NuAire XBOXER XBC Series Assembly instructions

ErP
COMPLIANT
2016
XBOXER XBC
UNIT SIZES 75 - 85 WITH
ECOSMART ADAPT (TREND) CONTROL (AT)
INSTALLATION, OPERATING AND
MAINTENANCE INSTRUCTIONS
FOR THE COMPLETE VENTILATION SOLUTION

22. 01. 18. Leaflet Number 671730
CONTENTS - INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS
XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
1.0 - 2.0 XBC 75 & 85 Horizontal (AT) Introduction and Access Concepts 3
3.0 - 4.0 XBC 75 & 85 Horizontal (AT) Dimensions and Weights 5
5.0 XBC 75 & 85 Horizontal (AT) Spare Parts 8
6.0 - 7.0 XBC 75 & 85 Vertical (AT) Introduction and Access Concepts 9
8.0 - 9.0 XBC 75 & 85 Vertical (AT) Dimensions and Weights 11
10.0 XBC 75 & 85 Vertical (AT) Spare Parts 14
11.0 Delivery of Equipment 15
12.0 Erection and Assembly 15
13.0 Commissioning and Setting to Work 16
14.0 Description of Control - Software Strategy 17
20.0 After Sales Enquiries 36
15.0 Electrical Details 21
16.0 Connection and Wiring Diagrams 24
17.0 - 19.0 Maintenance & Warranty 36
PAGE

22. 01. 18. Leaflet Number 671730 3
The EMC Directive
2014/30/EU
The Low Voltage
Directive
2014/35/EU
XBOXER XBC 75 & 85 (AT Models)
Supply & Extract Ventilation Unit with Heat Recovery
Installation and Maintenance
1.0 XBC 75 & 85 Horizontal Ecosmart Adapt
(Trend) (AT) Control Models
The information contained in this document provides details of
installation, operation and maintenance for installers and users of
the XBOXER XBC75 & 85 Supply and Extract Ventilation Units with
Heat Recovery.
This supply and extract air handling unit range comprises an
combination of high efficiency centrifugal fans with EC motors, a
counterflow design plate heat exchanger, filters, optional heaters
(LPHW and Electric) and a casing with high mass acoustic treatment.
The one-piece ventilation unit shall be constructed with double
skinned Aluzinc panels on an aluminium Pentapost frame with integral
acoustic mineral fibre ensuring low breakout noise levels. The unit
shall incorporate a high efficiency aluminium counterflow plate heat
exchanger matrix with a thermal efficiency of up to 92%, fitted with
a segmented 100% bypass facility and actuator (patent app. for)
operating under automatic control.
A range of matched, side by side internal and external attenuators
(horizontal units) and double deck internal and external attenuators
(vertical units) with a similar construction method to that of the unit is
available.
General information regarding performance and specifications for the
equipment may be obtained from our Technical Literature, and / or
project specific documentation.
Code description: XBOXER XBC Ventilation Unit
XBC 75 - H - LAT - R - WP
| | | | | | |
1 2 3 4 5 6 7
1. XBOXER XBC Range
2. Unit size 75 & 85
3. H = Horizontal Side by Side layout
4. N = No Heater
L = LPHW Heater
E = Electric Heater
5. AT = Adapt (Trend)
6. R = Opposite arrangement
7. WP = Separate Matched Weather Roof if required
Code description: Matched Attenuator
XBC 75 - H - SIL900
| | | |
1 2 3 4
1. XBOXER XBC Range
2. Unit size 75 & 85
3. H = Horizontal Attenuator
4. SIL900 = 900mm Attenuator
SIL900WP = 900mm Attenuator with roof
Figure 1. Layout Overview of the XBC horizontal unit, viewed from
above with lid removed.

XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
nuaire.co.uk 029 2085 8200
2.0 XBC 75 & 85 Horizontal Unit Access Concepts
Access covers on both
sides of the fan unit.
Access covers on both
sides of the fan unit.
Control cover.
Intake
Extract
Exhaust
from room
Supply to
room
G4 Filter
Counterflow
Heat Exchanger
8mm outside dia.
condensate drain.
Condensate pump
fitted as standard
with alarm facility
Control
LPHW or Electric Heater Battery
In this product range, several unique concepts have been
implemented with a view to simplifying the installation design.
1. The unit must be installed with at least 650mm clearance from a
wall / barrier. With this absolute minimum clearance, the unit may
be connected to the power supply and control connection.
1000mm clearance is required to remove the LPHW coil and electric
heater.
2. With this clearance, unit filters may be changed, and the fans coils,
heat exchanger and condensate tray may be inspected and cleaned
if necessary.
3. The LPHW and Electrical heater settings, coil bleed and drain, and
all other control adjustments are similarly accessible.
Figure 2. The unit must be installed with at least 650mm clearance from a wall / barrier to gain access from the side. Isolate before removing
panels.
Figure 3. Horizontal unit access and configuration. Standard (left hand) unit shown.
4. Side access, where possible, is preferred in all cases in terms of safe
working access to the equipment under the CDM regulations.
5. Note however, that access in the situation is difficult and additional
time should be allocated. For convenience it is preferred that
wherever possible, this minimum access provision is not adopted,
and it is recommended that a minimum of around 600mm
clearance (as stated in ADF 2010) is allowed.
6. Where these arrangements are not suitable, the Consultant’s
and Contractor’s project specific requirements will always be
accommodated where possible.

