Omron E5AK-T User manual


Ramp/Soak Process Controller E5AK-T/E5EK-T
Advanced Ramp/Soak Process
Controllers Ideal for Worldwide Use
E5AK-T offers up to eight patterns of
simple programming control (4 patterns
for E5EK-T), with 16 steps per pattern
Modular structure, one-stock type
High-accuracy: 100 ms sampling (for
analog input)
Conforms to international EMC and
safety standards.
IP66/NEMA4 (indoor use) front face
Serial communications (RS-232C,
RS-422 and RS-485) and transfer
output (4 to 20 mA)
Position-proportional control model is
offered
Heat/Cool control
24 V AC/DC types also available

Ordering Information
When ordering, order control output boards and option boards separately. Example: for a relay control output, order the E53-R output
board in addition to the standard Process Controller (E5AK-T/E5EK-T). Also specify the current transformer.

PROCESS CONTROLLERS
Item Description Part number
Base unit Standard model with terminal cover E5AK-TAA2-500 AC100-240
E5AK-TAA2-500 AC/DC24
Position-proportional model with terminal cover E5AK-TPRR2-500 AC100-240
E5AK-TPRR2-500 AC/DC24
Standard model with terminal cover E5EK-TAA2-500 AC100-240
E5EK-TAA2-500 AC/DC24
Position-proportional model with terminal cover E5EK-TPRR2-500 AC100-240
E5EK-TPRR2-500 AC/DC24
Note: 1. When using the heater burnout alarm function with a standard model, the linear output board cannot be used for the control
outputs (heat).
2. The Process Controller provides transfer outputs at 4 to 20 mA for the PV and other values and control outputs at 4 to 20 mA
for the current outputs.
E5AK-T/E5EK-T E5AK-T/E5EK-T

OUTPUT BOARDS
Item Description Part number
Output board Relay E53-R
SSR E53-S
Pulse (NPN) 12 VDC E53-Q
Pulse (NPN) 24 VDC E53-Q3
Pulse (PNP) 24 VDC E53-Q4
Linear (4 to 20 mA) E53-C3
Linear (0 to 20 mA) E53-C3D
Linear (0 to 10 V) E53-V34
Linear (0 to 5 V) E53-V35
Note: The Controller uses a dedicated, high-resolution output board. The E53-C current output board for the E5

X cannot be used with
the E5AK-T/E5EK-T Controller.

OPTION BOARD
Item Description Part number
Option board Event input E53-AKB
Communication (RS-232C) E53-AK01
Communication (RS-422) E53-AK02
Communication (RS-485) E53-AK03
Transfer output E53-AKF
Note: 1. The option board can be used either by the E5AK or E5EK.
2. The E5AK-T allows a maximum of three option boards to be mounted. Refer to the
Operations
Section for mounting combina-
tions. The E5EK-T allows only one option board to be mounted.

ACCESSORIES (ORDER SEPARATELY)
Current Transformer
Item Hole diameter Part number
Current transformer (See Note.) 5.8 mm E54-CT1
(
)
12.0 mm E54-CT3
Note: No CT is required unless the heater burnout alarm function is used.
Terminal Cover
Item Connectable models Part number
Terminal cover E5AK E53-COV0809
E5EK E53-COV08
Unit Label
Item Part number
Unit label Y92S-L1
E5AK-T/E5EK-T E5AK-T/E5EK-T

TEMPERATURE RANGES
Platinum Resistance Thermometer
Input (See Note.) JPt100 Pt100
Range °C--199.9°to 650.0°--199.9°to 650.0°
g
°F--199.9°to 999.9°--199.9°to 999.9°
Setting (°C/°F) (main setting and alarm) 0 1
Note: Switch selectable.
Thermocouple
Input
(see note) K1 K2 J1 J2 T E L1 L2 U N R S B W PL

