NIPPON VALVE CONTROLS SP-1491 User manual

OSCZX22A-EN
1/13
Instruction manual
Electric Actuated Butterfly Valve Z
SP-1491
Please read this manual before installation and use.
GENERAL
Light weight, low price and economical butterfly valve.
This type designed for 3-piece structure and it is easy to maintenance.
Actuator
AM : For AC power.
AH1 : For AC power. (High speed)
DM : For DC power.
PAX : Proportional control.
ACR : Emergency Shut Off.
Valve
Z type It is small, light weight and economical butterfly valve.
This type designed for 3 piece structure and it is easy
to maintenance.
Threaded End Rc Socket End
PRODUCT CODE
Z type Threaded End Rc Z - 5 T U - - -
Z type Socket End (PVC) Z - 7 T P - - -
(C-PVC) Z - 7 T H - - -
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11)
(1) Actuator
AM1 AM2 AH1
DM0 DM2 PAX ACR
(2)
Valve
Z-
(3)
Voltage
1 : 100 / 110 V AC
2 : 200 / 220 V AC
2 : 100 to 220 V AC (ACR)
0 : 24V DC
(4) Sizing code
0 : Standard
1 : Light
2 : Heavy
(5) Connection
5 : Threaded End Rc
7 : Socket End
(6) Body material
T : SCS13A
(7) Cap / Socket material
U : SCS14A
P : PVC
H : C-PVC
(8) Seat material
E : EPDM
B : NBR
V
: FKM
(9) Size [mm]
ex. 25 A ® 025
(10) Option
AK : Aluminum alloy
motor cover
M1 : Manual lever
C1 : Flexible cable
(11) Operation mode (PAX)
Nil : Mode A
J : Mode B

OSCZX22A-EN
2/13
VALVES SPECIFICATIONS
Water Oil Air, Gas Steam Chemicals Sea water Slurry Negative pressure
Valve type Z
Design 3 piece structure
Connection Threaded End Rc Socket End
Fluid
Max pressure 1 MPa
Size [mm] 015 to 050
Material Body SCS13A
Disc PPS
Cap SCS14A -
Socket - PVC C-PVC
Seat EPDM NBR FKM
Stem seal O-ring Depend on seat material
SEAT MATERIAL GUIDE
Seat material Fluid temp. Use
EPDM -20 to +80 °C
NBR -10 to +60 °C
FKM -0 to +90 °C
Note) • EPDM seat cannot be used for oil.
• Unsuitable for steam or hot water over 80 °C.
• Can flow the seawater with PVC socket and
EPDM sheet.
PRESSURE & TEMPERATURE RATING
Valve seat Cap / Socket
INHERENT FLOW CHARACTERISTIC
Cv
value
(%)
Valve opening
(%)
Range ability 30:1

OSCZX22A-EN
3/13
ELECTRIC ACTUATOR SPECIFICATIONS
AM1 AM2 type
Actuator type
(:Voltage code) AM1-030- AM1-070- AM1-180- AM2-030- AM2-070- AM2-180-
Voltage 100 / 110 V AC ±10 % 50/60 Hz (Voltage code: 1)
200 / 220 V AC ±10 % 50/60 Hz (Voltage code: 2)
Rated torque [Nm] 3 7 18 3 7 18
Operation time [s] 5.4 / 4.5
(50/60 Hz)
15.5 / 13
(50/60 Hz)
16 / 13.5
(50/60 Hz)
5.4 / 4.5
(50/60 Hz)
15.5 / 13
(50/60 Hz)
16 / 13.5
(50/60 Hz)
Power consumption [VA] 16 19 18 19
Motor Synchronous motor
Overload protection Thermal protector
Method of operation Transfer input type a-contactinput type, with built-in relay
Operation Power to S ® SHUT (SHUT PL is lit.)
Power to O ® OPEN (OPEN PL is lit.)
SW is OFF ® SHUT (SHUT signal is output.)
SW is ON ® OPEN (OPEN signal is output.)
Input signal current Nil 9 mA (O-terminal)
Leakage current in SW: less than 1 mA
Output signal rating Resistance load 3 A 250 V AC
(Minimum 0.1 A)
Resistance load 0.5 A 125 V AC
2 A 30 V DC
Micro load 1 mA 5 V DC
Duty cycle 20 % 15 min.
Ambient temperature -20 to 55 ºC
Space heater 1 W
Manual operation Direct operation of actuator by loosening lock screw
Enclosure Equivalent to IP65 (IEC 60529)
Housing material Aluminum alloy die cast + Polycarbonate resin cover
Terminal block For bare wire 0.14 to 1.5 mm² (AWG 26 to 14) Ground terminal: M4
Conduct port G3/8 Cable gland (for 5 to 10.5 mm cable)
WIRING
AM1 AM2
• Control switch should be prepared one by one for
actuator. Do not operate two or more actuator from
one switch. It might malfunction.
• Two or more actuators can be operated with one
control switch.
• When using control switch with current leakage
(more than 1 mA) such as TRIAC or relay with CR,
it can cause malfunction.
Voltage
100/110V AC
200/220V AC
TP
SH
SHUT PL
OPEN PL
Ground terminal(M4)
S.LS
O.LS
TP
SHUT signal
OPEN signal
S.LS
O.LS
Motor
control
Space
heater
circuit
Voltage
100/110V AC
200/220V AC
Ground terminal(M4)

