9
5) FOR N-0751M US NG NATURAL GAS (ELV C RCU T BOARD) ONLY: Use the “up” arrow
key until the remote controller displays “19”. Change “19” from “OFF” to “ON”. The
priority light should be flashing after pressing the “FLOW METER ALARM SET”.
6) Change “FC” and “FE” from OFF to ON. The priority light should be flashing on both item
numbers after pressing the “FLOW METER ALARM SET”.
7) Choose the proper conversion setting from the chart below and set the “A1”
Maintenance Writer item number according to the chart below.
Note: DO NOT change the other item numbers. This will cause a fault in the water heater.
ON: “Priority” light is
flashing.
OFF: “Priority” light is off.
8) After setting the “A1” item number for the desired gas type, press and hold the “up”
and “down” buttons together for five seconds to confirm the new settings. The remote
controller will emit a tone and the display will go blank when the settings are confirmed.
If this is not done, the unit will not put the setting changes into effect.
Note: The setting changes can be cancelled by pressing the Power ON/OFF button
before confirming the settings, or if the unit is left alone for ten minutes without
confirming the settings. If the default setting needs to be changed again, disconnect the
electrical power to the unit, reconnect it and repeat this procedure.
Testing:
1) efore turning on the gas supply to the unit, verify that the inlet gas supply pressure is
within the following operating ranges:
a. Natural Gas Supply: Min. 4 – Max. 10.5 inches
b. Propane Supply: Min. 8 – Max. 14 inches
Note: If the supply pressure is higher that the maximum allowable pressure, adjust the pressure
at the regulator or install a secondary regulator on the supply line connected to the water
heater. DO NOT attempt to operate heater if gas supply pressure is not within ranges
specified above. High supply pressure can damage the unit and possibly cause a gas leak.
Next, verify the supply pressure at the unit. To check the gas supply pressure to the unit, a tap
is provided on the gas inlet (Figure 8). Make sure gas supply is turned off to the unit. Remove
the hex head Philips screw from the tap. A 9/32” nut driver is recommended for the removal of
this screw. If a nut driver is not available, a Philips screwdriver can be used. Gently remove the
screw, so as not to strip out the screw.
Models Desired Gas Type A1
N-0751M/NR98-SV, N-0751M-
OD/NR98-OD/NC199-OD,
N-0751M-DV, and N-0751M-
DVC/NR98-DVC/NC199-DVC
Natural Gas ON
N-0751M/NR98-SV, N-0751M-
OD/NR98-OD/NC199-OD,
N-0751M-DV, and N-0751M-
DVC/NR98-DVC/NC199-DVC
Propane OFF