Range °C--200
to
1,300
0.0 to
500.0 --100
to
850
0.0 to
400.0 --199.9
to
400.0
0to
600 --100
to
850
0.0 to
400.0 --199.9
to
400.0
--200
to
1,300
0to
1,700 0to
1,700 100
to
1,800
0to
2,300 0to
1,300
°F--300
to
2,300
0.0 to
900.0 --100
to
1,500
0.0 to
750.0 --199.9
to
700.0
0to
1,100 --100
to
1,500
0.0 to
750.0 --199.9
to
700.0
--300
to
2,300
0to
3,000 0to
3,000 300
to
3,200
0to
4,100 0to
2,300
Resolution
(°C/°F)
(main setting
and alarm)
23456 78910 11 12 13 14 15 16
Note: Switch selectable: Setting number is factory-set to 2 (K1).
Thermocouple W is W/Re5-26 (tungsten rhenium 5, tungsten rhenium 26).
Current/Voltage
Input (See Note.) Current input Voltage input
(
)
4to20mA 0to20mA 1to5V 0to5V 0to10V
Range One of following ranges depending on results of scaling
--1999 to 9999
--199.9 to 999.9
--19.99 to 99.99
--1.999 to 9.999
Setting 17 18 19 20 21
Note: Switch selectable.
E5AK-T/E5EK-T E5AK-T/E5EK-T
Specifications

RATINGS
Model E5EK/AK-T (Standard) E5EK/AK-T (24 V Type)
Supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC/VDC, 50/60 Hz
Power consumption E5AK-T 16 VA 12 VA, 8 W
E5EK-T 15 VA
,
Operating voltage range 85% to 110% of rated supply voltage
Input Thermocouple K, J, T, E, L, U, N, R, S, B, W, PL

Platinum resistance
thermometer JPt100, Pt100
Current input 4 to 20 mA, 0 to 20 mA (Input impedance: 150 Ω)
Voltage input 1 to 5 V, 0 to 5 V, 0 to 10 V (Input impedance: 1 MΩ)
Control output Standard model According to Output Unit (see
Output Board Ratings and Characteristics
)
Position-proportional model
(See Note.) 2 Relay outputs: SPST-NO, 1 A at 250 VAC (including inrush current)
Auxiliary output SPST-NO, 3 A at 250 VAC (resistive load)
Control method ON/OFF or advanced PID control (with auto-tuning)
Setting method Digital setting using front panel keys or communications features
Indication method 7-segment digital display and LEDs
Potentiometer 100 Ωto 2.5 kΩ
Event input Contact input ON: 1 kΩmax.,
OFF: 100 kΩmin.
No-contact input ON: residual voltage: 1.5 V max.,
OFF: leakage current: 0.1 mA max.
Transmission output 4 to 20 mA, permissible load impedance: 600 Ωmax.,
resolution: approx. 2,600 steps
Current transformer input Connect only Omron Current Transformer (E54-CT1 or E54-CT3)
Additional functions Standard Manual output, heating/cooling control, SP limiter, loop burnout alarm, MV
limiter, MV change rate limiter, input digital filter, input shift, run/reset,
protect functions, scaling function
Approved standards UL 1092, CSA22.2 No. 14, CSA22.2 No. 1010-1
C
o
n
f
o
r
m
s
t
o
E
N
5
0
0
8
1
2
E
N
5
0
0
8
2
2
E
N
6
1
0
1
0
1
(
I
E
C
1
0
1
0
1
)
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/part 100
(
Fin
g
er Protection
)
,
when the separatel
y
-
C
o
n
f
o
r
m
s
t
o
V
D
E
0
1
0
6
/
a
r
t
1
0
0
(
F
i
n
g
e
r
P
r
o
t
e
c
t
i
o
n
)
,
w
h
e
n
t
h
e
s
e
a
r
a
t
e
l
y
-
ordered terminal cover is mounted.
Note: All control outputs are insulated from the input circuit.
E5AK-T/E5EK-T E5AK-T/E5EK-T