OSCZX22A-EN
4/13
ELECTRIC ACTUATOR SPECIFICATIONS
AH1 type
Actuator type ( :Voltage code) AH1-030- AH1-070- AH1-180-
Voltage 100 / 110 V AC ±10 % 50/60 Hz (Code: 1)
200 / 220 V AC ±10 % 50/60 Hz (Code: 2)
Rated torque [Nm] 3 7 18
Operation time [s] 3 / 2.5 (50/60 Hz) 6 / 5 (50/60 Hz)
Power consumption [VA] 19 50
Motor Synchronous motor Reversible motor
Overload protection Thermal protector
Method of operation Transfer input type
Operation Power to S ® SHUT (SHUT PL is lit.)
Power to O ® OPEN (OPEN PL is lit.)
Output signal rating Resistance load 3 A 250 V AC (Minimum 0.1 A)
Duty cycle 20 % 15 min.
Ambient temperature -20 to 55 ºC
Space heater 0.5 W 1 W
Manual operation Direct operation of output shaft
Enclosure Equivalent to IP65 (IEC 60529)
Housing material Aluminum alloy die cast + Polycarbonate resin cover
Terminal block For bare wire 0.14 to 1.5 mm² (AWG 26 to 14) Ground terminal: M4
Conduct port G3/8 Cable gland (for 5 to 10.5 mm cable)
WIRING
Note) Control switch should be prepared one by one for actuator.
Do not operate two or more actuator from one switch. It might malfunction.
TP
SH
S.LS
O.LS
Voltage
100/110V AC
200/220V AC
SHUT PL
OPEN PL
Ground terminal(M4)

OSCZX22A-EN
5/13
ELECTRIC ACTUATOR SPECIFICATIONS
DM0 DM2 type
Actuator type DM0-030-0 DM0-070-0 DM0-180-0 DM2-030-0 DM2-070-0 DM2-180-0
Voltage 24 V DC
Rated torque [Nm] 3 7 18 3 7 18
Operation time [s] 0.8 to 1.5 2 to 3 4 to 6 2 to 3.5 2 to 3 4 to 6
Power consumption (Max)
[VA] 24 10 24
Motor DC motor
Overload protection Thermistor
Method of operation Switching polarity type a-contactinput type, with built-in relay
Operation
2
+
3
- ® SHUT (SHUT PL is lit.)
3
+
2
- ® OPEN (OPEN PL is lit.)
SW is OFF ® SHUT (SHUT PL is lit.)
SW is ON ® OPEN (OPEN PL is lit.)
Input signal current Nil 16.2 mA (O-terminal)
Output signal rating Resistance load 2 A 30 V DC Resistance load : Less than 1 A 24 V DC
Micro load 1 mA 5 V DC
Duty cycle 20 % 15 min.
Ambient temperature -20 to 55 ºC
Space heater 1 W
Manual operation Direct operation of output shaft
Enclosure Equivalent to IP65 (IEC 60529)
Housing material Aluminum alloy die cast + Polycarbonate resin cover
Terminal block For bare wire 0.14 to 1.5 mm² (AWG 26 to 16)
Conduct port G3/8 Cable gland (for 5 to 10.5 mm cable)
WIRING
DM0 DM2
Voltage
24V DC
SHUT PL
OPEN PL
Motor control
circuit
PTC
PTC
RY
RY
S.LS
O.LS
Voltage
24V DC
SHUT PL
OPEN PL

