TFHB24F3XYZ1 Specification & Installation Instructions
2
Mounting Instructions
A
E
D
C
B
CAUTION: Risk of malfunction. Remove power prior to separate thermostat cover from its base.
A. Remove the screw (captive) holding the base and the front cover of the thermostat.
B. Lift the front cover of the thermostat to separate it from the base.
C. Pull wire through the base hole.
D. Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections.
E. Mount the control module on the base and secure using the screw.
Terminal Description
2 Pipe Analog On/Off Floating
erminals Fan option analog 1 spd 2 spd 3 spd analog 1 spd 2 spd 3 spd analog 1 spd 2spd 3spd
TB1
1Common Common Common Common
224 Vac 24 Vac 24 Vac 24 Vac
3Common Triac Common Triac Common Triac Common Triac
4Triac output 1 (TO1) Floating
output 1
- 2 Pipe on/off 2 Pipe floating (close)
5Triac output 2 (TO2) - - 2 Pipe floating (open)
6Triac output 3 (TO3) Reheat Local reheat (optional) (on/off or pulse) Local reheat (optional) (on/off or pulse) Local reheat (optional) (on/off or pulse)
7Common Relay - Common Relay - Common Relay - Common Relay
8Digital output 1 (DO1) - - - High - - - High - - - High
9Digital output 2 (DO2) - - High Med - - High Med - - High Med
10 Digital output 3 (DO3) /
Analog Fan Speed (AO4) Fan analog 1 spd Low Low Fan analog 1 spd Low Low Fan analog 1 spd Low Low
11 Occupancy Sensor (DI1) Occupancy Sensor (optional) Occupancy Sensor (optional) Occupancy Sensor (optional)
12 External Humidity Sensor (AI1) External Humidity Sensor (optional) External Humidity Sensor (optional) External Humidity Sensor (optional)
13 External Changeover (AI2) External Changeover External Changeover External Changeover
14 Analog output 1 (AO1) 2 Pipe analog - -
15 Analog output 2 (AO2) - - -
16 Analog output 3 (AO3) Reheat Local reheat analog (optional) Local reheat analog (optional) Local reheat analog (optional)
17 A+ Communication
port RS-485 BACnet BACnet BACnet
18 B-
4 Pipe Cool & Heat Analog Cool & Heat On/Off Cool Analog-Heat On/Off or pulse Cool On/Off - Heat Analog
erminals Fan option analog 1 spd 2 spd 3 spd analog 1 spd 2 spd 3 spd analog 1 spd 2 spd 3 spd analog 1 spd 2 spd 3 spd
TB1
1Common Common Common Common Common
224 Vac 24 Vac 24 Vac 24 Vac 24 Vc
3Common Triac Common Triac Common Triac Common Triac Common Triac
4Triac output 1 (TO1) Floating
output 1
- 4 Pipe on/off cool - 4 Pipe on/off cool
5Triac output 2 (TO2) - 4 Pipe (on/off or pulse) heat 4 Pipe (on/off or pulse) heat -
6Triac output 3 (TO3) Reheat Local reheat (optional)(on/off or pulse) Local reheat (optional)(on/off or pulse) Local reheat (optional)(on/off or pulse) Local reheat (optional)(on/off or pulse)
7Common Relay - Common Relay - Common Relay - Common Relay - Common Relay
8Digital output 1 (DO1) - - - High
- -
- High
- -
- High
- -
- High
9Digital output 2 (DO2) - - High Med - -
High Med - -
High Med
- -
High Med
10 Digital output 3 (DO3) /
Analog Fan Speed (AO4) Fan analog 1 spd Low Low Fan analog 1 spd Low Low Fan analog 1 spd Low Low
Fan analog 1 spd Low Low
11 Occupancy Sensor (DI1) Occupancy Sensor (optional) Occupancy Sensor (optional) Occupancy Sensor (optional) Occupancy Sensor (optional)
12 Ext. Humidity Sensor (AI1) Ext. Humidity Sensor (optional) Ext. Humidity Sensor (optional) Ext. Humidity Sensor (optional) Ext. Humidity Sensor (optional)
13 External Changeover (AI2) - - - -
14 Analog output 1 (AO1) 4 Pipe analog cool - 4 Pipe analog cool -
15 Analog output 2 (AO2) 4 Pipe analog heat - - 4 Pipe analog heat
16 Analog output 3 (AO3) Reheat Local reheat analog (optional) Local reheat analog (optional) Local reheat analog (optional) Local reheat analog (optional)
17 A+ Communication
port RS-485 BACnet BACnet BACnet BACnet
18 B-
Settings on PC Board
Connecting
strip TB1
Temperature
sensor
TB1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Mode selector
JP3
PGM RUN
Dip
switch
ON
1 2 3
Triac output
signal selector
JP1
JP4
Fan output signal
selector
JP2
Digital output
signal selector
Triac Output Signal Selection (JP1) Mode Selection (JP3)
Jumper (JP1) on top: All triac output
signal is linked to internal 24Vac.
(Same 24Vac than thermostat) PGM
RUN
JP3 Jumper (JP3) on RUN:
Thermostat is in operation mode.
Thermostat must be set in this mode to operate properly.
If not locked, set point, control mode and speed fan
(Heating & Cooling ON, Cooling only ON or Heating only
ON) may be modified by end user.
Jumper (JP1) on bottom: All triac output
signal is linked to external 24Vac.
(Different 24Vac than thermostat)
Digital Output Signal Selection (JP2)
24VAC
Jumper (JP2) on left: All digital output
signal is linked to internal 24Vac.
(Same 24Vac than thermostat)
PGM
RUN
JP3 Jumper (JP3) on PGM:
Thermostat is set in Programming mode.
Refer to following section about all settings description
Jumper (JP2) on right: All digital output
signal is linked to external 24Vac.
(Different 24Vac than thermostat)
Fan Output Signal Selection (JP4) Bacnet dip switch (DS1) - Optional
AO4
DO3
JP4 Jumper (JP4) on top:
Pin 10 of TB1 is set to be digital output
signal (DO3).
ON
1 2 3
Pull up
120 ohm termination (Last node)
Pull down
AO4
DO3
JP4 Jumper (JP4) on bottom:
Pin 10 of TB1 is set to be analog output
signal (AO4).
24VAC EXT.
EXT.
24VAC
24VAC