TFxB Series Thermostat Controller
Page | 7
Objects Table
The TFxB24 Thermostat series of controllers use the following BACnet®object table. The type is the BACnet®
Object type, the instance is the BACnet®Object. Together the type and instance form the BACnet®
Object_Identifier for an object according to the following C-language algorithm:
object_identifier=(unsigned long)((unsigned long)type<<22)+instance
ID8Name Writable
Property
TFCB24F3XYZ1
TFCB24F3XY2
TFHB24F3XYZ1
TFHB24F3XYZ2
TFCB24P3-OE1
TFHB24P3-OE1
TFHB24P3-OE2
Notes
AI.1 Intern.Temper. Out of service xxxx xxx
0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF
AI.2 Extern.Temper. Out of service xx x xxx
0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF
AI.3 ChangeOverTemper. Out of service xxxx xxx
0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF
AI.4 Intern.Humidity Out of service x x
5-95%RH, Resolution 0.1%RH
AI.9 Extern.Humidity Out of service x x
5-95%RH, Resolution 0.1%RH
AV.1 ControlTemper. Out of service xxxx xxx
0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF
AV.2 HeatingDemand Out of service xxxx xxx
0-100%, Resolution 0.1%
AV.3 CoolingDemand Out of service xxxx xxx
0-100%, Resolution 0.1%
AV.4 FanDemand Out of service xxxx xxx
0-100%, Resolution 0.1%
AV.5 Intern.Temper.Offset Present Value
xxxx xxx
± 5.0ºC, Resolution 0.1ºC
AV.6 Extern.Temper.Offset Present Value xx x xxx
± 5.0ºC, Resolution 0.1ºC
AV.7 Temper.SetPointOcc. Present Value xxxx xxx
AV.8 to AV.9, Resolution 0.5ºC/1ºF
AV.8 Min.SetPointOcc. Present Value xxxx xxx
0 to AV.9, Resolution 0.5ºC/1ºF
AV.9 Max.SetPointOcc. Present Value xxxx xxx
AV.8 to 40ºC or 104ºF, Resolution 0.5ºC/1ºF
AV.10 Temper.SetPointCoolNoOcc. Present Value xxxx xxx
AV.11 to 40ºC or 104ºF, Resolution 0.5ºC/1ºF
AV.11 Temper.SetPointHeatNoOcc. Present Value xxxx xxx
10.0ºC or 50ºF to AV.10, Resolution 0.5ºC/1ºF
AV.12 CoolingProp.Band Present Value xxxx xxx
0.5-5ºCor 1-10ºF, Resolution 0.5ºC/1ºF
AV.13 HeatingProp.Band Present Value xxxx xxx
0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF
AV.14 CoolingDeadBand Present Value xxxx xxx
0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF
AV.15 HeatingDeadBand Present Value xxxx xxx0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF
AV.16 FanTimeOutDelay Present Value xxxx xxx
0-15 minutes, Resolution 1 minute
AV.17 Heat/CoolVoltageMin.2pipes Present Value xxxx xxx
0 Volt to AV.20, Resolution 0.1 Volt
AV.18 CoolingVoltageMin.4pipes Present Value xxxx xxx
0 Volt to AV.21, Resolution 0.1 Volt
AV.19 HeatingVoltageMin.4pipes
For TFHB24P3-OE1 and TFHB24P3-OE2
Heating4PipesOrHumid.Volt.Min. Present Value xxxx xxx
0 Volt to AV.22, Resolution 0.1 Volt
AV.20 Heat/CoolVoltageMax.2pipes Present Value xxxx xxxAV.17 to 10.0 Volt, Resolution 0.1 Volt
AV.21 CoolingVoltageMax.4pipes Present Value xxxx xxx
AV.18 to 10.0 Volt, Resolution 0.1 Volt
AV.22 HeatingVoltageMax.4pipes
For TFHB24P3-OE1 and TFHB24P3-OE2
Heating4PipesOrHumid.Volt.Max. Present Value xxxx xxx
AV.19 to 10.0 Volt, Resolution 0.1 Volt
AV.23 ChangeOverSetPoint Present Value xxxx xxx
10-40ºC or 50-104ºF, Resolution 0.5ºC/1ºF
AV.25 FanDampingFactor Present Value xxxx xxx
0-10 seconds, Resolution 1 second
AV.26 Int.TimeFactor Present Value xxxx xxx
0-250 seconds, Resolution 5 seconds
AV.27 CoolingAntiCycleDelay Present Value xxxx xxx
0-15 minutes, Resolution 1 minute
AV.28 Loc.Heat.Demand Out of service xxxxxx
0-100%, Resolution 0.1%
AV.29 Loc.Heat.Prop.Band Present Value x xx xxx
0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF
AV.30 Loc.Heat.DeadBand Present Value xxxxxx
0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF
AV.31 FloatingMotorTiming Present Value x xx xxx
15-250 seconds, resolution 5 seconds
AV.32 Loc.Heat.VoltageMin. Present Value xxxxxx
0 Volt to AV.33, Resolution 0.1 Volt
AV.33 Loc.Heat.VoltageMax. Present Value x xx xxx
AV.32 to 10.0 Volt, Resolution 0.1 Volt
AV.34 FanVoltageMin. Present Value x xx xxx
0 Volt to AV.35, Resolution 0.1 Volt
AV.35 FanVoltageMax. Present Value x xx xxxAV.34 to 10.0 Volt, Resolution 0.1 Volt
AV.36 Dehumid.Demand Out of service xx xx
0-100%, Resolution 0.1%
AV.37 HumiditySetPoint Present Value
xx xx
10.0-65.0%RH, Resolution 0.5%RH
AV.38 Intern.HumidityOffset Present Value
x x
± 5.0%RH, Resolution 0.1%RH
AV.39 NoOcc.OverrideDelay Present Value xxxx xxx
0-180 minutes, Resolution 15 minutes
AV.40 HumidityControlRamp Present Value
xx xx
3.0-10.0%RH, Resolution 0.5%RH
AV.41 Humidif.Demand Out of service xx
0-100%, Resolution 0.1%
AV.42 CoolingDemand2 Out of service xxx
0-100%, Resolution 0.1%
AV.43 CoolingProp.Band2 Present Value xxx
0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF
AV.44 CoolingDeadBand2 Present Value xxx
0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF
AV.45 Extern.HumidityOffset Present Value
x x
± 5.0%RH, Resolution 0.1%RH
8ID is equal to ObjectType.Instance