OSCZX22A-EN
6/13
ELECTRIC ACTUATOR SPECIFICATIONS
OPTIONAL PARTS
Specifications Code No. AM AH1 DM Remarks
Aluminum alloy motor cover AK
Manual lever M1 Detachable lever
Flexible cable (Approx. 300 mm long) C1
DIMENSIONS
AM (030 / 070) DM2 (030) DM0
(030)
DM
(070)
AH1 (030 /
070) AM (180) DM (180) AH1 (180)
Parts name
1 Body 4 Control board 7 Drive gear
2 Motor cover 5 Terminal block 8 Drive shaft
3 Motor 6 Limit switch 9 Rubber packing
107
36
74
99
58 2
5
3
4
1
9
6
8
85
36
74
126
107
2
5
3
4
1
9
6
8
107
85
53
74
140
7
2
5
4
3
9
6
8
1

OSCZX22A-EN
7/13
ELECTRIC ACTUATOR SPECIFICATIONS
PAX type
Actuator type ( :Voltage code) PAX-050- PAX-120-
Voltage 100 / 110 V AC ±10 % 50/60 Hz (Code: 1)
200 / 220 V AC ±10 % 50/60 Hz (Code: 2)
Rated torque [Nm] 5 12
Operation time [s] 14 / 12 (50/60 Hz) 30 / 25 (50/60 Hz)
Power consumption [VA] 9.5
Motor Synchronous motor (Triac control)
Overload protection Impedance protect
Method of operation Proportional control
Input signal 4 to 20 mA / 1 to 5 V (Input resistance: 250 )
Operation *¹ [Mode A] SHUT by decreased signal « OPEN by increased signal (Standard)
[Mode B] SHUT by increased signal « OPEN by decreased signal (Option: J)
Indication signal 0 mA : SHUT « 1 mA : OPEN (External load resistance: less than 3 k)
Common in mode A / B
Resolution Less than 0.2 %
Duty cycle 100 %
Ambient temperature -20 to 55 ºC
Space heater 1 W
Manual operation Direct operation of actuator by loosening lock screw
Enclosure Equivalent to IP65 (IEC 60529)
Housing material Aluminum alloy die cast + Polycarbonate resin cover
Terminal block For bare wire 0.2 to 1.5 mm² (AWG 26 to 16) Ground terminal: M3
Conduct port G3/8 Cable gland (for 5 to 10.5 mm cable)
*¹ Change by DIP switch. (Standard ® Mode B)
WIRING
Setting with DIP switch
Mode A / B is selected simply by setting the mode
change DIP switch located on built-in control board.
Mode A Mode B
Note) • Input signal circuit is non-isolated. Do not connect DC (-) wire to other DC (-) common.
• Do not adjust operating angle of a valve (OPEN/SHUT trimmer).
Please contact us if you need to adjust operating angle.
Input signal
4 to 20mA
1 to 5V
Indication signal
0 to 1mA
Voltage
100/110V AC
200/220V AC
Ground terminal(M3)
Trimmers
Operation
range
Potentiometer
1kΩ
Dead band
Indication
signal

OSCZX22A-EN
8/13
ELECTRIC ACTUATOR SPECIFICATIONS
OPTIONAL PARTS
Specifications Code No. PAX Remarks
Aluminum alloy motor cover AK
Flexible cable (Approx. 300 mm long) C1
Operation SHUT by decreased signal « OPEN by Increased signal Nil Mode A
SHUT by increased signal « OPEN by decreased signal J Mode B
DIMENSION
PAX (050) PAX (120)
Parts name
1 Body 4 Control board 7 Drive shaft
2 Motor cover 5 Terminal block 8 Rubber packing
3 Motor 6 Potentiometer
ADJUSTMENT (PAX)
Dead band
Turn the trimmer clockwise for wide the dead band as necessary.
It is useful to prevent the hunting reaction of actuator.
*Each trimmer on a built-in control board.
Operating range
Do not adjust operating angle of a valve (OPEN, SHUT trimmer).
Please contact us if you need to adjust operating angle.
Operating speed (Speed control)
No adjustment required. (ZERO, SPAN trimmer)
36
107 74
126
85
1
2
6
3
4
5
7
8
74
53
107
140
85
1
2
6
3
4
5
7
8
T1
POWER
SPAN
ZERO
SHUT OPEN D.B.
T2
ON
↑
I-
4~20 mA
I+ +
1
S1
0~1 mA
-
DIP SW
Adjustment trimmer

