CAN/CSA Z240MH SERIES GAS
EQUIPPED MOBILE HOMES, IN CANADA OR
IN THE UNITED STATES THE
MANUFACTURED HOME CONSTRUCTION
AND SAFETY STANDARD, TITLE 24 CFR,
PART 3280. WHEN THIS US STANDARD IS
NOTAPPLICABLE USE THE STANDARD FOR
FIRE SAFETY CRITERIAFOR
MANUFACTURED HOME INSTALLATIONS,
SITES AND COMMUNITIES,ANSI / NFPA
501A. FOR USE WITH BARRIER W565-0121.
FOLLOW THE INSTALLATION INSTRUCTIONS
LOCATED IN THE INSTALLATION MANUAL.
FOYER À GAZ VENTILÉS À ÉVACUATION
DIRECTE. HOMOLOGUE POUR INSTALLATION
DANS UNE CHAMBRE ACOUCHER, UNE
SALLE DE BAIN ET UN STUDIO.APPROPRIE
POUR INSTALLATION DANSUNE MAISON
MOBILE SI SON INSTALLATION CONFORME
AUX EXIGENCES DE LA NORME CAN/CSA
Z240MH SERIE DE MAISONS MOBILES
EQUIPEES AU GAZ, EN VIGUEURAU CANADA
OU AUX ETATS-UNIS DE LANORME DE
SECURITE ET DE CONSTRUCTION DE
MAISONS MANUFACTUREES,TITRE 24 CFR,
SECTION 3280. DANS LE CAS OU CETTE
NORME D’ETATS-UNIS NE PEUTETRE
APPLIQUEE, SE REFERER ALA NORME
RELATIVE AU CRITERE DE MESURES DE
SECURITE CONTRE L’INCENDIE POUR LES
INSTALLATIONS DANS LES MAISONS
MANUFACTURES, LES SITES ETLES
COMMUNAUTES, ANSI/NFPA 501A.
POUR UNE
UTILISER AVEC BARRIÈRE W565-0121. SUIVEZ
LES INSTRUCTIONS D'INSTALLATION SE
TROUVENT DANS LE MANUEL D'INSTALLATION.
WHD31N CWHD31N CWHD31P WHD31P
NATURAL GAS MODEL PROPANE MODEL
0-4500ft ALTITUDE / ELEVATION 0-4500ft
20,000 BTU/hr INPUT / ALIMENTATION 16,000BTU/hr
65.2% P4 63.7%
MANIFOLD PRESSURE: 3.5 INCHES W.C. (NG)
PRESSION AU COLLECTEUR: 3.5” D’UNE
COLONNE D’EAU(GN)
MIN SUPPLY PRESSURE: 4.5” W.C.(NG)
PRESSION D’ALIMENTATION MIN: 4.5” D’UNE
COLONNE D’EAU (GN)
MAX. SUPPLY PRESSURE: 7” W.C. (NG)
PRESSION D’ALIMENTATION MAX: 7” D’UNE
COLONNE D’EAU (GN)
MANIFOLD PRESSURE: 10 INCHES W.C.(LP)
PRESSION AU COLLECTEUR: 10” D’UNE
COLONNE D’EAU (PL)
MIN SUPPLY PRESSURE: 11” W.C. (LP)
PRESSION D’ALIMENTATION MIN: 11” D’UNE
COLONNE D’EAU (PL)
MAX. SUPPLY PRESSURE: 13” W.C. (LP)
PRESSION D’ALIMENTATION MAX: 13” D’UNE
COLONNE D’EAU (PL)
NOT FOR USE WITH SOLID FUEL/ UN COMBUSTIBLE SOLIDE NE DOIT
PAS ETRE UTILSE AVEC CET APPAREIL
CAUTION: FOR USE WITH GLASS DOORS
CERTIFIED WITH THIS UNIT ONLY.
WARNING: DO NOT ADD ANY MATERIAL TO
THE APPLIANCE, WHICH WILLCOME IN
CONTACT WITH THE FLAMES, OTHER THAN
THAT SUPPLIED BY THE MANUFACTURER
WITH THE APPLIANCE.
THIS VENTED GAS FIREPLACE IS NOT FOR
USE WITH AIR FILTERS.
DECORATIVE PRODUCT: NOT FOR USE AS A
HEATING APPLIANCE
ELECTRICAL RATING: 115V.60HZ. LESS
THAN 12 AMPERES
THE APPLIANCE MUSTBE VENTED USING
THE APPROPRIATE WOLF STEEL VENT KITS.
SEE OWNERS INSTALLATION MANUALFOR
VENTING SPECIFICS.
MINIMUM CLEARANCE TO COMBUSTIBLE
MATERIAL:
MANTEL 11 FLOOR 0”
SIDES 7” VENT TOP 2”
VENT SIDES/BOTTOM 1”
ATTENTION: UTILISER AVEC LES PORTES
VITREES HOMOLOGUEES SEULEMENTAVEC
CETTE UNITE.
AVERTISSEMENT: N’AJOUTEZ PAS A CET
APPAREILAUCUN MATERIAU DEVANT ENTRER EN
CONTACT AVEC LES FLAMMES AUTRE QUE
CELUI QUI EST FOURNIAVEC CETAPPAREILPAR
LE FABRICANT.
CE FOYER À GAZ VENTILÉS NE DOIT PAS ÊTRE
UTILISÉ CONJOINTEMENTAVEC DES FILTRES À
AIR.
PRODUIT DÉCORATIF: NE PAS UTILISER COMME
APPAREIL DE CHAUFFAGE
SPÉCIFICATIONS ÉLECTRIQUES : 115 V,
60 HZ. MOINS DE 12 AMPÈRES.
L’APPAREIL DOIT EVACUER SES GAZ EN
UTILISANT L’ENSEMBLE D’EVACUATION PROPRE
A WOLF STEEL. REFERERAU MANUEL
D’INSTALLATION DE PROPRIETAIRE POUR
L’EVACUATION PRECISE.
DEGAGEMENTS MINIMAUX DES MATERIAUX
COMBUSTIBLES:
MANTEAU 11” PLANCHER 0”
COTES 7” EVENT SUPERIEUR 2”
COTES DE L’EVENT/ EVENT INFERIEUR 1
”
SERIAL NUMBER
/ NO. DE SERIE
WHD31
W385-1968
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
9700539 (WSL) 4001657 (NGZ)
4001658 (NAC) 4001659 (WUSA)
TIVE AU CRITERE DE MESURES DE
CURITE CONTRE L’INCENDIE POUR LES
NSTALLATIONS DANS LES MAISONS
MANUFACTURES, LES SITES ETLES
COMMUNAUTES, ANSI/NFPA 501A.
UTILISER AVEC BARRIÈRE W565-0121.
RESSURE: 3.5 INCHES W.C. (NG)
AU COLLECTEUR: 3.5” D’UNE
SSION D’ALIMENTATION MIN: 4.5” D’UNE
MAX. SUPPLY PRESSURE: 7” W.C. (
PRESSION D’ALIMENTATION MAX: 7” D