E5AK-T/E5EK-T E5AK-T/E5EK-T
CHARACTERISTICS
Indication accuracy
Thermocouple (±0.3% of indication value or ±1°C, whichever greater) ±1 digit max.
(See Note 1.) Platinum resistance
thermometer (±0.2% of indication value or ±0.8°C, whichever greater) ±1 digit max.
Analog input ±0.2% (of indication value) ±1 digit max.
Hysteresis 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P) 0.1% to 999.9% FS (in units of 0.1% FS)
Integral (reset) time (I) 0 to 3,999 s (in units of 1 s)
Derivative (rate) time (D) 0 to 3,999 s (in units of 1 s)
Control period 1to99s(inunitsof1s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range --1,999 to 9,999 or --199.9 or 999.9 (decimal point position dependent on
input type or result of scaling)
Set time 0to99hrs59minor0to99min59s
Program capacity 8 patterns (E5AK-T) or 4 patterns (E5EK-T), 16 steps
Programming method Time or ramp setting method
Time accuracy ±0.2% (±500 ms) of the set value
Sampling period
Temperature input 250 ms
(See Note 2.) Analog input 100 ms
Insulation resistance 20 MΩmin. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Vibration resistance Malfunction: 10 to 55 Hz, 10 m/s2(approx. 1G) for 10 min each in X, Y,
and Z directions
Destruction: 10 to 55 Hz, 20 m/s2(approx. 2G) for 2 hrs each in X, Y, and
Z directions
Shock resistance Malfunction: 200 m/s2min. (approx. 20G), 3 times each in 6 directions
(100 m/s2(approx. 10G) applied to the relay)
Destruction: 300 m/s2min. (approx. 30G), 3 times each in 6 directions
Ambient temperature Operating -- 1 0°Cto55°C(14°F to 131°F) with no icing
and 3-year warranty period: --10°Cto50°C(14°F 122°F)
Storage -- 2 5°Cto65°C(--13°F to 149°F) with no icing
Ambient humidity Operating 35% to 85%
Enclosure ratings Front panel NEMA4 for indoor use (equivalent to IP66)
Rear case IEC standard IP20
Terminals IEC standard IP00
Memory protection Non-volatile memory (number of writings: 100,000 operations)
Weight E5AK-T approx. 450 g
E5EK-T approx. 320 g
Mounting bracket approx. 65 g
(This table continues on the next page.)
Note: 1. The indication accuracy of the K1, T, and N thermocouples at a temperature of -100°Cmax.is±2°C±1 digit maximum. The
indication accuracy of the U and L thermocouples at any temperature is ±2°C±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400°C max. is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200°Cmax.is±3°C±1 digit maximum.
The indication accuracy of the W thermocouple at any temperature is (±0.3% of the indicated value or ±3°C, whichever is
greater) ±1 digit maximum.
The indication accuracy of the PL
thermocouple at any temperature is (±0.3% of the indicated value or ±2°C, whichever is
greater) ±1 digit maximum.
2. The sampling period of the standard model with CT and remote SP inputs is 250 ms.