22. 01. 18. Leaflet Number 671730 5
XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
CK
B
M
J
E
FG
A
3.0 XBC 75 & 85 Dimensions and Weights
3.1 XBC 75 & 85 Horizontal (ES and BC) Unit Dimensions (mm) and Weights (kg)
Figure 4. Horizontal unit dimensions (mm) and weights (kg).
The unit is designed for side access as standard and must be installed with a minimum of clearance of 650mm from a wall or barrier.
This will provide access to filters, coil, fan, heat exchanger, condensate tray and pump.
All models: The weather roof is part of the unit code and is factory fitted only. Example: XBC85-H-LATWP.
*Includes unit and 76mm high base frame.
Unit Code Unit Dimensions (mm) Control Dimensions (mm) Unit Weights Packed Weights
A B C J K M E F G (kg) (kg)
XBC75-H-*** 2800 2126 876* 940 740 940 250 730 800 720 902
XBC85-H-*** 2800 2126 876* 940 740 940 250 730 800 740 942

XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
nuaire.co.uk 029 2085 8200
4.0 XBC 75 & 85 Horizontal (CO) Ancillary Dimensions (mm) and Weights
Figure 5. Horizontal unit ancillary key.
15 241
3
5 3
6
Ref No. 1 Unit Code Description Dimensions (mm) Weight
Width Height Length (kg)
XBC75-H-***WP Unit with weather roof 2000 1001 2800 720
XBC75-H-***-RWP Unit with weather roof 2000 1001 2800 720
XBC85-H-***WP Unit with weather roof 2000 1001 2800 720
XBC85-H-***-RWP Unit with weather roof 2000 1001 2800 720
Ref No. 2 Unit Code Description Dimensions (mm) Weight
Width Height Length (kg)
XBC75-H-RT Weather terminal for horizontal unit 940 740 700 10
XBC85-H-RT Weather terminal for horizontal unit 940 740 700 10
Ref No. 3 Unit Code Description Dimensions (mm) Weight
Width Height Length (kg)
XBC75-F7B/G4P-H F7 Bag / G4 Panel 2000 876 600 115
XBC85-F7B/G4P-H F7 Bag / G4 Panel 2000 876 600 115
XBC75-F7B/G4P-HR F7 Bag / G4 Panel 2000 876 600 115
XBC85-F7B/G4P-HR F7 Bag / G4 Panel 2000 876 600 115
XBC75-G4B-H G4 Bag 2000 1001 600 115
XBC85-G4B-H G4 Bag 2000 1001 600 115
XBC75-G4B-HR G4 Bag 2000 1001 600 115
XBC85-G4B-HR G4 Bag 2000 1001 600 115
XBC75-F7B/G4P-HWP F7 Bag / G4 Panel with weather roof 2000 876 600 117
XBC85-F7B/G4P-HWP F7 Bag / G4 Panel with weather roof 2000 876 600 117
XBC75-F7B/G4P-HRWP F7 Bag / G4 Panel with weather roof 2000 876 600 117
XBC85-F7B/G4P-HRWP F7 Bag / G4 Panel with weather roof 2000 876 600 117
XBC75-G4B-HWP G4 Bag with weather roof 2000 1001 600 117
XBC85-G4B-HWP G4 Bag with weather roof 2000 1001 600 117
XBC75-G4B-HRWP G4 Bag with weather roof 2000 1001 600 117
XBC85-G4B-HRWP G4 Bag with weather roof 2000 1001 600 117
Weather Kit
Weather Terminal
Filter & Module Options

22. 01. 18. Leaflet Number 671730 7
XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
Ref No. 4 Unit Code Description Dimensions (mm) Weight
Width Height Length (kg)
XBC75-H-MD24V Motorised dampers 24V for Ecosmart models (CO) 840 700 165 20
XBC85-H-MD24V Motorised dampers 24V for Ecosmart models (CO) 840 700 165 20
XBC75-H-MD-NC Damper no actuator with extended spindle 840 700 165 20
XBC85-H-MD-NC Damper no actuator with extended spindle 840 700 165 20
Ref No. 4 Unit Code Description Dimensions (mm) Weight
Width Height Length (kg)
XBC75-H-SIL900 Side by side silencer with base frame 2000 876 900 180
XBC85-H-SIL900 Side by side silencer with base frame 2000 876 900 190
XBC75-H-SIL900-WP Side by side silencer with base frame and weather roof 2000 1001 900 180
XBC85-H-SIL900-WP Side by side silencer with base frame and weather roof 2000 1001 900 190
Ref No. 6 Unit Code Description Dimensions (mm) Weight
Width Height Length (kg)
XBC75-FCL-LAT-H LPHW side by side module with base frame for Ecosmart control units (AT) 2000 876 600 113
XBC85-FCL-LAT-H LPHW side by side module with base frame for Ecosmart control units (AT) 2000 876 600 113
XBC75-FCL-RAT-H LPHW side by side module with base frame for Ecosmart control units (AT) 2000 876 600 155
XBC85-FCL-RAT-H LPHW side by side module with base frame for Ecosmart control units (AT) 2000 876 600 155
XBC75-FCE-LAT-H Electric side by side module with base frame for Ecosmart control units (AT) 2000 876 600 113
XBC85-FCE-LAT-H Electric side by side module with base frame for Ecosmart control units (AT) 2000 876 600 113
XBC75-FCE-RAT-H Electric side by side module with base frame for Ecosmart control units (AT) 2000 876 600 121
XBC85-FCE-RAT-H Electric side by side module with base frame for Ecosmart control units (AT) 2000 876 600 121
Dampers
2x Matching Silencers (Side by side and supplied as one piece)
Frost Coils (Side by side and supplied as one piece)
Above is an indicative list of XBC75 & 85 ancillaries, for further details please contact Nuaire.
Note: Codes with ‘R’ i.e. (XBC75-G4B-HR) refer to right hand unit versions.

XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
nuaire.co.uk 029 2085 8200
5.0 XBC 75 & 85 Horizontal (CO) Spare Parts
Ensure correct model is selected.
XBC75 – Horizontal
Part No. Description
XBC75-H-FILTERKIT Replacement G4 panel filters x 4
776187 Replacement Blower assembly x 1
XBC85 – Horizontal
Part No. Description
XBC85-H-FILTERKIT Replacement G4 panel filters x 4
776199 Replacement Blower assembly x 1
IMPORTANT
Isolation - Before unit panels are removed make sure that the unit is
isolated.
IMPORTANT
Caution - Blower Weight
XBC75 - 18kg
XBC85 - 37kg
Blower assemblies.
slide out to replace
Supply panel filters.
Remove retaining plate &
slide filters out to replace
Remove 4 x fixings &
Extract panel filters.
Remove retaining plate &
slide filters out to replace
Figure 6. Replacing filters and blower assembly

22. 01. 18. Leaflet Number 671730 9
XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
6.0 XBC 75 & 85 Vertical Ecosmart Adapt (Trend)
(AT) Control Models
The information contained in this document provides details of
installation, operation and maintenance for installers and users of
the XBOXER XBC75 & 85 Supply and Extract Ventilation Units with
Heat Recovery.
This supply and extract air handling unit range comprises an
combination of high efficiency centrifugal fans with EC motors, a
counterflow design plate heat exchanger, filters, optional heaters
(LPHW and Electric) and a casing with high mass acoustic treatment.
The one-piece ventilation unit shall be constructed with double
skinned Aluzinc panels on an aluminium Pentapost frame with integral
acoustic mineral fibre ensuring low breakout noise levels. The unit
shall incorporate a high efficiency aluminium counterflow plate heat
exchanger matrix with a thermal efficiency of up to 92%, fitted with
a segmented 100% bypass facility and actuator (patent app. for)
operating under automatic control.
A range of matched, side by side internal and external attenuators
(horizontal units) and double deck internal and external attenuators
(Vertical units) with a similar construction method to that of the unit is
available.
General information regarding performance and specifications for the
equipment may be obtained from our Technical Literature, and / or
project specific documentation.
Code description: XBOXER XBC Ventilation Unit
XBC 75 - V - LAT - R - WP
| | | | | | |
1 2 3 4 5 6 7
1. XBOXER XBC Range
2. Unit size 75 & 85
3. V = Vertical Stacked layout
4. N = No Heater
L = LPHW Heater
E = Electric Heater
5. AT = Adapt (Trend)
6. R = Opposite arrangement
7. WP = Separate Matched Weather Roof if required
Code description: Matched Attenuator
XBC 75 - V - SIL900
| | | |
1 2 3 4
1. XBOXER XBC Range
2. Unit size 75 & 85
3. V = Vertical Attenuator
4. SIL900 = 900mm Attenuator
SIL900WP = 900mm Attenuator with roof
Figure 7. Layout Overview of the XBC vertical unit, with side removed.

XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
nuaire.co.uk 029 2085 8200
7.0 XBC 75 & 85 Vertical Unit Access Concepts
All access panels are located
on one side of the fan unit
Note: Unit must be isolated before panels are removed.
Side view
Internal control
panel
Intake
Supply
Extract
Discharge
End view
access
G4 Panel Filter
Slide out fans
LPHW or Electric
Heater Battery (76mm) high
Base Frame 8mm outside dia. condensate drain.
Condensate pump fitted as standard
with alarm facility.
In this product range, several unique concepts have been
implemented with a view to simplifying the installation design.
7. The unit must be installed with at least 650mm clearance from a
wall / barrier. With this absolute minimum clearance, the unit may
be connected to the power supply and control connection.
1000mm clearance is required to remove the LPHW coil and electric
heater.
8. With this clearance, unit filters may be changed, and the fans coils,
heat exchanger and condensate tray may be inspected and cleaned
if necessary.
9. The LPHW and Electrical heater settings, coil bleed and drain, and
all other control adjustments are similarly accessible.
Figure 8. The unit must be installed with at least 650mm clearance from a wall / barrier to gain access from the side. Isolate before removing
panels.
Figure 9. Vertical unit access and configuration. Standard (left hand) unit shown.
10. Side access, where possible, is preferred in all cases in terms of safe
working access to the equipment under the CDM regulations.
11. Note however, that access in the situation is difficult and additional
time should be allocated. For convenience it is preferred that
wherever possible, this minimum access provision is not adopted,
and it is recommended that a minimum of around 600mm
clearance (as stated in ADF 2010) is allowed.
12. Where these arrangements are not suitable, the Consultant’s
and Contractor’s project specific requirements will always be
accommodated where possible.

22. 01. 18. Leaflet Number 671730 11
XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
8.0 XBC 75 & 85 Dimensions and Weights
8.1 XBC 75 & 85 Vertical (ES and BC) Unit Dimensions (mm) and Weights (kg)
Figure 10. Horizontal unit dimensions (mm) and weights (kg).
The unit is designed for side access as standard and must be installed with a minimum of clearance of 650mm from a wall or barrier.
This will provide access to filters, coil, fan, heat exchanger, condensate tray and pump.
All models: The weather roof is part of the unit code and is factory fitted only. Example: XBC85-V-LATWP.
*Includes unit and 76mm high base frame.
Unit Code Unit Dimensions (mm) Control Dimensions (mm) Unit Weights Packed Weights
A B C J F H W D (kg) (kg)
XBC75-V-*** 2500 954 1416* 610 894 60 954 2500 630 730
XBC85-V-*** 3000 1000 1676* 940 740 65 1000 3000 780 880

XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
nuaire.co.uk 029 2085 8200
3
1
5
2563
4
5
1
9.0 XBC 75 & 85 Vertical (CO) Ancillary Dimensions (mm) and Weights
Figure 11. Vertical unit ancillary key.
Ref No. 1 Unit Code Description Dimensions (mm) Weight
Width Height Length (kg)
XBC75-V-***WP Unit with weather roof 954 1476 2500 630
XBC75-V-***-RWP Unit with weather roof 954 1476 2500 630
XBC85-V-***WP Unit with weather roof 1000 1741 3000 780
XBC85-V-***-RWP Unit with weather roof 1000 1741 3000 780
Ref No. 2 Unit Code Description Dimensions (mm) Weight
Width Height Length (kg)
XBC75-RT Weather terminal for vertical unit 842 570 610 8
XBC85-RT Weather terminal for vertical unit 940 740 700 10
Ref No. 3 Unit Code Description Dimensions (mm) Weight
Width Height Length (kg)
XBC75-F7B/G4P F7 Bag / G4 Panel 954 1416 600 90
XBC85-F7B/G4P F7 Bag / G4 Panel 1000 1676 600 105
XBC75-F7B/G4P-R F7 Bag / G4 Panel 954 1416 600 90
XBC85-F7B/G4P-R F7 Bag / G4 Panel 1000 1676 600 105
XBC75-G4B G4 Bag 954 1416 600 90
XBC85-G4B G4 Bag 1000 1676 600 105
XBC75-G4B-R G4 Bag 954 1416 600 90
XBC85-G4B-R G4 Bag 1000 1676 600 105
XBC75-F7B/G4P-WP F7 Bag / G4 Panel with weather roof 954 1476 600 92
XBC85-F7B/G4P-WP F7 Bag / G4 Panel with weather roof 1000 1741 600 107
XBC75-F7B/G4P-RWP F7 Bag / G4 Panel with weather roof 954 1476 600 92
XBC85-F7B/G4P-RWP F7 Bag / G4 Panel with weather roof 1000 1741 600 107
XBC75-G4B-WP G4 Bag with weather roof 954 1476 600 92
XBC85-G4B-WP G4 Bag with weather roof 1000 1741 600 107
XBC75-G4B-RWP G4 Bag with weather roof 954 1476 600 92
XBC85-G4B-RWP G4 Bag with weather roof 1000 1741 600 107
Weather Kit
Weather Terminal
Filter & Module Options

22. 01. 18. Leaflet Number 671730 13
XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
Ref No. 4 Unit Code Description Dimensions (mm) Weight
Width Height Length (kg)
XBC75-V-MD24V Motorised dampers 24V for Ecosmart models (CO) 620 560 165 14
XBC85-V-MD24V Motorised dampers 24V for Ecosmart models (CO) 840 700 165 20
XBC75-V-MD-NC Damper no actuator with extended spindle 620 560 165 14
XBC85-V-MD-NC Damper no actuator with extended spindle 840 700 165 20
Ref No. 4 Unit Code Description Dimensions (mm) Weight
Width Height Length (kg)
XBC75-V-SIL900 Double deck silencer with base frame 954 1416 900 180
XBC85-V-SIL900 Double deck silencer with base frame 1000 1676 900 200
XBC75-V-SIL900-WP Double deck silencer with base frame and weather roof 954 1476 900 185
XBC85-V-SIL900-WP Double deck silencer with base frame and weather roof 1000 1741 900 205
Ref No. 6 Unit Code Description Dimensions (mm) Weight
Width Height Length (kg)
XBC75-FCL-LAT-H LPHW double deck module with base frame for Ecosmart control units (AT) 2000 876 600 113
XBC85-FCL-LAT-H LPHW double deck module with base frame for Ecosmart control units (AT) 2000 876 600 113
XBC75-FCL-RAT-H LPHW double deck module with base frame for Ecosmart control units (AT) 2000 876 600 113
XBC85-FCL-RAT-H LPHW double deck module with base frame for Ecosmart control units (AT) 2000 876 600 113
XBC75-FCE-LAT-H Electric double deck module with base frame for Ecosmart control units (AT) 2000 876 600 121
XBC85-FCE-LAT-H Electric double deck module with base frame for Ecosmart control units (AT) 2000 876 600 121
XBC75-FCE-RAT-H Electric double deck module with base frame for Ecosmart control units (AT) 2000 876 600 121
XBC85-FCE-RAT-H Electric double deck module with base frame for Ecosmart control units (AT) 2000 876 600 121
Dampers
2x Matching Silencers (Side by side and supplied as one piece)
Frost Coils (Side by side and supplied as one piece)
Above is an indicative list of XBC75 & 85 ancillaries, for further details please contact Nuaire.
Note: Codes with ‘R’ i.e. (XBC75-G4B-HR) refer to right hand unit versions.

XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
nuaire.co.uk 029 2085 8200
10.0 XBC 75 & 85 Vertical (CO) Spare Parts
Ensure correct model is selected.
XBC75 – Vertical
Part No. Description
XBC75-V-FILTERKIT Replacement G4 panel filters x 4
776187 Replacement Blower assembly x 1
XBC85 – Vertical
Part No. Description
XBC85-V-FILTERKIT Replacement G4 panel filters x 4
776188 Replacement Blower assembly x 1
IMPORTANT
Isolation - Before unit panels are removed make sure that the unit is
isolated.
IMPORTANT
Caution - Blower Weight
XBC75 - 18kg
XBC85 - 37kg
Extract panel filters.
Remove retaining plate &
slide filters out to replace
Blower assemblies.
slide out to replace
Supply panel filters.
Remove retaining plate &
slide filters out to replace
Remove 4 x fixings &
Figure 12. Replacing filters and blower assembly