OSCZX22A-EN
9/13
ELECTRIC ACTUATOR SPECIFICATIONS
ACR type
Actuator type ACR-030-2
Voltage 100 to 220 V AC ±10 % 50/60 Hz
Rated torque [Nm] 3
Operation time [s] When power supply on ® less than 12
When power supply shut off ® less than 6
Power consumption (Max) [VA] 30
Motor DC motor
Overload protection Thermistor
Method of operation Operation by power ON / OFF
Operation Power OFF : SHUT « Power ON : OPEN (Standard)
Power ON : SHUT « Power OFF : OPEN (Option: 45)
Built-in power supply Electric double layer capacitor
Duty cycle 20 % 15 min.
Ambient temperature -20 to 50 ºC
Manual operation Direct operation of output shaft
Enclosure Equivalent to IP65 (IEC 60529)
Housing material Aluminum alloy die cast + Polycarbonate resin cover
Terminal block For bare wire 0.14 to 1.5 mm² (AWG 26 to 16) Ground terminal: M3
Conduct port G3/8 Cable gland (for 5 to 10.5 mm cable)
WIRING
Note) This actuator uses a switching power supply. After turning on the power, inrush current flows.
Selecting the switch to afford.
Backup
capacitor
S.LS
O.LS
Voltage
100 to 220V AC
Ground terminal(M3)

OSCZX22A-EN
10/13
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
HANDLING & STORAGE
HANDLING
Do not drop or throw the product as it may break.
STORAGE
Store away from dust, moisture and direct sunlight.
If possible, store in the original package.
CHECKING
• Check the product code, power supply, and voltage
before installation.
• Make sure that the bolts are not loose.
• The DIP switch should be set up before the power is
turned on. Do not touch unnecessary switches.
(PAX)
INSTALLATION
PRECAUTIONS
• Flush the pipeline carefully before installing the
valve. Foreign particles, such as sand or pieces of
welding electrode, will damage the disk and seats.
• When piping the valve disk should be closed before
mounting.
• Avoid oil or grease when using EPDM seat.
• The butterfly valve should be piped upstream of the
elbow. When piping downstream from the elbow,
considered a straight line that is at least five times
the length of the pipe.
• The valve stem should be mounted perpendicular to
the flow for biased fluid.
PIPING
• Using a pipe with too long a thread will damage the
valve.
• If sealing tape or sealant gets inside the valve, the
valve seat leaks or malfunctions.
• When connecting a pipe or fitting to a valve, use a
tool on the octagonal or hexagonal part of the
insertion side and screw it.
• Refer to the recommended tightening torque table
and do not apply excessive torque.
Valve size [mm] Torque [Nm]
015 25 to 35
020 40 to 50
025 50 to 60
032 60 to 80
040 75 to 85
050 90 to 110
Socket End
Should use adhesive suitable for valve materials.
ENVIRONMENT
• Do not install in place where corrosive gas is present
or where vibration is heavy (0.5 G or more).
• When radiant heat causes the surface temperature
of the control unit to exceed 55 °C (ACR: 50 °C),
provide an appropriate shielding plate.
• If there is a possibility that the fluid and drive part
freeze, please take measures to prevent freezing.
POSITIONING
Should be positioned through 90° upward from
horizontal. Provide space around the product to
allow manual operation, inspection and replacement
work.
Margin required around the actuator for maintenance
AM (030 / 070) DM2 (030) More than 65 mm
AM AH1 DM PAX ACR More than 90 mm
OTHER NOTES
Until the wiring is completed there must be no
condensation or flooding in the interior of the
actuator, after piping. Protective caps on the cable
gland are not waterproof.
WIRING
• Do not wiring outdoors on a rainy day.
• Check the power supply and voltage.
Connect the signal as shown in the wiring diagram.
• Do not connect unnecessarily terminal.
• Use suitable flexible cable (5 to 10.5 mm).
Lock and seal the cable completely to prevent
condensation inside the actuator.
• Built-in terminal block can clamp up to 1.5 mm² in
diameter without using solderless terminal.
• Allow proper cable slack for maintenance.
• Actuator should be electrically grounded.
Use the terminal marked ( ) inside the actuator.
PREVENT DEW CONDENSATION
• When installing the cover after wiring, perform the
bolt by the temporary tightening procedure and the
permanent tightening procedure to tightly and
securely tighten the rubber packing so that water
does not enter from the outside.
• Tighten the cable gland nut so that there is no
leakage from the wire entrance.
Slow Fast Slow Fast

