Nokeval 2800-2061 User manual

1
Nokeval
Manual
No 250803
Model 2800-2061
Scalable counter for
pulse sensors

2
Manufacturer:
Nokeval Oy
Yrittäjäkatu 12
37100 NOKIA, FINLAND
Tel. +358 (0)3 342 4800
Fax. +358 (0)3 342 2066
http//:www.nokeval.com

3
Counter / batch controller 2800-2061 for pulse sensors
Description
The field display series 2800-2061 is designed for
pulsecountingandbatchcontrolinapplicationswhere
a readability of 20 to 100 metres is required.
Theincomingpulsesarefreelyscaleableondisplayto
correspondthewantednumbervalue,e.g.1incoming
pulse equals to 5,34 on display. Display memory
stores the calculated value in memory for one week
afterpowersupplybreak.
The preset function makes it possible to use the
counterasabatchcontrolleraswell.Countingcanbe
doneup-ordownwardsfromthepresetvalue. Alarm
relaysmaycontrolotherdevices.Newcountingcanbe
started automatically or manually by external key.
Largefieldcountersarepartofalargerdisplayseries
wherebychangingtheinput/outputcardsthedisplay
can be modified to other input values such as
temperature, serial or frequency input. Two power
suppliy possibilities, one for 85..240 VAC and the
otherfor24VDC,bothgalvanicallyisolatedfrominput/
output.Readabilityofthedisplaysisalsogoodoutdoors
ifexposure todirect sunlight isprevented byusing a
suncover.Case protection is IP65.
*
5620.0
Flow sensor with
pulse output
1 pulse=15,3 litres
Valve
Output relay closes valve
when counter reaches set
value. Reset activates
relay and opens valve.
Reset and new start
Contact information
when new barrel
ready for fill up
*
100.0
Output
relay
Valve
Quantity
t
Scaleable pulse input may be set to
indicate real value on display, e.g. 1
pulse corresponds to 5,3 m³ on display
or 1 pulse corresponds to 15,3 litres.
Picture on the right shows
application of flow sensor with
pulse output.
Below an application from piece
goods automation.

4
Technical specification:
Sensors: NPN, PNP, Namur, closing
contact
Inputvoltagelevels: 0 = < 1V, 1 = 5..32V
Sensorsupply: 24 VDC ± 5%, max. 150 mA
Input frequency range: 0..5 kHz
Decimal selection: 0,001..1
Displayscaling: freely by configuration keys
Measuringmethod:
Counting of input pulses into counter. You can multiply the
counter value by a desired number value. The result is
shown on display.
Output:
Alarmrelay will beactivatedwhenthe set pointisreached.
Alternatively loop-function; display is reset at alarm value
automatically and relay is activated for only 200 mS.
Serialoutput:
RS232 and RS485. Serial output only for measurement
reading. Baud rate and address (RS485 selectable.
Relays:
You can set alarm value by button inside the case.
Relay contacts max. 230 VAC, 0,5 A. Alternatively semi-
conductor relays 60 V / 0,5 A
Displaymemory:
Add-on card 2000-MEM stores display for 1 week without
power supply.
Model 2800-2061-MEM-REL2-24VDC
Model
Input card (2061)
Memorycard(MEM)
or Serial card (RS)
Relay card (REL2)
Power supply
85-230VAC
or 24VDC (0ption)
Type code:
Dimensions:
General
Power supply 85..240 VAC or 24VDC (12W)
Display 6 digits, red LED
Digit size 20 mm
Enclosure Grey plastic
Protection IP65
The counter is also available for analog inputs 0/4-20
mA or 0-10 V, series 2800-2026
Wall mounting brackets at the corners of the case - easily removable.
Glands 3 x PG11
180
130
80
164
153

