
817. 06. 15. Leaflet Number 671424
Installation, Operatin and Maintenance Instructions XBOXER Run Around Coil
W r ng (cont nued)
The system’s response to a 0-10V dc BMS si nal
is iven in the table below.
Note the BMS si nal will override any sensors
and user control connected in the system. The
volta e tolerance is +/_ 125mV and is measured
at the fan’s terminal.
Vent lat on mode Cool ng mode* Heat ng mode*
Local control 0.00 --
OFF / trickle 0.25 --
Speed 1 0.50 0.75 1.00
Speed 2 1.50 1.75 2.00
Speed 3 2.50 2.75 3.00
Speed 4 3.50 3.75 4.00
Speed 5 4.50 4.75 5.00
Speed 6 5.50 5.75 6.00
Speed 7 6.50 6.75 7.00
Speed 8 7.50 7.75 8.00
Speed 9 8.50 8.75 9.00
Speed 10 9.50 9.75 10.00
* Only ava lable on relevant un t.
5.0 Comm ss on ng & Sett ng to work
(Note – not all of the components l sted here are necessar ly
ncluded w th the equ pment suppl ed).
5.1 Dampers (shut-off, solat on and
face/bypass)
Check the free action of the damper blades before powered
operation (the actuator has a ear release button).
Check that the actuator operates freely and over the correct ran e.
5.2 M x ng Boxes
Mixin box dampers should be checked as in 4.1 and should be
adjusted / set up to ive the required airflows throu h each le .
5.3 F lters
Remove filter access panels (observe and note airflow direction
labels), inspect filters for contamination with construction debris,
replace as necessary. Replace access panels.
Filter pressure drops will depend on actual flow rate and condition.
Observe and record filter pressure drops after performance
commissionin .
Typically, filter “dirty” condition occurs when the initial filter
“clean” readin s have been increased by 125Pa.
If filter manometers, pressure switches or indicators have been
fitted, they should be set or adjusted to reflect the commissioned
system operation.
5.4 Heat ng & Cool ng Co ls
Water
Water coils should be connected to ensure that full counter flow
exists i.e. - the enterin airflow meets the return connection.
All water coils should be connected with the flow at the bottom
and the return at the top unless otherwise advised.
Drain and bleed valves are located on the coil, others may be
required in the system pipe-work dependin on the installation.
Frost protection must be incorporated on shut down and fresh air
conditions to avoid coil freezin . The Ecosmart control system if
fitted, includes temperature sensin and frost protection
strate ies. Ideally, where the system is at risk of frost dama e,
the addition of a proprietary anti-freeze solution to the water is
recommended.
Where Ecosmart heatin / coolin controls are provided, the coil
is pre-fitted with a 3 / 4 port valve and actuator housed in the
casin extension.
Pipe-work connections should be made to the unit usin appropriate
techniques, and must be independently supported. The connections
should be pressure tested.
DX
Direct expansion coils must be fitted with a correctly sized
thermostatic expansion valve with an external equalisin connection.
The expansion valve phial must be fitted between the suction
header connection and the equalisin line. The recommendations
of the TE valve manufacturer should be referred to when locatin
the phial and adjustin the superheat. In all cases, settin s should
be in accordance with the recommendations of the manufacturer
of the refri eration equipment.
All coolin coil drains must be connected to the slopin drain with
a correctly sized trap runnin to an open tundish or similar.
Note: ES-TC must be used n conjunct on w th DX.
5.5 Electr c Heaters
Remove control access panel to permit site wirin to the Ecosmart
heatin controller, or directly to the heatin elements.
Elements have threaded connection points for linkin elements
and site wirin . Elements should be linked with reference to the
appropriate wirin dia ram, and the maximum available element
power combination may be decreased if required. Always maintain
a balanced load on three phase systems.
Cable entry must be made throu h the apertures provided.
Screwed lands with cable restraint devices should be used.
PVC or similar cables must not be used inside the heater unit –
due to the temperatures that may be experienced.
Units with Ecosmart electric heatin controls incorporate a fan
run-on facility and overheat / fan failure protection.
In non-Ecosmart units, heaters are fitted with an over-heat cut-out
that must be wired into the control system.
It is stron ly recommended that an airflow switch is incorporated
within the control system with a fan run on timer (15 minutes) and
an interlock provided between the heater contactor and fan motor
starter – to allow elements to cool on shutdown.
Nuaire will accept no liability for dama e caused by an inadequate
control system.
All heaters must be wired in accordance with IEE re ulations and
conform to local and national statutory requirements. The element
tray s a ma ns carry ng component and must be earthed.
5.6 Fan Sect ons
Access to the fan section is via lift off panels. Cable entry must be
made throu h the apertures provided. Screwed lands with cable
restraint devices should be used.
For units with Ecosmart controls, the fan motors and failure
protection devices are pre-wired to the control assembly.
For non-Ecosmart units, wirin to the fan motor / unit terminal
box should be mechanically protected and in made in accordance
with the details on the motor name plate and dia ram attached to
the unit.
For star delta startin , all links should be removed from the motor
terminal box and the motor wired as per the instructions supplied
with starter.
With the unit electrically isolated, rotate the fan impeller / drive
manually, checkin that it spins freely. Check all fixin s are
secure.
Units must not be operated without all access panels in place –
dama e to equipment or injury to personnel may result.
Units must not be operated unless control interlocks are in place –
dama e to equipment may result. Test run motor for condition and
correct rotation.
Check that the correct current overloads are fitted and that the
current bein drawn does not exceed the motor nameplate value.
Excessive current normally indicates that the ductwork system
resistance is different to desi n.
Fi ure 20.