10
HY H (Hysteresis Low) (starting from firmware V2.2)
Hysteresis prevents relays from changing their state needlessly when the display value fluctuates near the
alarm level. The alarm is deactivated when the display value moves away from the alarm level by the value
of HY H. For example if AL H = 80 and HY H = 5, the alarm is activated when the display value is 80 and is
deactivated when the display value is 75.
A keyboard alarm reset can be enabled by setting the hysteresis higher than the scaled range
(for example 9999). This way the alarm stays on waiting for a vkey press or for the display value to
decrease under the alarm level. The alarm is then switched off because both relays cannot be active
simultaneously.
Alarm can be disabled completely by changing this setting to a negative value. This will however not reduce
voltage drop. For models 201, 301 and 305 the default is -1.0. For 202 and 302, the default is 1.0.
ALHy (Alarm Hysteresis) (only in firmware V2.0-V2.1)
Hysteresis prevents relays from changing their state needlessly when the display value fluctuates near the
alarm level. The alarm is deactivated when the display value moves away from the alarm level by the value
of ALHy. For example if AL H = 80 and ALHy = 5, the alarm is activated when the display value is 80 and is
deactivated when the display value is 75.
A keyboard alarm reset can be enabled by setting the hysteresis higher than the scaled range
(for example 9999). This way the alarm stays on waiting for a vkey press or for the display value to
decrease under the alarm level. The alarm is then switched off because both relays cannot be active
simultaneously.
Alarms can be disabled completely by changing this setting to a negative value. This will however not
reduce voltage drop. For models 201, 301 and 305 the default is -1.0. For 202 and 302, the default is 1.0.
Dec (Decimal)
The number of decimals displayed. Options are 0, 1, 2 or 3. Default is 1.
Lo (Low)
The display value shown with a 4mA current. Default is 0.000.
Hi (High)
The display value shown with a 20mA current. Default is 100.0.
Dead
Dead changes the lowest numbers of the display to show zero. For example if Dead=5, the display will
function normally with a value higher than 5, but values lower than 5 will be forced to 0. Negative display
values can be disabled by setting Dead=0. Negative values will disable this setting. Default is -1.00.
LoPass (Low-Pass)
A digital low-pass filter for damping big display values and fluctuations. The value is a time constant in
seconds. Default is 0.5 seconds. The filter is disabled when the value is 0. Alarms are controlled by the
filtered value, so the low-pass filter also increases alarm reaction time. Default is 0.5.
Intens (Intensity)
Display intensity. With the current below 6mA, the intensity decreases automatically so that at 4mA it is at
most half of the maximum intensity. Value range is 1…15. Default is 15.