CHARACTERISTICS
Indication accuracy
(
S
N
t
1
)
Thermocouple (±0.3% of indication value or ±1°C, whichever greater) ±1 digit max.
y
(See Note 1.) Platinum resistance
thermometer (±0.2% of indication value or ±0.8°C, whichever greater) ±1 digit max.
Analog input ±0.2% (of indication value) ±1 digit max.
Hysteresis 0.01% to 99.99% FS (in units of 0.01% FS)
Proportional band (P) 0.1% to 999.9% FS (in units of 0.1% FS)
Integral (reset) time (I) 0 to 3,999 s (in units of 1 s)
Derivative (rate) time (D) 0 to 3,999 s (in units of 1 s)
Control period 1to99s(inunitsof1s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range --1,999 to 9,999 or --199.9 or 999.9 (decimal point position dependent on
input type or result of scaling)
Set time 0to99hrs59minor0to99min59s
Program capacity 8 patterns (E5AK-T) or 4 patterns (E5EK-T), 16 steps
Programming method Time or ramp setting method
Time accuracy ±0.2% (±500 ms) of the set value
Sampling period
(
S
N
t
2
)
Temperature input 250 ms
g
(See Note 2.) Analog input 100 ms
Insulation resistance 20 MΩmin. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Vibration resistance Malfunction: 10 to 55 Hz, 10 m/s2(approx. 1G) for 10 min each in X, Y,
and Z directions
Destruction: 10 to 55 Hz, 20 m/s2(approx. 2G) for 2 hrs each in X, Y, and
Z directions
Shock resistance Malfunction: 200 m/s2min. (approx. 20G), 3 times each in 6 directions
(100 m/s2(approx. 10G) applied to the relay)
Destruction: 300 m/s2min. (approx. 30G), 3 times each in 6 directions
Ambient temperature Operating -- 1 0°Cto55°C(14°F to 131°F) with no icing
and 3-year warranty period: --10°Cto50°C(14°F 122°F)
Storage -- 2 5°Cto65°C(--13°F to 149°F) with no icing
Ambient humidity Operating 35% to 85%
Enclosure ratings Front panel NEMA4 for indoor use (equivalent to IP66)
g
Rear case IEC standard IP20
Terminals IEC standard IP00
Memory protection Non-volatile memory (number of writings: 100,000 operations)
Weight E5AK-T approx. 450 g
g
E5EK-T approx. 320 g
Mounting bracket approx. 65 g
(This table continues on the next page.)
Note: 1. The indication accuracy of the K1, T, and N thermocouples at a temperature of -100°Cmax.is±2°C±1 digit maximum. The
indication accuracy of the U and L thermocouples at any temperature is ±2°C±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400°C max. is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200°Cmax.is±3°C±1 digit maximum.
The indication accuracy of the W thermocouple at any temperature is (±0.3% of the indicated value or ±3°C, whichever is
greater) ±1 digit maximum.
The indication accuracy of the PL

thermocouple at any temperature is (±0.3% of the indicated value or ±2°C, whichever is
greater) ±1 digit maximum.
2. The sampling period of the standard model with CT and remote SP inputs is 250 ms.
E5AK-T/E5EK-T E5AK-T/E5EK-T
Characteristics Table -- continued from previous page
EMC Emission Enclosure: EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
Immunity ESD: EN61000-4-2: 4 kV contact discharge
(level 2) 8 kV air discharge (level 3)
Immunity RF-interference: ENV50140: 10 V/m (amplitude
modulated, 80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
Immunity Conducted Disturbance: ENV50141:10 V (0.15 to 80 MHz)
(level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Approved standards UL1092, CSA22.2 No. 14, CSA22.2 No. 1010-1
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-or-
dered terminal cover is mounted.

OPTION BOARD RATINGS AND CHARACTERISTICS
Model Description Specifications
E53-AKB Event input Contact input:
ON: 1 kΩmax., OFF: 100 kΩmin.
No-contact input:
ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.
E53-AK01 Communications RS-232C Transmission method: Half-duplex
S
h
i
t
i
t
h
d
S
t
t
t
h
i
t
i
(
h
t
h
d
)
E53-AK02 RS-422 Synchronization method: Start-stop synchronization (asynchronous method)
B
a
u
d
r
a
t
e
:
1
2
/
2
4
/
4
8
/
9
6
/
1
9
2
k
b
p
s
E53-AK03 RS-485
B
au
d
ra
t
e:
1
.
2
/
2
.
4
/
4
.
8
/
9
.
6
/
1
9
.
2
k
b
ps
E53-AKF Transfer output 4 to 20 mA: Permissible load impedance: 600 Ωmax.;
Resolution: approx. 2,600 steps
Note: Event input is used for switching the target value, run or stop command, or automatic and manual mode with an external signal
input.

