OPTICAL SMOKE DETECTOR
18-30V DC
150µA for 50 sec
103 (diam.) x 48 (height) mm
0.120dB/m
Alarm LED
To panel / to external LED driver (BS-572)
20-30mA
IP20
EN 54-7
50µA
o
-10 to 60 C
Up to 95%
2 years
160gr.
TECHNICAL CHARACTERISTICS
BS-655
START UP POWER CONSUMPTION
STAND BY POWER CONSUMPTION
ALARM POWER CONSUMPTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
DEGREES OF COVER PROTECTION
OPERATION VOLTAGE
RELATIVE HUMIDITY
TYPICAL WEIGHT
EXTERNAL DIMENSIONS
GUARANTEE
SENSITIVITY
INDICATORS
OUTPUT
921655000_23_018
Page 1 from 2
GENERAL
Beforeinstallingthedetector, the user must read these instructions
carefullyandstorethismanualforfuture reference.
The detectorsBS-655werecreatedtoofferquickdetectionincase
offire.
They have two parts, one plastic base which is installed on the
ceiling and the main unit of the detector which is fastened to the
base by a simple turning to the right. The detectors have an
indication led which lights continuously in case of fire detection
until there is a reset signal from the panel. The indication led also
flashes every 4 sec to indicate good operation. These detectors
can cooperate with conventional fire alarm panels like BS-632 and
BS-636.
OPERATIONCHECK
The operation check can be done by spraying a small amount of
smokeinto the detector’schamber.You can use the special smoke
deviceA-752ofourcompany,orasimilardevice.
It is advised to conduct a good operation test every 6 months and
everytimethedetector positionischanged.
It is essential to have good air circulation inside the detector.
Therefore care must be taken so that the vents of the detector are
notcovered.
NOTE
The detectors must be placed in the ceiling on visible areas with no
side obstacles and away from sides with no air circulation or strong
2
aircurrentsandvapors.Eachdetectorcoversalmost50m andthe
distance between two detectors must not exceed 15m. Also the
detectors must be placed away from fluorescent tubes at least 50
cm.2
Thecablescrosssectionmustbefrom0.5to1.5mm .
ATTENTION!!
After the device is installed, care must be taken, so that the
detectorvents arenotblocked by anything(i.e. dust,paint).Failing
to do so will prevent the smoke particles to enter the detection
chamber.
After the installation, it is the sole responsibility of the
user to maintain the detector for good operation.
Certification
The optical smoke detector BS-655 is certified from
LPCB. Also LPCB controls the production under CPR
number:
ΚΟLINDROS
PIERIAS
60061
GREECE
BS-655
Optical smoke detector 0832
0832-CPR-F0122 95
EN-54-7
Thank you for your trust in our products.