Networkable Fan Coil Controller
Specification and Installation Instructions
www.neptronic.com EFCB Series Page | 13
Operation Menus
This menu is accessible through normal operation mode.
1. The Mode Selector jumper (JP1) of the thermostat must be set to the “RUN” position (Operation Mode). Refer to Wiring on
page 4.
2. Press the and buttons simultaneously for 5 seconds. “PAS” appears on the screen.
3. Enter the password within 1 minute by using the arrow keys to increase or decrease the value and the and buttons
to toggle between the digits.
a. Password 372 = Sensor Offset Menu
b. Password 637 = Network Settings Menu
4. If you enter the wrong password, the thermostat displays “Err” and returns to Operation Mode. The thermostat will return to
normal mode if you navigate through the entire menu and do not make any selection, or if you do not press any key for 5
minutes. The changed values will be saved automatically.
Menu 372 – Sensor Offset
Menu 637 – Network Settings
Reset to Factory Default Settings
This will erase all actual configurations and replace them with the factory default settings.
1. The Mode Selector jumper (JP1) of the thermostat must be set to the “RUN” position (Operation Mode). Refer to Wiring on
page 4.
2. During the power up sequence of the controller and thermostat (when the firmware versions are displayed), press and hold
both the and buttons.
3. The “Enter Password” screen appears. Enter 372 within 1 minute by using the arrow keys to increase or decrease the value and
the and buttons to toggle between the digits.
4. Use the arrow buttons to select YES and then press .
HS2 (Extn humdity sensor offset)
End (exit menu)
HS1 (Intr humdity sensor offset)
EtS (external temp sensor)
Sensor Offset setting
ItS (internal temp sensor)
= scroll menu items
Exit menu and return to normal operation
tS1 (Intern Temp Sensor Offset)
Actual°C/°F(± 5°C/9°F) AV.5
EtS (Extern Temp Sensor Offset)
Actual°C/°F(± 5°C/9°F) AV.6
Go to
"EtS"
Go to
"HS1"
HS1 (Intr humdity sensor offset)
Actual%RH(± 5%)AV.71
Go to
"HS2"
HS2 (Extn humdity sensor offset)
Actual%RH (± 5%)AV.72
Go to
"End"
*** You must press the button to save any changes ***
*** Pressing the button returns to the previous step without saving ***
Go to "BACnet Auto Baud Rate"
Go to "Modbus Auto Baud Rate"
Returns to
run mode
CPy(copy configuration)
bAC
Md
Network Config
tYP NEt (Type)
= scroll menu items
Network Choice
bAC (BACnet)
mOd (Modbus)
= select / set value
Abr (Modbus auto baud rate)
NO(Manual)
YEs (Automatic)
= select / set value
Abr (BACnetauto baud rate)
NO(Manual)
YEs (Automatic)
= select / set value
= select / set value
Add (Start address)
0(0-254)
If type = bAC, menu contains
"tYpe", "bAC" and "CPY"
If type = mOd, menu contains
"tYpe" and "mOd"bAu (Modbus baud rate)
57.6k(9.6k, 19.2k, 38.4, 57.6k)
bAu (BACnetbaud rate)
76.8k(9.6k, 19.2k, 38.4, 76.8k)
Add (MSTP MAC address)
0(0-254)
Modifiable only if Auto Baud Rate
set to "No".
Modifiable only if Auto Baud Rate
set to "No".
Modifiable only if all DS2 DIP
switches are set to OFF.
Go to
"CPy"
MSTP MAX master
127 (1-127)
OP1 (odd parity, 1 stop bit)
CF9 (Modbus comport config)
NP2 (no parity, 2 stop bits)
EP1 (even parity, 1 stop bit)
MA (Modbus address)
1(1 -2 46)
Modifiable only if all DS2 DIP
switches are set to OFF.
Go to "HrS"
Add (End address)
0(0-254, start address+63)
CPy (Confirm copy onfig)
NO (cancel)
YES(confirm)
Copy configuration
in(in progress)
Go to "HrS"
Copy config succeeded
SCd(done)
1001 1000
AV.165 AV.166 BV.90
AV.167
End (exit menu)
Exit menu and return
to normal operation
*** You must press the button to save any changes***
*** Pressing the button returns to the previous step without saving***