5
Powersupply
85..240VAC
NPN-sensor
PNP-sensor
Namur-sensor
Contactinput
Inputandoutputcards
Expansion slot A is for input card and the
expansion slots B and C is for optional
cards.
+
NPN-sensor
NPN
0V
24 VDC (max 150 mA)
to sensor (1/3)
Slot A
6
5
4
3
2
1
Input pulse
5...24V
+
-
PNP-anturi
PNP
0V
24 VDC (max 150 mA)
Slot A
6
5
4
3
2
1
Input pulse
5...24V
Only if you supply
24V from panelmeter
+
Namur-sensor
Namur
0V
+
Slot A
6
5
4
3
2
1
Namur-sensor
2-wire sensor
0= <1mA, 1=>3mA
Closing contact
Input
0
Slot A
6
5
4
3
2
1
Pulse
5...24V
Power supply selection
to sensor: Powersupply 12 V
max 50 mA
Power supply 24 V
Default (max 150 mA)
ConnectorJumper setting for contact input.
Max. input frequence 40 Hz.
6
5
4
3
2
1
6
5
4
3
2
1
6
5
4
3
2
18 9
Slot A Slot B Slot C
Relay 1
REL2
Relay cardInput
Reset No
Nc
7
Connections:
It is possible to connect external reset to the
display. For this function attach closing contact
connectors to input card (A) pins 3 and 6.
Display can also be reset by pressing ▼and ▲
simultaneously.
Alarm cards:
Frequency of output relay
is max. 1Hz. With bigger
frequencies use the
additional I/O-card, max.
40V, 50mA.
Note:SelectNPN-sensor
frominputmenu.
6
5
4
3
2
1
Slot B/C
Up/down counting
selection from external
contact: Use option
card 2000-I/O card
Input card jumper settings
12..32 VDC and
24VAC
No polarity
8 97

6
Configuration keys
*
5620.0
Conf-LEDindicatesthat
displayisin configuration
state.
Movenumbersfromlefttorightwhen
you change alarms or settings.
With -keys You can move on or change
numbersandvaluesinprogrammingmenu.
Acceptance of chosen state and
returnin tothe previoismenu.
Alarm light A1
Programming state
The programming state is entered pressing simulta-
neously★-and▲ -buttonsfor2seconds.Inprogram-
mingstateitispossibletochangemanydifferentvalues
f.ex. scaling the display, change alarm values, select
sensors etc.
400.00
Number setting
Numbers
0...9 and , (decimal)
Setting of alarm value
You can set alarm value by ▲-keys number
bynumber.Settingstarts from largest number
from left to right. You may go to next number by
X-key. Exit by ★-key.
Alarmsetting
Alarmvaluescanbechangedandviewedinmeasuring
state.Otherfunctions mustbedone in configuration
mode.Unithasonealarmlevelwhichcanbeviewed
withX-button.AfterX-pressingthelightA1-LEDlids
and display shows alarm1 level, A1-LED blinks to
informthatunitisinalarmlevelstate.SecondX-push
returnsdisplayintomeasuringstate.Ifbuttonsarenot
pressedwithin8secondstheunitreturnsautomatically
into measuring state and saves settings.
WhenA1ledblinksusercanentereditingmodeusing
▲ or▼ -buttons.Valuescanbechangedasdescribed
above. Accept changes with -button.