OSCZX22A-EN
11/13
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
CONTROL
AM1 / AH1
Control switch should be prepared one by one for
actuator. Do not operate two or more actuator from
one switch. It might malfunction.
AM2
• Two or more actuators can be operated with one
control switch.
• When using control switch with current leakage
(more than 1 mA) such as TRIAC or relay with CR,
it can cause malfunction.
• When wiring is long distance or handling a weak
current signal, it may be affected by induced voltage
or noise. In this case, please use countermeasures
such as using a shielded wire, separating it from
other power cables.
DC POWER SUPPLY
• It is usable with a battery and full-wave rectification
circuit.
• Consider an inrush current of motor.
(It is 1.5 to 3 times of consumed current.)
• They may cause malfunction with decreasing voltage
by the long wiring.
• Do not use power supply that require more than
1 second with rise and fall time.
USE OF OPEN/SHUT SIGNALS (AM / AH1 / DM)
Use signals within the capacity of output signal
rating.
ACR
• Inrush current flows when the switching power
supply is turned on. Use a fuse, relay or switch with
sufficient capacity.
• It may be affected by induced voltage or noise.
Please use countermeasures such as using a
shielded wire, separating it from other power cables.
(When a power supply is off, the terminal block
should make the induced voltage less than 10V.)
PAX
• Use shielded wire for signal wiring where high level
noise is generated or when the wiring distance is
long.
• Control with a 1 to 5 V input signal becomes an input
resistance 250 . Provide a voltage that can safely
20 mA or more than.
• Check whether the MODE change DIP SW on a
circuit board substrate is set up correctly.
When wiring, if wiring of a signal is mistaken, it will
not operate correctly. Contact us when you use two
valve or more by one controller or indicator.
• Input signal circuit is non-isolated.
Do not connect DC (-) wire to other DC (-) common.
• The input signal and operation mode are set as
follows. (Factory shipped)
Input signal 4 to 20 mA / 1 to 5 V
Operation mode Mode A
Operation SHUT by decreased signal
OPEN by increased signal
OPERATION
TESTING
• Make sure that power supply voltage is correct. Also
check operating position, wiring, speed and signals.
• During trial operation, check that valve movement
and output signal are correct.
DUTY CYCLE (AM / AH1 / DM / ACR)
Confirm that the operation frequency is within the
specified duty cycle.
Use beyond the load time rate range will affect
product life. Also, it may cause burnout.
Duty cycle is a value that regulates the opening /
closing frequency of the actuator. The meaning of
20 % 15 minutes for Duty cycle is that 3 minutes
(20 % of 15 minutes) operation is possible.
The calculated value obtained by dividing 3
minutes by the operation time is the number of
times of operation within 15 minutes.
CONFIRM THE OPERATING CONDITION (PAX)
• Adjust fluid condition, controller setting, sensor etc.
so that stable control is achieved.
• When used in an unstable control state, the life of
the actuator and the valve will be shortened.
• The desired control state is stable at the target value.
Adjust the PID setting value of the controller when
overshooting the target value greatly, when not
converging for a long time or hunting operation. Also,
when the time delay is large, please consider the
sensor position.
ATTENTION
• Be sure to set the DIP-SW before turning on the
power supply. (PAX)
• Keep power supplied for built-in space heater to
prevent condensation inside actuator. (AM / AH1 /
DM / PAX)
• Do not touch the moving parts of actuator in
operation.
• Do not insert a reverse signal during operation.
It may shorten the life of product. (AM / AH1 / DM /
PAX)
• Never put anything on the actuator or make it into a
foothold.