22. 01. 18. Leaflet Number 671730 15
XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
IMPORTANT
Safety first! – Before commencing any work ensure:
• That all appropriate risk assessments have been carried out and the
required safety measures have been taken.
• That you understand the work required.
• That you are trained and competent to carry it out.
11.0 Delivery of Equipment
11.1 Receipt of equipment
All equipment is inspected prior to despatch and leaves the factory in
good condition. Upon receipt of the equipment an inspection should be
made and any damage indicated on the delivery note.
Particulars of damage and/or incomplete delivery should be endorsed
by the driver delivering the goods before offloading by the purchaser.
No responsibility will be accepted for damage sustained during the
offloading from the vehicle or on the site thereafter.
All claims for damage and/or incomplete delivery must be reported to
Nuaire within two days of receipt of the equipment.
11.2 Offloading and Handling from the delivery Vehicle
The weight of the unit modules and palletised items is displayed on
the unit rating plate or on the packaging. Some of the modules have
an ‘uneven’ weight distribution, and this will be indicated by labelling
where appropriate. Ensure that lifting and handling equipment is
adequately rated. Offloading and positioning of the equipment is the
responsibility of the purchaser.
Spreaders should be used when lifting with slings to avoid damage
to the casings. Care must be taken to ensure that slings are correctly
positioned to avoid crushing and twisting of the unit castings.
Where channels and/or support frames are bolted to the underside of
the unit casing, slings or fork-lift arms should be positioned to locate in
the apertures in the channels. If Lifting Eyes have been supplied / fitted
it is recommended that they are used.
CAUTION: The XBC75 & 85 fan units have an uneven weight
distribution, please refer to the unit labelling before Lifting /
offloading the unit.
11.3 Storage
The equipment must be stored in a dry, internal location. Ductwork
connection apertures shall be sealed against the ingress of dust, water
and vermin.
If the storage period is to exceed two months, contact Nuaire for
guidance on the appropriate “mothballing” procedures. Do not stack
units, modules or components.
12.0 Erection and Assembly
Units must be installed in accordance with good industry practice.
These units may only be mounted horizontally and must be fully
levelled in the horizontal plane.
The units are heavy, and should be mounted using suitable methods
of support. The supporting structure must be assessed for structural
suitability.
If these units are being fitted into a ceiling void a suitable support
structure must be provided under each unit, the baseframe provided is
‘NOT’ suitable for this purpose.
Heat recovery components and modules that incorporate cooling
coils may produce condensation during use. An insulated drip tray and
condensate pump is provided. The drain connection must be connected
to a suitable drainage point (see fig. 9. and 18 on page 8 and 15 for
details).
12.1 Condensate Pump Alarm
The condensate pump incorporates an alarm function. If the water
level in the condensate tray exceeds a maximum level (for example, as
a result of the discharge tube becoming blocked or frozen), the alarm
contact will open. This contact is internally connected to the heat
exchanger bypass actuator, and the unit will automatically be placed
into bypass mode, preventing further condensate production. Unit
operation will otherwise be unaffected.
Condensate pump specification
Maximum flow rate = 12 l/h
Maximum head = 20m Vertical, 100m Horizontal
Pipe Connection size (Condensate) XBOXER XBC = 8 mm
LPHW Coils, if fitted, are tested during manufacture to 16 Bar (using
dry compressed air). Coil and valve assemblies are similarly tested to 10
Bar. Operation of standard equipment is rated at PN6, if the intended
system requires higher operating pressures; please contact the Nuaire
Technical department for advice.
Electrical connections to the unit shall be made in accordance with the
appropriate product (see below); and installation wiring diagrams, and
shall use appropriately sized and rated cables.
Only the prepared apertures in the unit casing may be used for cable
entry. Do not drill or cut the unit casing for this purpose. Cable access
points are provided at the ends of the control enclosure.
If the control is rotated to aid connection of cables, please ensure that
sufficient flexibility is provided in the final connection run.
N.B. to avoid conflict with the unit access panels, it is
recommended that electrical and plumbing service connections to
the unit are run at 90 degrees to the main air flow axis.
Control circuit connections must be segregated (i.e. routed separately)
from power connections.
The unit rating label shows the maximum electrical load of the
equipment. Connections to the unit may include single phase supply
connections, and a variety of control circuits.
Only the prepared apertures in the unit casing may be used for cable
entry. Do not drill or cut the unit casing for this purpose.
The equipment must be earthed and earth-bonded. Means of local
isolation for maintenance purposes are generally required (by others).
Ensure that all mains connections are isolated.
Palletised.
Slings via spreaders fitted to unit with base frame.
Figure 13. Lifting
XBOXER XBC unit sections will be delivered to site in one section.
The unit will be labelled with the direction of air flow.
The direction convention must be observed during assembly.
The unit may only be operated in its intended horizontal
installation plane.
The unit must be fully levelled during installation (this is essential to
ensure that condensate drains correctly).
See page 6 and 13 for dimensions and weights.

XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
nuaire.co.uk 029 2085 8200
13.0 Commissioning and Setting to Work
(Note – not all of the components listed here are necessarily
included with the equipment supplied).
13.1 Filters
Remove filter access panels (observe and note airflow direction labels),
inspect filters for contamination with construction debris, replace as
necessary. Replace access panels.
Filter pressure drops will depend on actual flow rate and condition.
Observe and record filter pressure drops after performance
commissioning. Typically, filter “dirty” condition occurs when the initial
filter “clean” readings have been increased by 125Pa.
If filter manometers, pressure switches or indicators have been fitted,
they should be set or adjusted to reflect the commissioned system
operation.
13.2 Heating Coils LPHW
Observe the Flow and Return connection labels on the unit. Drain and
bleed valves are located on the coil (see fig 19). Other valves may be
required in the system pipe-work depending on the installation (by
others).
Where the wet system is at risk of frost damage, the addition of a
proprietary anti-freeze solution to the water is recommended. Note
that any frost protection offered by the unit’s integral control system
will not operate if the power supply to the unit is interrupted.
Ecosmart frost protection is activated on any Ecosmart unit fitted with
LPHW heating, when the outlet air temperature is 4ºC or below. The
unit reacts by shutting down the fan to prevent a ‘wind chill’ effect
reducing the temperature to a point whereby the coil could freeze
and burst. The unit will also drive open the LPHW valve to a fully open
position to allow full water flow through the coil and the main PCB
will close the ‘Heat demand’ contacts. These contacts could be used to
send a signal to activate the boiler and/or valve to open to provide heat
if not already doing so.
Piped connections should be made to the unit using appropriate
techniques, and all pipework must be independently supported. No hot
work is permitted within one metre of the unit.
Ensure that installed pipework runs do not prevent or restrict access to
the unit at any point.
The completed installation (including the connections within the unit,
as these may be disturbed during installation) shall be pressure tested
to the project engineer’s specification (This is a condition of the unit
warranty).
13.3 Electric Heaters
Heater Capacity: XBC75 – 3ph, 12Kw
XBC85 – 3ph, 18Kw
The Electric Heater requires a 3ph supply which is independent from
the main unit supply. Connections to be made through the low level
fixed panel. The Electric Heater may be withdrawn to allow access to
the Heater Controller without the need for wiring to be disconnected
(Ensure the mains supply is isolated before removing any access panels
and any adjustments are made to the Heater Controller).
13.4 Fan Sections
Access to the fan section is via lift off panels (see fig. 1 & 19).
For non-Ecosmart units, wiring to the fan motor / unit terminal box
should be mechanically protected and in made in accordance with the
details on the motor name plate and diagram attached to the unit.
With the unit electrically isolated, rotate the fan impeller / drive
manually, checking that it spins freely.
Check all fixings are secure.
Units must not be operated without all access panels in place – damage
to equipment or injury to personnel may result. Units must not be
operated unless control interlocks are in place – damage to equipment
may result.
Test run motor for condition and correct rotation.
Check that the correct current overloads are fitted and that the current
being drawn does not exceed the motor nameplate value. Excessive
current normally indicates that the ductwork system resistance is
different to design.
LPHW or electric heater
supply connections Control box
Access to condensate
tray and pump
Condensate drain
connection Ø 8mm push-fit
LPHW or electric heater
supply connections
Control box
Access to condensate
tray and pump
Condensate drain
connection
Ø 8mm push-fit
Fixed panel for
customer connections
Figure 14. Customer connections. Control side of horizontal
unit, showing coil and condensate connections.
Figure 15. Customer connections. Control side of vertical
unit, showing coil and condensate connections.
CONDENSATE ALARM
The condensate pump incorporates an alarm function.
If the water level in the condensate tray exceeds a maximum level (for example, as a result of the discharge tube becoming blocked
or frozen), the alarm contact will open. This contact is internally connected to the heat exchanger bypass actuator, and the unit will
automatically be placed into bypass mode, preventing further condensate production. Unit operation will otherwise be unaffected.

22. 01. 18. Leaflet Number 671730 17
XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
14.0 Description of Control - Software Strategy
14.1 Unit Contains The Following Controllable Items:
14.2 Enable Signal
•Inlet damper (if fitted).
•Extract damper (if fitted).
•Heat recovery & bypass damper.
•Heating coil.
•Cooling Coil
•Supply fan speed.
•Extract fan speed.
The unit can be enabled via the following methods:
• Software switch (ENABLE) via SDU, IQView4, IQView8 or network.
• Switched live (230VAC) input, PIR etc.
• Low voltage contact.
• Night cooling / summer free-cooling strategy.
• Scheduled via weekly calendar.
When the enable signal is removed, the unit will run on for a time defined by the
run-on set-point. If an electric heater is fitted, the fans will automatically run-on
for an extra 2 minutes, without heating, in order to dissipate residual heat.
14.3 Occupancy Control
14.4 Boost
14.5 Trickle Mode
When a Trend occupancy sensor is selected via UI4 & 5 software module, the
control will look for a Trend OCC-U sensor in the appropriate input.
An occupied signal will give an enable signal.
0V = Occupied
14V = Unoccupied
When the control receives a boost signal the fans will run at boost speed. Once
the signal is removed the fans will run on for a time defined by the boost run-on
set-point.
When trickle mode is active, the fans will run at their minimum speed even when
there is no enable signal. Heating and cooling will also function in this mode if
available.
14.6 CO Control
14.7 Supply Temperature Control
14.8 Frost Protection
14.9 Night Cooling / Summer Free Cooling
14.10 Alarms
14.10.1 CRITICAL ALARM (LATCHING)
14.10.2 Thermal Trip
14.10.3 Maintenance Alarms (Non-Latching)
When a CO2 sensor is selected via UI4 & 5 function knobs, and an enable signal
is received, ventilation will increase to reduce CO2 concentration the target
CO2 set-point. The target CO2 sensor set-point can be changed as one of the
commissioning set-points.
While an enable signal is present, this mode modulates heating, cooling &
heat exchanger bypass dampers with the aim of the supply air reaching the
temperature set-point. Please note that heating and cooling outputs will only
function if the HeatingType or CoolingType set-points are set to heating or
cooling options.
Should the internal temperature of the unit fall below a value defined in the
commissioning variables, the control will override all heating/cooling logic to
open the LPHW or CW control valves, if fitted. This is to allow any protective
flow through the heating/cooling coils. The supply fan will also stop and the
appropriate frost protection software module will enter an alarm state. This
period will last for a minimum of 5 minutes by default. The fault relay will also
open. Heat and cool demand relays will not operate but digital inputs “Frost
Protecting LPHW” or “Frost protecting CW” will enter an alarm state. Please
note that frost protection will only function if the HeatingType or CoolingType
set-points are set to LPHW or CW.
Once enabled in software, this routine uses an individual time schedule to cool
the fabric of the building at night using only the external air. This mode only
functions if the daytime temperature is above the set-point, cooling is possible
and if the cooling air is not too cold.
Once in critical alarm state the unit will drive all heating and cooling outputs
to 0V. Other functions continue as normal. The critical alarm is latched and
required manual reset to clear.
In case of software failure, as a final resort, the electric heater is protected by a
fail-safe thermal overload switch. This switch disables the heater controller once
the temperature reaches 80°C. When this occurs, the critical alarm will latch in
software.
Once the unit cools, the contactor will re-engage but the heater signal will
remain at 0V until the critical fault is reset in software or by power cycle.
Once in maintenance alarm state the only action taken is de-energising of the
fault relay. Once the trigger is removed, the alarm will reset automatically.
Causes of critical alarm:
• Fan fail via alarm circuit 1.
• Heater overtemp via alarm circuit 1.
Causes of maintenance alarm:
•Condensate pump fault via alarm circuit 2 (This bypasses the heater
exchanger automatically).
•Sensor failure.
•Low supply temperature, default 8°C.
•Frost protection routine active, default 4°C (Only runs if water valves are
selected as fitted).
•Excessively high supply temperature reading (this will stop heating).
•Filter fault
All alarms have a hold off period set by the set-point “Alarm delay”.
The system incorporates a web enabled Trend IQ422/12/LAN/BAC/230
controller.

XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
nuaire.co.uk 029 2085 8200
Point Name Description Range Default
ENABLE Software enable switch Off / On Off
RUNONTIME Run-on timer value 0 - 3600 Seconds 0
TRICKLEMODE When on, fans will trickle even with no enable signal Off / On Off
SETTEMP Desired temperature set-point 10°C to 30°C 22
DEADBAND Dead-band for temp control 0.5°K to 10°K 3
BOOST Software boost switch Off / On Off
BOOSTRUNON Boost run on 0 - 3600 Seconds 0
FROSTPROTEMP Temperature, below which, any water valves will be overridden open -40°C to 10°C 4
MINFROSTPROTECTPERIOD Minimum time frost protection will be enabled 0 - 600 Seconds 300
DAMPERDELAY Startup delay to allow I/o dampers to open 0 - 300 Seconds 0
ALARMDELAY Alarm hold-off delay 0 - 20 Seconds 5
HIGHAIRTEMPALARM High supply air temp alarm temperature 30°C to 70°C 50
LOWTEMPALARM Low supply air temp alarm temperature -40°C to 20°C 8
FORCESTOPONLOWTEMP Stops fans upon LOWTEMPALARM Off / On Off
ALARMRESET Resets any latched alarms (Resets to Off Automatically) Off / On Off
SUPPLYFANMAX Individual fan maximum speed settings 20 - 100% 100
SUPPLYFANMIN Individual fan minimum speed settings (trickle speed) 0 - 100% 20
EXTRACTFANMAX Individual fan maximum speed settings 20 - 100% 100
EXTRACTFANMIN Individual fan minimum speed settings (trickle speed) 0 - 100 % 20
SUPPLYFANBOOST Supply fan boost speed 20 - 100% 100
EXTRACTFANBOOST Extract fan boos speed 20 - 100% 100
SUPPLYFANSTARTVOLTAGE The voltage threshold of passing 0% rotational speed 0 - 5V 1
EXTRACTFANSTARTVOLTAGE The voltage threshold of passing 0% rotational speed 0 - 5V 1
SUPPLYFANVOLTAGELIMIT The maximum voltage to be supplied to the fan motor 6 - 10V 10
EXTRACTFANVOLTAGELIMIT The maximum voltage to be supplied to the fan motor 6 - 10V 10
CO2TARGET The target set-point for CO2 control 0 - 10000 PPM 650
CO2RANGEMIN The lower limit CO value corresponding to the limit voltage 0 - 10000 PPM 0
CO2VOLTAGEMIN The lower limit voltage corresponding to the limit of range 0 - 10 VDC 0
CO2RANGEMAX The upper limit CO value corresponding to the limit voltage 0 - 10000 PPM 2000
CO2VOLTAGEMAX The upper limit voltage corresponding to the limit of range 0 - 10 VDC 10
CO2-LOOPGAIN CO Loop Gain 0 to -30 -0.5
CO2-LOOPINTEGRAL CO Loop Integral 0 to 30 10
CO2-LOOPDERIVATIVE CO Loop derivative 0 to 30 0