CURRENT TRANSFORMER RATINGS
Maximum continuous heater current 50 amps
Dielectric strength 1,000 VAC (for 1 min)
Vibration resistance 50 Hz, 98 m/s2(10G)
Weight E54-CT1 approx. 11.5 g
g
E54-CT3 approx. 50 g
Accessories (E54-CT3 only) Armature 2
(
y
)
Plug 2

HEATER BURNOUT ALARM
Max. heater current Single-phase 50 A VAC (See Note 1.)
Heater current value display accuracy ±5% FS±1 digit max.
Heater burnout alarm setting range 0.1 to 49.9 A (in units of 0.1 A) (See Note 2.)
Min. detection ON time 190 ms (See Note 3.)
Note: 1. Use the K2CU-F

A-

GS (with gate input terminals) for the detection of three-phase heater burnout.
2. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and always ON if the alarm is set to 50.0 A.
3. No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less
than 190 ms.
E5AK-T/E5EK-T E5AK-T/E5EK-T
Nomenclature

E5AK-T
Operation Indicators
•OUT1
Lit when the pulse output function
assigned to control output 1 turns
ON.
•OUT2
Lit when the pulse output function
assigned to control output 2 turns
ON.
•SUB1
Lit when the output function as-
signed to auxiliary output 1 turns
ON.
•SUB2
Lit when the output function as-
signed to auxiliary output 2 turns
ON.
•MANU
Lit when the manual operation
mode.
•RST
Lit when the operation is reset.
•RMT
Lit during remote operation.
•AT
Flashes during auto-tuning.
•HOLD
Lit when the program is on hold.
•WAIT
Lit when the program is waiting.
RUN/RST Key
Switches between RUN and RESET mode.
Display 1
Displays the process value or
parameter code.
Display 2
Displays the present SP, manip-
ulated variable, or parameter
settings.
Up Key/Down Key
Press to increase or decrease
the value on the No.2 display.
Pattern Number
Indicates the pattern number.
Display Key
Press to shift the display to the
next parameter.
Program Status Indicators
Bar Graph
Indicates the rate of pattern elapsing time at
the rate of 20% (5 levels) per one segment.
The top indicator indicates the rising step,
the middle indicator indicates the constant
step, and the bottom indicator indicates
the falling step.

E5EK-T
RUN/RST Key
Display Key
Display 1
Display 2
Operation indicators
Up Key/Down Key
E5AK-T/E5EK-T E5AK-T/E5EK-T
Operation
Note: Before changing any switch settings, always turn OFF the power supply to the Process Controller

SETTINGS
1. On a standard model, set up the output boards for control
outputs 1 and 2 before mounting the Controller.
2. On a position-proportional model, the relay output board is
already set, so this setup operation is unnecessary. (Do not
replace with other output boards.)
3. When setting up the output boards, remove the internal
mechanism from the housing and insert the output boards
into the sockets for control outputs 1 and 2.
Setting Up the Output Board
Removing the Output Board
To replace the output board, use a flat-blade screwdriver to push
up the output board.
Setting Up the Option Board
E5AK-T
1. Remove the power board and option boards in the order
shown in the following diagram.
2. Insert the option boards into the sockets for options 1 to 3.
The following diagram shows the relationship between the
option boards and mounting positions.
3. Mount the option boards and the power board in the
order shown.
E5AK-T/E5EK-T E5AK-T/E5EK-T
E5EK-T
1. Remove the power board and option boards in the order
shown in the following diagram.
2. Insert the option board into the socket for option 1. The fol-
lowing diagram shows the relationship between the option
board and mounting position.
3. Mount the option board and the power board in the order
shown.
Removing the Internal Mechanism
To remove the internal mechanism from the housing, use a
Phillips screwdriver matching the screw on the lower part of the
front panel.
1. Turn the screw counterclockwise while pressing the hook on
the upper part of the front panel.
Hook
2. Carefully pull out the internal mechanism while holding the
left and right sides of the front panel.
Mounting
1. Insert the E5AK-T Controller into the panel’s mounting hole
at the position shown in the figure below.
2. Fit the mounting bracket (accessory) into the fixing slots on
the top and bottom of the rear case.
3. Tighten the mounting bracket screws on the upper and lower
parts of the E5AK-T in small increments alternately and
equally until the ratchet starts to slide.
E5AK-T/E5EK-T E5AK-T/E5EK-T
E53-COV0809, E53-COV08 Terminal Cover (Order Separately)
Fasten the terminals covers as follows by using the snap pins.
Note: Snap pins are provided with the terminal covers.
E5AK-T
E5EK-T
Dimensions
Unit: mm (inch)
91 x 91
110 (4.33) min.
120
(4.72)
min.