OSCZX22A-EN
12/13
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
MANUAL OPERATION
PRECAUTIONS
• Manual operation should be a temporary operation.
• Be sure to turn off the power before manual
operation.
ACR
If it is not left after power supply cut off for 6 hours, it
will operate with capacitor charge voltage. Make
sure that the following procedure in case of
emergency.
1) Put an allen wrench into the hold on drive
shaft and turn slowly.
2) Internal limit switch gets used from a switch
setting cam, then the motor of actuator will
operate and it hold in the position.
3) The capacitor discharge in about 1 minute,
perform manual operation.
NOTE
For manual operation, do not give more than the
rated torque and make at a slow rate. Actuator might
be damaged if excessive force is added.
AM PAX AH1 DM ACR
Actuator can be easily
removed from the valve
by loosing 3 lock
screws, and that allows
direct operation of the
valve. After operation,
be sure to put back the
actuator to the original
position and lock.
Put an allen wrench
(5 mm) or a lever
(5.7) into the hole on
drive shaft and turn
slowly.
Manual lever is
optional.
MAINTENANCE
• To prevent electric shock, be sure to turn off the
power when removing the actuator cover.
• Do the routine maintenance at least once in half a
year.
Inspection items
• Confirm operation of opening and closing.
• Confirm that an actuator is not hot excessively.
• Confirm existence of abnormal noise and
vibration during operation.
• Confirm whether screws are loose or not.
• Confirm that water or condensation no remains
in the actuator.
• Turn off the power and check if the valve
operates normally with built-in capacitor. (ACR)
• Confirm the fluid temperature or pressure.
• Confirm the leak from valve stem.
• Confirm the bolt tightening torque.
Lock
screws

OSCZX22A-EN
Document is subject to change without notice.
NIPPON VALVE CONTROLS, INC.
1-21-19 Meieki minami, Nakamura-ku, Nagoya 450-0003 JAPAN
TEL: 81-52-582-6435 FAX: 81-52-582-6439
13/13
INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS
TROUBLE SHOOTING
Problem Cause Solution
Actuator
does not
move.
Faulty wiring. Correct the wiring.
No voltage is
coming.
Check the voltage.
Incorrect
voltage.
When it's burned out by
excess voltage, replace
the actuator.
Connection or
wiring is not
correct. (PAX)
Correct the miswiring
and misconnection.
Be careful not to
mistake the plus and
minus of wiring.
Short the
circuit, contact
failure.
Review wires and
connection.
Motor is too
old.
Replace the actuator.
Operation
is unstable.
Excess surge
or voltage was
applied.
Replace the actuator.
Rainwater
entered the
actuator.
Switch leakage
current is large.
(AM2)
Current leakage should
be less than 1 mA.
Operation
is unstable.
(PAX)
Added high
harmonics
noise from an
inverter.
Attachment a filter for
each inverter maker
option.
Effect of high
level noise.
Use the shielded wire
and ground the wiring.
Separate signal wire
from power line.
Stop in the
mid
position.
(Input
signal’s
1 to 5 V.)
(PAX)
Signal voltage
source capacity
shortage.
Use a voltage source
that can be made to
flow more than 20 mA.
Please contact us.
Stop in the
mid
position.
Continuous irregular stop will shorten the
motor life and wear the gear. Turn off the
power and check.
(AM1 AM2 AH1-030)
Problem Cause Solution
Stop in the
mid
position.
Biting of valve
seat.
Remove a foreign
object.
Overload
protector runs
because of
over-torque.
Turn off the power for
about 3 minutes to
remove a heat from
motor protection circuit.
(AM AH DM ACR)
Motor protection circuit
returns by the signal of
operation of an
opposite direction. Turn
on the power again.
(PAX)
Capacitor is too
old. (ACR)
Replace the actuator.
Leakage
from
valve seat
Seat is worn or
damaged.
Replace the valve.
Leakage
from
valve stem
Packing is worn
or distorted.
For more information contact
NIPPON VALVE CONTROLS, INC. for consultation.
This manual suits for next models
1
Table of contents
Other NIPPON VALVE CONTROLS Control Unit manuals
Popular Control Unit manuals by other brands

Multitech
Multitech MultiConnect Dragonfly MTQ-MNA1-B02 Device guide

Ublox
Ublox NINA-B1 Series System integration manual

Ublox
Ublox LISA-U100 Integration manual

Hitech
Hitech HT884/8 user manual

Plast-O-Matic
Plast-O-Matic True Blue RVDT Series Assembly/Installation/Operating Instructions

Paradox
Paradox PCS265LTE Installation and programming guide