7
Mainmenu Menuvalue Name Description
Pulse Pulse multiplayervalue Whatvalue 1 pulse means in display.Value can
include decimals.
Divide Value ofpulse divider Used in special case when there is notpossible to use
multiplayer to setenough decimals. See example*.
Start Value where counting starts
Limit1 Alarmlevel 1 Countervalue when the alarm 1 pulls.
No Closing contact, alarm 1
Nc Opening contact,alarm 1
Adjust Start Startvalue in quicksetup.
Limit1 Limit1value in quicksetup
Loop On Loop function in use
Off Loop function notin use
Limit2 Alarmlevel 2 Countervalue when the alarmrelay2 pulls.
On Alarmlevel 2 depends the
alarmlevel 1. Value ofthe alarmlevel 1 added to a alarmlevel 2,after
the combined value alarm 2 pulls.
Off Alarmlevel 2 is absolut. Alarmlevel 2 function is exactlylike alarmlevel 1.
No Closing contact, alarm 2
Nc Opening contact,alarm 2
Divout Value ofdivider States how manypuses needed to pull alarm.
Limit2 Relay2 = alarmrelay,Relay3 =
divide out
Divout Relay2 = divide out,Relay3 =
alarm 3
On Esternal resetprohibited.
Off Esternal reset allowed.
On Start/ Limitvalue inspection.
Off Inspection is notused.
On Relays in alarm state after the power up (untill reset).
Off Relays working normallyafter power up.
Up Counting up
Down Counting down
OFF No external contact in use.
revers Countdirection selection.
Step External contactsteps backto previous value.
SlotB I/O-card in slotB,external contactin line 4.
SlotC I/O-card in slotC,external contactin line 4.
NC External switch contactselection,normallyclosed.
NO External switch contactselection,normallyopen.
Dec Number ofdesimals How manydesimals are shown in display.
Int 0…15 Intensityof display. Change the displayintensityfrom 0 to 15.
NPN (Contact) Sensortype selection
PNP
Namur
Pickup
Baud r 300…19200 Baud rate Baud rate for serial interface:300...19200
Addres Addre 0…127 Serialaddress Serialdata address selection:0…127
Off RS485 notin use
SlotB RS485 used in slotB.
Save XSave the changes to memory.
Undo XCancels selections.
Cont 1
PO res
Check
Res bl
When reseting counter,first pulse brings the value of
what is selected in Adjust setting (Start or Limit1).
Second resetpulse clears the counter value.
Slot
Slot c
Cont 2
Direct
E Swit
ST
- moving up/down in menu,X
- change settings/move to a nextlevel,Ì
-
accept/return back
Type of the pulse sensor.
NOTE !Ifclosing contactis used,please selectsensor
to NPN.
Starting value (Start) or counting alarm value (Limit1)
can be change directlyfrom displaywithoutentering
inside menu.
With function Loop (On)counter reset's to zero and start
automaticallynew counting untill the alarm (Limit1) is
achieved.
External resetcontact lock while counting. Reset can be
done after the alarmlevel is achieved.Doesen'taffect
reseting from the frontpanel.
Alarm 1 relayposition setup.
Follow
Alarm 2 realyposition setup.
REL2 Relay2 and relay3 setup,here you can switch relay2
and relay3 funtions among themselves.
RS485 serialdata-card selection.NOTE !ifRS232 is
used you doesen'tneed to make this selection.
You can jump to Save and Undo selection in
mainmenu using Ì-button.Selection is confirmed with
X-button.
Selection ofwich direction the counter startcounting,
up or down.
Sensor
RS-485
Mode
Programmenu

8
Serial output RS485/RS232 (option)
Metermaybeprovidedwithoptionalserialoutputand
you can read measurements by e.g. PC. Display
programming can not be made via serial port. Addi-
tional card provides serial signal RS232 and RS485,
only one of those can be selected.
Serial signal is isolated from both input signal and
power supply. Meters with RS485 can be max. 31 in
same loop and longest distance 1000m. RS232 en-
ables only connection of two devices and max. dis-
tance 10..20 m.
In programming stage you can first select card type
(serial) mounted to slot B or C and then address and
Baud rate. Baud rates are: 300, 1200, 2400, 4800,
9600,19200andaddresses0...127.
Accept selection and move forward by -key. You
come back to previous level always by -key.
Programrememberscardtypemounted,ifithasbeen
saved by save command when leaving program. In
case you can not choose serial card, slot has
automaticallyrecognizedcard(plugandplay).
Terminalconnections:
By serial signal RS485 last unit must be
terminated by 110 ohm resistor. you can
maketermination atterminalconnectors
or by connecting jumper J1 to ON-
position.
Serialcard
6
5
4
3
2
1
Card slot A Card slot B or C
Input
6
5
4
3
2
1Com
RxD
Serial output
A
BRS-485
TxD
2000-RS
on off Term
Fs
on off
on off
on off
Term
Fs
Term
Fs
Term
Fs
RS232 RS485
channel's middle
unit
(Factory settings)
RS485
channel's last
unit
Mainmenu Selection Term Description
- move up/down to menu, - move to the adjustment level/next level, - accept selection/return to the previous level
Baud r 300...19200 Baud rate Baud rate selection: 300..19200
Addres Addre 0...127 Serial address Serial address selection: 0..127
RS-485 Off
Slot B Serial card RS485 not in use
Serial card RS485 installed slot B RS485 serial signal selection.
Note ! if used to serieal signal RS232, selection doesn't
need to make.
Serial signal configuration

