84. "AO2 OAT low TEMP"
Default:
Range:
Increment:
-400 C
-400 C to 1250 C
0.10 C
[-104ºF]
[-104ºF to 257ºF]
[33.8ºF]
Set the desired heating outside air low-temperature limit for the analog input 1. The minimum value is restricted by the value set at
Step 82, "AO2 OAT HI TEMP". If the temperature read from the Outside Air Temperature sensor connected to AI1 is higher than
the value set here, the AO1 output will no longer modulate and remain at its minimum voltage (default 0Vdc).
85. "BO1 OAT HI TEMP"
Default:
Range:
Increment:
[122ºF]
[104ºF to 257ºF]
[33.8ºF]
Set the desired heating outside air high-temperature limit for the binary output 1. This setpoint appears when 'OAT' is selected in
the Step 77, "AI1 mode". If the temperature read from the Outside Air Temperature sensor connected to AI1 is higher than the
value set here, the AO1 output will no longer modulate and remain at its minimum voltage (default 0Vdc).
86. "BO1 OAT low TEMP"
Default:
Range:
Increment:
-400 C
-400 C to 1250 C
0.10 C
[-104ºF]
[-104ºF to 257ºF]
[33.8ºF]
Set the desired heating outside air low-temperature limit for the binary output 1. The minimum value is restricted by the value set at
Step 86, "BO1 OAT HI TEMP". If the temperature read from the Outside Air Temperature sensor connected to AI1 is higher than
the value set here, the AO1 output will no longer modulate and remain at its minimum voltage (default 0Vdc).
87. "BO2 OAT HI TEMP"
Default:
Range:
Increment:
[122ºF]
[104ºF to 257ºF]
[33.8ºF]
Set the desired heating outside air high-temperature limit for the binary output 2. This setpoint appears when 'OAT' is selected in
the Step 77, "AI1 mode". If the temperature read from the Outside Air Temperature sensor connected to AI1 is higher than the
value set here, the AO1 output will no longer modulate and remain at its minimum voltage (default 0Vdc).
88. "BO2 OAT low TEMP"
Default:
Range:
Increment:
-400 C
-400 C to 1250 C
0.10 C
[-104ºF]
[-104ºF to 257ºF]
[33.8ºF]
Set the desired heating outside air low-temperature limit for the binary output 2. This setpoint appears when 'OAT' is selected in
the Step 77, "AI1 mode". If the temperature read from the Outside Air Temperature sensor connected to AI1 is higher than the
value set here, the AO1 output will no longer modulate and remain at its minimum voltage (default 0Vdc).
89. “unocc cool setpnt min”
Default:
Range:
Increment:
[50ºF]
[32ºF to 50ºF]
[33.8ºF]
Set the minimum cooling setpoint when the zone is in unoccupied mode. This setpoint appears when 'Occupancy' is selected in the
Step 77, "AI1 mode" and Step 78, "BI1 mode". The minimum value is restricted by the maximum value set at Step 89, "“unocc cool
setpnt". In other words, the value that is set as the minimum cannot be greater than the maximum value.
90. “unocc cool setpnt mAX”
Default:
Range:
Increment:
[104ºF]
[50ºF to 257ºF]
[33.8ºF]
Set the maximum cooling setpoint when the zone is in unoccupied mode. This setpoint appears when 'Occupancy' is selected in
the Step 77, "AI1 mode" and Step 78, "BI1 mode". The maximum value is restricted by the minimum value set at Step 88, “unocc
cool setpnt. In other words, the value that is set as the maximum cannot be less than the minimum value.