E5AK-T Panel Cutouts
Note: 1. Recommended panel thickness is 1 to 8 mm.
2. Maintain the specified vertical and horizontal mounting space between each Unit. Units must
not be closely mounted (vertically or horizontally).
100 (3.94)
13.5
(0.53)
112 (4.41)
96 x 96 (3.78 x 3.78)
E5AK-T/E5EK-T E5AK-T/E5EK-T

E5EK-T Panel Cutouts
Note: 1. Recommended panel thickness is 1 to 8 mm.
2. Maintain the specified vertical and horizontal mounting space between each Unit. Units must
not be closely mounted vertically or horizontally.
60
(2.36)
min.
120
(4.72)
min.
100 (3.94)
48
(1.89)
96
(3.78)
91
112 (4.41)

ACCESSORIES (ORDER SEPARATELY)
Terminal Cover
E53-COV0809 E53-COV08
43.2
(1.70) 43.2
(1.70)
89 (3.50)
89 (3.50)
89 (3.50)
22.05
(0.87)
3
(0.12)
1.5
(0.06)
3
(0.12)
3
(0.12)
3
(0.12)
1.5
(0.06)
Current Transformer
E54-CT1
5.8 (0.23)
dia.
30 (1.18)
10 (0.39)
10.5 (0.41)
2.8 (0.11)dia.21 (0.83)
25 (0.98)
7.5 (0.30)
15
40 (1.57)
E5AK-T/E5EK-T E5AK-T/E5EK-T
Unit: mm (inch)
E54-CT3
12 dia.
2.36 (0.09)dia.
Two, M3
(depth: 4)
40 (1.57)
x
40 (1.57)
9 (0.35)
15 (0.59)
30 (1.18)
30 (1.18)
Installation

INSTALLATION
Main Parts
Terminals
Output Board
Housing
Front panel
Option Board
Input type
connector
Removing Internal Mechanism
While pressing the hooks on the left and right sides of the front
panel, carefully pull the internal mechanism from the housing.
(Refer to the drawing below.)

SETTING UP THE OUTPUT BOARD
1. Two rectangular holes are provided on the power board (right
side of Controller). Fit the two protrusions of the output board
into these two holes.
2. With the output board fitted into the power board, fit the out-
put board into the connector on the control board (left side of
Controller). 1
2

SETTING UP THE OPTION BOARD
1. Place the Controller bottom up, and fit the option board
horizontally into the connector on the power board (right side
of Controller).
2. With the power board connected, fit the board vertically into
the connector on the control board (left side of controller).
1
2
E5AK-T/E5EK-T E5AK-T/E5EK-T

MOUNTING THE CONTROLLER
1. Insert the Controller into the panel’s mounting hole at the position shown in the figure below.
2. Push the adapter along the Controller body from the terminals up to the panel, and fasten temporarily.
3. Tighten the two fixing screws on the adapter. When tightening screws, tighten the two screws alternately keeping the torque to
approximately 0.29 to 0.39 N

m,or3to4kgf

cm.
Adapter
Panel
Watertight packing
I: Current input V: Voltage input
TC

PT: Temperature input
Note: Do not touch the pins of the jumper connector when setting the input type.
Note: The jumper is factory-set to TC

PT (temperature input).
Set the jumper to temperature, voltage, or current input accord-
ing to the sensor connected to the input terminal.
Input Jumper Setting
After setting the jumper, put on the housing, pressing the housing until the hooks of the front panel snap on.
E5AK-T/E5EK-T E5AK-T/E5EK-T

WIRING TERMINALS
Terminal Arrangement
TRSF: Transfer output
EV1 to 4: Event input
PTMR: Potentiometer
AC100--240V 50/60 Hz
(AC/DC24V)
SOURCE
TRSF: Transfer output
EV1/2: Event input
PTMR: Potentiometer
SOURCE
E5AK-T E5EK-T
AC100--240V 50/60 Hz
(AC/DC24V)

