GENERAL
The user have to read carefully the following instructions, in order to be properly informed and keep them
for future use.
The BSR-6157 is an analogue addressable smoke detector which integrates functions of optical smoke
and heat detection and it can work with any fire panel supports Olympia A Protocol. It can be adjusted to
detect multiple levels of smoke and heat offering flexibility and rich functionality. Also, it integrates a short
circuit isolation circuit which is automatically activated and disconnects the defective node from the
remaining loop, allowing it to be located by the panel.
The detector sends to the main panel an analogue value which depends on the concentration of smoke
and heat. The value is 100 in concentration of 0.107dB/m (small amount of smoke) or a temperature of
o o
57 C and increases proportionally to 120 in concentration of 0.300dB/m or a temperature of 90 C. When a
sudden increase in temperature is detected the detector sends the value of 121.
By default the panel is set to sound an alarm when the concentration of smoke is 0.107dB/m or the
temperature is 57 C. The user can change this setting from the panel for each detector and define any
level of smoke concentration or temperature between the lower and the upper limits, specifying the
sensitivity of the system depending on the requirements of each site. Also, the user can select A1R or A2S
working mode through the panel.
They are composed by two parts. A plastic base which is placed on the ceiling and the main body of the
o
detector which fits on the plastic base with a simple rotation to the right. The detectors have a 360 visible
led and a remote led driver which are light up constantly in case of detection of fire, till cancelled from the
panel. Also, they are staying lit even if the sirens are silenced from the panel, so the detector which
o
140μΑ
11-30V DC
TEMPERATURE SENSITIVITY
SMOKE CONCENTRATION SENSITIVITY
1A
5A
IP42
100mΩ
2.5mA (with activated LED)
Adjustable from 0.107 to 0.300 in 0.010 dB/m steps
Adjustable from 57 to 90 in 1.5 steps oC
10.7 - 12.7
9.3 - 10.6
Up to 95%
ο
-40 to 70 C
ABS/PC
160 gr.
103 (d) x 55 (h) mm
2 years
Remote LED driver
Alarm LED
INDICATORS
OUTPUT
Analogue addressable optical smoke and
rate-of-rise heat detector with integrated isolator
TECHNICAL CHARACTERISTICS
MAIN VOLTAGE
STANDBY CONSUMPTION
ALARM CONSUMPTION
MAXIMUM LOOP CURRENT (Ic max, -L in/out)
MAXIMUM SWITCH CURRENT (Is max, -L in/out)
MAXIMUM SERIES RESISTANCE (Zc max, -L in-out)
MAXIMUM LEAKAGE CURRENT
IN ISOLATION MODE (I max, -L in/out)L
ISOLATION VOLTAGE (Vso min-max)
RECONNECT VOLTAGE (Vsc min-max)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATING TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
25mA pulses (6ms duration every 2sec)
Thank you for your trust in our products
Olympia Electronics - European manufacturer
EN 54-5 EN 54-7 EN 54-17, ,
CLASS A1R/A2S
Olympia A ProtocolCOMMUNICATION PROTOCOL