9
Termination resistor 110 ohm
on last units terminals Dataacquisition
withPC
RS485
Address 2 Address 1 Address 0
Twisted pair cable
Serial protocol (SCL):
MESSAGES: When asking the measurement data
from the panelmeter 2061 through the serial port, a
command sequence which is in accordance with the
SCL protocol is used for the inquiry:
(Onlythemeasurementresultscanbeaskedfromthe
panelmeter2061)
<ADDR+80h>COMMANDSTRING<ETX><BCC>
<ADDR>
ThefirstbytecharactertobesentcontainstheADDR
(0..127)oftheaddressofthedestinationdeviceandat
the same time functions as the start bit of the com-
mand.80H(inadecimal128)withwhichanuppermost
bit is set as the number one is added to the address.
COMMAND STRING: When measurement data is
requested, the actual command is: MEA CH 1 ? , in
which1meansthechannelnumber.(thereisonlyone
channel in the panelmeter 2061 so the number is
always1).
<ETX>
<ETX>meantheendmark ofthecommand,
ASCIIcharacter03h.
<BCC>
Finally the checksum is calculated using the XOR
operation on the byte characters of the actual com-
mand including the ETX. In the example the ASCII
codeshavebeenpresentedinhexadecimal.
e.g.
One wants the measurement result from the display
unit address 1. To the channel an inquiry is sent:
MEA CH 1 ? (ASCII codes shown for <BCC>
calculation)
M E A C H 1 ?<ETX> <BCC>
4Dx45x41x20x43x48x20x31x20x3F x03 = 6F
(Presented the XOR operation with a character x)
(ASCIIcode20hcorrespondstospacecharacter)
So the following bytes are sent to 2061:
81 4D 45 41 20 43 48 20 31 20 3F 03 6F
RETURNMESSAGE:Theanswerfromthepanelmeter
2061isobtainedinthefollowingformat:
<ACK>RETURNMESSAGE<ETX><BCC>
<ACK>
The first byte of the answer contains the start of the
answer <ACK> (ASCII-code 06h) and the answer
itself,endmark<ETX>(ASCII-03h)andthechecksum
of the answer which is calculated from all the byte
charactersof theanswerincluding<ACK>and<ETX>.
2061countsthechecksuminwhichcasethereceiver
does not need necessarily to care about it,
e.g.
e.g.Whenameasurementresultisforexample21.3,
itwillbeobtainedfromthepanelmeterinthefollowing
form
<ACK> 2 1 . 3 <ETX> <BCC>
Answer: 06 32 31 2E 33 03 1B
Serial communication
Baudrate:300,1200,2400,4800,9600and19200
1 Start, 8 Data and 1 Stop bit, no parity.
*
5620.0 *
5620.0 *
5620.0