WIRING PRECAUTIONS
•Use ducts to separate input leads and power lines in order to protect the Controller and its lines from external noise.
•Solderless terminals are recommended when wiring the Controller.
•Tighten the terminal screws using a torque no greater than 0.78 N

m, or 8 kgf

cm max. Be careful not to tighten the terminal
screws too tightly.
10
9
8
7
6
5
4
3
2
1
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
31 32
33
AB C
B
FD
C
E
10
9
8
7
6
5
4
3
2
1
20
19
18
17
16
15
14
13
12
11
2122
23
AB/CC
B
FD
E
E5EK-T
Power Blocks for E5AK-T/EK-T
The E5AK/E5EK has independent power supplies for each of the terminal blocks shown below.
E5AK-T
E5AK-T/E5EK-T E5AK-T/E5EK-T

E5AK-T WIRING
In the following wiring diagrams, the left side of the terminal numbers indicate the inside of the Controller.
Power Supply
Input 100 to 240 VAC or AC/DC 24 V to terminal numbers 9 and 10 according to the specifications.
Sensor Input
Connect the sensor input to terminal numbers 11 to 14 and 33 as follows according to the input type.
Control Output
Terminal numbers 7 and 8 are for control output 1 (OUT1), and terminal numbers 5 and 6 are for control output 2 (OUT2). The following
diagrams show the available output boards and their internal equalizing circuits.
With E53-V

output boards, approx. 2 V is output for one second after the power is interrupted.
E5AK-T/E5EK-T E5AK-T/E5EK-T
Specifications for Each Output Board
Model Output type Specifications
E53-R Relay 5 A at 250 VAC
E53-S SSR 1 A at 75 to 250 VAC
E53-Q
E53-Q3
E53-Q4
Voltage (NPN)
Voltage (NPN)
Voltage (PNP)
NPN: 40 mA at 12 VDC (with short-circuit protection)
NPN: 20 mA at 24 VDC (with short-circuit protection)
PNP: 20 mA at 24 VDC (with short-circuit protection)
E53-C3
E53-C3D 4to20mA
0to20mA 4 to 20 mA; permissible load impedance: 600 Ωmax.; resolution: approx. 2600
0 to 20 mA; permissible load impedance: 600 Ωmax.; resolution: approx. 2600
E53-V34
E53-V35 0to10V
0to5V 0 to 10 VDC; permissible load impedance: 1 kΩmin.; resolution: approx. 2600
0 to 5 VDC; permissible load impedance: 1 kΩmin.; resolution: approx. 2600
With E5AK-PRR2 Controllers, the relay output (1 A at 250 VAC) is fixed.
When replacing the output board, use the E53-R. The following diagrams show the relationship between terminals and open/close relay
settings.
Open Close
75
68
Auxiliary Output
Terminal numbers 3 and 4 are for auxiliary output 1 (SUB1) and terminal numbers 1 and 2 are for auxiliary output 2 (SUB2). The following
diagrams show the internal equalizing circuits for the auxiliary outputs:
10
9
8
7
6
5
4
3
2
1
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
31 32
33 Auxiliary
output 1 Auxiliary
output 2
Output specifications are as follows: SPST-NO, 3 A at 250 VAC
31
24
CT Input/Potentiometer
When using the HBA function on the E5AK-TAA2 Controller, connect CT input (CT) to terminal numbers 15 to 17. When monitoring the
valve opening on the E5AK-TPRR2 Controller, connect the potentiometer (PTMR) to terminal numbers 15 to 17. Connect each of these
inputs as follows:
10
9
8
7
6
5
4
3
2
1
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
31 32
33
C
W
O
CT
CT input Potentiometer
17 17
15
16
15
16
For details on CT inputs, refer to
Appendix, About Current Transformer
in the
E5AK-T/E5EK-T User’s Manual (H83/H85)
.
For details on the potentiometer, refer to the
Instruction Manual
for the valve connected to the Controller. The variable resistance range is
100 Ωto 2.5 kΩ.
E5AK-T/E5EK-T E5AK-T/E5EK-T
Remote SP Input
Connect the input (RSP) to be used as the remote SP to terminal numbers 21 and 22. Only 4 to 20 mA inputs can be connected. Connect
the input as follows:
10
9
8
7
6
5
4
3
2
1
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
31 32
33
+
--
4to20mA
21
22
Event Input
Connect event inputs 1 and 2 (EV1/2) to terminal numbers 18 to 20, and events 3 and 4 (EV3/4) to terminal numbers 24 to 26. However,
note that terminal numbers 18 to 20 cannot be used on Controllers with a communications function. Connect the event inputs as follows:
20 EV3
EV4
COM
+
+
--
10
9
8
7
6
5
4
3
2
1
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
31 32
33
19
18
26
25
24
+
+
--
Event input 1 and 2 Event input 3 and 4
EV1
EV2
COM
Terminals 18 and 24 (COM) are connected internally.
Use event inputs under the following conditions:
Contact input ON: 1 kΩmax.
OFF: 100 kΩmin.
No-contact input ON: Residual voltage 1.5 V max.,
OFF: Leakage current 0.1 mA max.
Polarities during no-contact input are as follows:
20
19
18
26
25
24
+
+
--
Event input 1 and 2 Event input 3 and 4
EV1
EV2
COM
EV3
EV4
COM
+
+
--
E5AK-T/E5EK-T E5AK-T/E5EK-T
Transfer Output
Connect transfer output (TRSF) to terminal numbers 29 and 30. The internal equalizing circuit for transfer output is as follows:
30
29
4to20mA L
+
--
Transfer output specifications are as follows: 4 to 20 mA
Permissible load impedance: 600 Ωmax.
Resolution: approx. 2600
Communications
Terminal numbers 18 to 20, 31 and 32 can be used only on Controllers with communications boards (E53-AK01/02/03). For details on
wiring, refer to
Chapter 6, Using the Communications Function
in the
E5AK-T/E5EK-T User Manuals (H83 and H85)
.

