TFCB24F3XYZ1 Specification & Installation Instructions
2
Mounting Instructions
A
E
D
C
B
CAUTION: Risk of malfunction. Remove power prior to separate thermostat cover from its base.
A. Remove the screw (captive) holding the base and the front cover of the thermostat.
B. Lift the front cover of the thermostat to separate it from the base.
C. Pull wire through the base hole.
D. Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections.
E. Mount the control module on the base and secure using the screw.
Terminal Description
2 Pipe Analog On/Off Floating
erminals Fan option analog 1 spd 2spd 3spd analog 1 spd 2spd 3 spd analog 1 spd 2spd 3spd
TB1
1 Common Common Common Common
2 24 Vac 24Vac 24Vac 24Vac
3 Common Triac Common Triac Common Triac Common Triac
4 Triac output 1 (TO1) Floating
output 1
- 2 Pipe on/off 2 Pipe floating (close)
5 Triac output 2 (TO2) - - 2 Pipe floating (open)
6 Triac output 3 (TO3) Reheat Local reheat (optional) (on/off or pulse) Local reheat (optional) (on/off or pulse) Local reheat (optional) (on/off or pulse)
7 Common Relay - Common Relay - Common Relay - Common Relay
8 Digital output 1 (DO1) - - - High - - - High - - - High
9 Digital output 2 (DO2) - - High Med - - High Med - - High Med
10 Digital output 3 (DO3) /
Analog Fan Speed (AO4) Fan analog 1 spd Low Low Fan analog 1 spd Low Low Fan analog 1 spd Low Low
11 Occupancy Sensor (DI1) Occupancy Sensor (optional) Occupancy Sensor (optional) Occupancy Sensor (optional)
12 External Temp. Sensor (AI1) External Temp. Sensor (optional) External Temp. Sensor (optional) External Temp. Sensor (optional)
13 External Changeover (AI2) External Changeover External Changeover External Changeover
14 Analog output 1 (AO1) 2 Pipe analog - -
15 Analog output 2 (AO2) - - -
16 Analog output 3 (AO3) Reheat Local reheat analog (optional) Local reheat analog (optional) Local reheat analog (optional)
17 A+ Communication
port RS-485 BACnet BACnet BACnet
18 B-
4 Pipe Cool & Heat Analog Cool & Heat On/Off Cool Analog-Heat On/Off or pulse Cool On/Off - Heat Analog
erminals Fan option analog 1 spd 2 spd 3spd analog 1 spd 2spd3spd analog 1 spd 2spd 3 spd analog 1 spd 2spd3spd
TB1
1 Common Common Common Common Common
2 24 Vac 24Vac 24Vac 24Vac 24Vac
3 Common Triac Common Triac Common Triac Common Triac Common Triac
4 Triac output 1 (TO1) Floating
output 1
- 4 Pipe on/off cool - 4 Pipe on/off cool
5 Triac output 2 (TO2) - 4 Pipe (on/off or pulse) heat 4 Pipe (on/off or pulse) heat -
6 Triac output 3 (TO3) Reheat Local reheat (optional) (on/off or pulse) Local reheat (optional) (on/off or pulse) Local reheat (optional) (on/off or pulse) Local reheat (optional) (on/off or pulse)
7 Common Relay - Common Relay - Common Relay - Common Relay - Common Relay
8 Digital output 1 (DO1) - - - High
- -
- High
- -
- High
- -
- High
9 Digital output 2 (DO2) - - High Med - -
High Med - -
High Med
- -
High Med
10 Digital output 3 (DO3) /
Analog Fan Speed (AO4) Fan analog 1 spd Low Low Fan analog 1 spd Low Low Fan analog 1 spd Low Low
Fan analog 1 spd Low Low
11 Occupancy Sensor (DI1) Occupancy Sensor (optional) Occupancy Sensor (optional) Occupancy Sensor (optional) Occupancy Sensor (optional)
12 Ext. Temp Sensor (AI1) External Temp. Sensor (optional) External Temp. Sensor (optional) External Temp. Sensor (optional) External Temp. Sensor (optional)
13 External Changeover (AI2) - - - -
14 Analog output 1 (AO1) 4 Pipe analog cool - 4 Pipe analog cool -
15 Analog output 2 (AO2) 4 Pipe analog heat - - 4 Pipe analog heat
16 Analog output 3 (AO3) Reheat Local reheat analog (optional) Local reheat analog (optional) Local reheat analog (optional) Local reheat analog (optional)
17 A+ Communication
port RS-485 BACnet BACnet BACnet BACnet
18 B-
Settings on PC Board
Connecting
strip TB1
Temperature
sensor
TB1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Mode selector
JP3
PGM RUN
Dip
switch
ON
1 2 3
Triac output
signal selector
JP1
JP4
Fan output signal
selector
JP2
Digital output
signal selector
Triac Output Signal Selection (JP1) Mode Selection (JP3)
COM
24VAC
JP1 Jumper (JP1) on 24Vac:
All triac output signal is linked to 24 Vac.
PGM
RUN
JP3
Jumper (JP3) on RUN:
Thermostat is in Operation Mode.
Thermostat must be set in this mode to operate properly.
If not locked, set point, control mode and speed fan
(Heating & Cooling ON, Cooling only ON or Heating only
ON) may be modified by end user.
COM
24VAC
JP1 Jumper (JP1) on COMMON TRIAC:
All triac output signals are linked to common
triac.
Digital Output Signal Selection (JP2)
24VAC
JP2
Jumper (JP2) on 24Vac:
All digital output signal is linked to 24 Vac.
PGM
RUN
JP3 Jumper (JP3) on PGM:
Thermostat is set in Programming Mode.
Refer to following section about all settings description
JP2
COM
Jumper (JP2) on COMMON RELAY:
All digital output signals are linked to
common relay.
Fan Output Signal Selection (JP4) BACnet Dip Switch (DS1) - Optional
AO4
DO3
JP4
Jumper (JP4) on top:
Pin 10 of TB1 is set to be digital output
signal (DO3).
ON
1 2 3
Pull up
120 ohm termination (Last node)
Pull down
AO4
DO3
JP4
Jumper (JP4) on bottom:
Pin 10 of TB1 is set to be analog output
signal (AO4).