10
ABCPower supply 12...32 VDC
(Green connector)
or 85...240 VAC
(Grey connector)
The field display series is modular and easy to as-
semble. According to customers wishes. The basic
construction consists of mother board with tree slots,
A,BandC.SlotAdeterminesmetertypeandprovides
alwaysinputsignal.SlotBandCareinterchangeable.
Asfactorydeliveryinputsignalisalwaysinstalledinto
slotA, mAoutputinto slotBand alarms intoslotC. In
caseof f.ex4alarmsandrelaycardwith2change-over
contact(2+2relays)are used,youmustplacesecond
Slots A-C
Change of meter
type:
Input card is placed always
to slot A. By changing input
card you can get an other
type of meter. You can
changemeterwithpulse
input to meter with current
input,thermocouple,strain
gage etc.
Additionalslots:
Additionalcardsprovide
output 4..20 mA, alarms,
serialinterface,BCDoutput
etc. Meter data sheet
dictatespossiblecombina-
tions. grey connectors allow
linevoltage110..240 VAC
(relaycontacts).
Power supply:
Therearetwodifferentmother
boardspowersupply85..240
VACand12..32 VDC. VDC-
motherboardaccepts
24VAC.Connectorsare
colourcoded.
relay card into slot B. If you accept only closing or
openingrelaycontacts,youneedonlyonerelaycard
with 4 relays placed into slot C. The slot B is now
usablefor otheroptional outputs.
You can have different types of meters by only
changing the input card in slot A. Data sheet of each
type of meter dictates the possible combinations.
Recalibration of card is not needed; only scaling and
other settings must be set by front panel keys.
Allcardshavecalibration
memory
Construction of field display series

11
2011-IN Process input
2021-MU Multi input
2031-IR Infraredsensorinput
2041-SG Straingagemeasurement
2051-PU Scaleablefrequencyindicator
2061-CO Counterinput(max5 kHz)
2066-SEC Timer function, s/min/h ext.
2071-RS SerialinputRS232 / RS485
2081-BCD BCD-,Gray-binarycodeinput
(1-5digits)
2000-BASE Basecardwithpower supply
2000-REL2 Alarmcard,NO/NC
2000-REL3 Alarm card, Closing contacts
2000-OUT Output card, U and I
2000-RS SerialoutputRS232orRS485
2000-I/O 4 pcs input /output ports
(60 V / 100 mA)
DAC
E²
E²
E²
ADC
E²
uP
Modular field display series 2800
6543.21
5-6-digitredLEDdisplay
Power supply:
85..240VACor
12..32 VDC / 24
VAC
Optioncards
Alarmcards:
2 relay card, 4 alarm types,
change over contacts
3 relay card, closing contacts
4I/O-ports
Model2011:
2relayschangeovercontacts
(alsowithremotereset)
Outputcards(notfor2011):
0/4..20 mA, 0..10 V
RS232orRS485
Sensor supply:
24VDC,
150 mA
Model 2021 contains also process inputs but it can also measure RTD-sensors and ther-
mocouples.2021has very accurateandfastA/D-converter(16 bit 1/64000).
2000 series input and option cards:
Input card con-
tains:
-microprocessor
- bus control
- keys control
- display control
Processinputs(model2011):
0..20 mA, 4..20 mA, 0..5/10 V
Potentiometer100Ω..5kΩ
2021
2011

12

13

14
Manufacturer:
Nokeval Oy
Yrittäjäkatu12
37100NOKIA
Finland
Tel. +358 (0)3 342 4800
Fax. +358 (0)3 342 2066
email [email protected]
http:// www.nokeval.com
Table of contents
Popular Cash Counter manuals by other brands

Yoosol Electronics
Yoosol Electronics PRIMO-P1 user manual

SUTO
SUTO S132 Instruction and operation manual

Hengstler
Hengstler signo 723.1 operating instructions

Kaliming
Kaliming Nex Bill KL-2000 seies manual

Nautilus Hyosung
Nautilus Hyosung MONiMAX7800I installation manual

saia-burgess
saia-burgess CXG 21 operating instructions