Power supplies
The Stable-LWEU-T-DI is powered with a 3.6V Lithium Thionyl battery pack.
The device is supplied with batteries already installed, so it is ready to be used.
Settings
The Stable-LWEU-T-DI works with its default settings and no parameter configuration is normally
required. However, if it is necessary to change the settings of the device, it can be done with Nokeval’s
MekuWin software (available for free at www.nokeval.com). Following procedure should be followed in
order to get access to the settings:
•Open the enclosure by removing the 6 screws.
•Connect a micro-USB cable to the connector, and the other end of the cable to a computer.
•If Windows requests for a driver, download it at www.nokeval.com > Support, unzip it to a
temporary folder, and show that directory as the location for the driver. If there are problems
during the installation, try pushing the button every 5-15 seconds or keeping it pressed so that
the Stable-LWEU-T-DI will not shut down its USB port.
•Launch the MekuWin program.
•In MekuWin, choose the right COM-port form the Ports-menu. If the port is not visible, try
pushing the button on the Stable-LWEU-T-DI to wake up the port.
•From the Port settings -menu, choose Protocol = ModbusRTU, Address = 1.
•Click Direct.
•A new window will open for the settings.
The configuration menu includes the following settings:
•Protection
oDescribes password protection status “None”, “Locked”, “Unlocked”.
•Password input/setup
oUnlock protection or change password. See “Protecting the settings” section below for
details.
•Transmission Period
oTime between transmissions with options from ranging 5 minutes to 6 hours. Default is 30
min.
•Trigger high temperature
oTemperature measurement value which triggers an alarm state with more frequent
transmissions (same interval as Measurement Period).
•Measurement Period
oTime between measurements with options ranging from 1 minute to 1 hour. Default is 2
minutes. The measurements are transmitted only if above Trigger high temperature, or if
a digital input has changed.
•Digital inputs enabled
oIf enabled, all 3 digital inputs are measured, and a transmission is done when one of their
states changes. If disabled, none of the digital inputs are measured.
•Pt100 wire select status
oDisplay status, jumper is used this reads e.g. “Jumper selected 3-wire”. If jumper is not
used to select the wiring type, it reads “Menu selected wires”.
•Pt100 wire select
oPt100 wiring selection: 2-wire, 3-wire, or 4-wire. Only applicable if the above status is
“Menu selected wires”
•LoRaWAN