22. 01. 18. Leaflet Number 671730 19
XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
Point Name Description Range Default
SUMMERNIGHTFREECOOLACTIVE Set night cooling mode as active Off / On Off
SUMMERNIGHTFREECOOLMINTEMP Night cooling lower cut-off temperature 5°C to 30°C 10
SUMMERNIGHTFREECOOLFANSPEED Night cool fan speed 20 to 100 % 80
STC-COOLLOOPGAIN Supply Temp Control - Cool Loop Gain 0 to -30 -5
STC-COOLLOOPINTEGRAL Supply Temp Control - Cool Loop Integral 0 to 30 2
S TC-COOLLOOPDERIVATIVE Supply Temp Control - Cool Loop Derivative 0 to 30 0
2STC-HEATLOOPGAIN Supply Temp Control - Heat Loop Gain 0 to -30 -5
STC-HEATLOOPINTEGRAL Supply Temp Control - Heat Loop Integral 0 to 30 2
STC-HEATLOOPDERIVATIVE Supply Temp Control - Heat Loop Derivative 0 to 30 0
HEATINGTYPE Heating Type 0=None, 1=LPHW, 2=Electric 0 - 2 0
COOLINGTYPE Cooling Type 0=None, 1=CW, 2=DX 0 - 2 0
UI4FUNCTION Input 4 Function, 0 = None, 1 = CO2/T/D, 2 = Trend Occ, 3=FSC 0 - 3 0
UI5FUNCTION Input 5 Function, 0 = None, 1 = CO2/T/D, 2 = Trend Occ, 3=FSC 0 - 3 0
TACHOFITTED Is a tacho signal monitor PCB fitted? Off / On Model Dependant
SOFTWAREVERSION Shows the software number & Version N / A 0
FANANDHEATERTEST Factory Use Only (This resets on power cycle) Off / On Off
WIRINGVERIFICATION Factory Use Only (This resets on power cycle) Off / On Off
FORCEOVERHEAT Factory Use Only (This resets on power cycle) Off / On Off
DAMPERBYPASS Force bypass damper into bypass mode (This resets on power cycle) Off / On Off
DAMPEROUTOFBYPASS Force bypass damper out of bypass mode (Pump failure or
DAMPERBYPASS switch will override this) (This resets on power cycle) Off / On Off
F ANDAMPERTEST Factory Use Only Off / On Off

XBOXER XBC ECOSMART ADAPT (TREND) CONTROL (AT)
nuaire.co.uk 029 2085 8200
14.11 Sensors and Touch Screens
To help you select the appropriate control solution for your application, simply refer to one of the options below.
For the full range and technical details, please visit www.nuaire.co.uk
Thermistor Temerature Sensors
Low cost thermistor sensors comprising insertion, clamp-on, and outside air
versions. The insertion sensor may be used for duct or immersion purposes.
It has a 6mm diameter brass probe which is suitable for retrofit immersion
applications and will fit most existing pockets (universal fitting kit option).
Code: TB/TI/S - For duct or immersion use. Short 150mm.
TB/TI/L - For duct use only. Long 400mm.
Features
•Low cost
•High quality thermistors
•Brass probes
•M20 conduit entry with M16 cable gland
•IP67 housing
•Quarter turn quick release lid
•Easy to wire
•Universal kit option for retrofit of immersion sensors
•Adjustable insertion depth flange option for duct sensors
Code: HT/D - Ductand thermistor sensor (+/-3%)
Features
•Pre-calibrated for ease of commissioning
•IP65
•Operates over 10 to 100% RH non-condensing
•± 3% accuracy versions
•2 part connectors for ease of installation
•Humidity sensor element protected by replaceable filter
•Capacitive humidity sensing element provides excellent long term
stability
•Adjustable depth duct mounting flange option
Code: CO2/T/D - For duct or immersion use. Short 150mm.
CO2/T/S - Space carbon dioxide concentration and temperature sensor.
Features
•Low cost, high quality thermistor temperature sensor
•Humidity monitoring option for space sensor
•Optional digital display for space sensor
•M20 conduit entry with M16 cable gland
•IP67 housing (duct sensor)
•Quarter turn quick release lid (duct sensor)
•Two part terminals to facilitate wiring
•24 Vac/dc supply
•Adjustable depth duct mounting flange option
Code: OCC/UD/DC - Ultrasonic detector, adjustable in 1 direction.
OCC/UDA/DC - Ultrasonic detector, adjustable in 2 directions sensor.
Features
•Monitors occupancy over approximately 5 m diameter floor space
•Fully automatic system operation
•Direct connection to IQ Controllers
•Lights never go off when needed (even detects hand movements)
•IP67 housing
•Quarter turn quick release lid
•Simple low cost installation
•Extendable coverage of up to 10 detectors per IQ input
•Corridor linking facility
Duct Humidity & Temperature Sensors
Duct mounted relative humidity and temperature sensors for HVAC
applications.
The certified 2% high accuracy (/2%) and standard 3% versions offer excellent
linearity and stability over a wide humidity range (10 to 90 %RH).
CO Sensors
The CO duct and space sensors monitor the carbon dioxide concentration
and temperature of the air. The space sensors have additional options of
humidity monitoring and a 4 digit display. The display will show the measured
values in succession. The duct sensor has a quick-release lid to facilitate
installation.
Occupancy Sensors
The ceiling mounted OCC/U Ultrasonic Occupancy Detection System is
specifically designed for combined HVAC and lighting control in open plan
office environments.
Touch Screens
SDU Display
(10 x 6 inch).
RD/SDU-IQ2COMMSCABLE/3m – RJ11 plug
to RJ11 plug cable (3m) for SDU.
IQVIEW4 Touch Screen Display
(6 x 4 inch). FPK/Plate - Mounting Plate
IQVIEW4/SM Box - Surface mount box
for wall or panel.
Transformer for IQVIEW4 included.
ACC/24V - 230/24 VAC, 36VA
IQVIEW8 Touch Screen Display
(10 x 6 inch).
IQVIEW8/SM Box - Surface mount box
for flat surfaces
Transformer for IQVIEW8 included.
ACC/24V - 230/24 VAC, 36VA
Other manuals for XBOXER XBC Series
4
This manual suits for next models
16
Table of contents
Other NuAire Control Unit manuals