E5EK-T WIRING
In the following wiring diagrams, the left side of the terminal numbers indicate the inside of the Controller.
Power Supply
Input 100 to 240 VAC or AC/DC 24 V to terminal numbers 9 and 10 according to the specifications.
Sensor Input
Connect the sensor input to terminal numbers 11 to 14 and 33 as follows according to the input type.
E5AK-T/E5EK-T E5AK-T/E5EK-T
Control Output
Terminal numbers 7 and 8 are for control output 1 (OUT1), and terminal numbers 5 and 6 are for control output 2 (OUT2). The following
diagrams show the available output boards and their internal equalizing circuits.
With E53-V

output boards, approx. 2 V is output for one second after the power is interrupted.
Specifications for Each Output Board
Model Output type Specifications
E53-R Relay 5 A at 250 VAC
E53-S SSR 1 A at 75 to 250 VAC
E53-Q
E53-Q3
E53-Q4
Voltage (NPN)
Voltage (NPN)
Voltage (PNP)
NPN: 40 mA at 12 VDC (with short-circuit protection)
NPN: 20 mA at 24 VDC (with short-circuit protection)
PNP: 20 mA at 24 VDC (with short-circuit protection)
E53-C3
E53-C3D 4to20mA
0to20mA 4 to 20 mA, permissible load impedance: 600 Ωmax., resolution: approx. 2600
0 to 20 mA, permissible load impedance: 600 Ωmax., resolution: approx. 2600
E53-V34
E53-V35 0to10V
0to5V 0 to 10 VDC, permissible load impedance:1 kΩmin., resolution: approx. 2600
0 to 5 VDC, permissible load impedance: 1 kΩmin., resolution: approx. 2600
With E5EK-TPRR2 Controllers, the relay output (1 A at 250 VAC) is fixed.
When replacing the output board, use the E53-R. The following diagrams show the relationship between terminals and open/close relay
settings.
8
7
Open
6
5
Close
Auxiliary Output
Terminal numbers 3 and 4 are for auxiliary output 1 (SUB1) and terminal numbers 1 and 2 are for auxiliary output 2 (SUB2). The following
diagrams show the internal equalizing circuits for the auxiliary outputs:
10
9
8
7
6
5
4
3
2
1
20
19
18
17
16
15
14
13
12
11
21 22
23
42
1
Auxiliary
output 1 Auxiliary
output 2
3
Output specifications are as follows: SPST-NO, 3A at 250 VAC
E5AK-T/E5EK-T E5AK-T/E5EK-T
CT Input/Potentiometer
When using the HBA function on the E5EK-TAA2 Controller, connect CT input (CT) to terminal numbers 15 to 17. When monitoring the
valve opening on the E5EK-TPRR2 Controller, connect the potentiometer (PTMR) to terminal numbers 15 to 17. Connect each of these
inputs as follows:
10
9
8
7
6
5
4
3
2
1
20
19
18
17
16
15
14
13
12
11
21 22
23
17
16
15
17
16
15
O
W
C
CT input Potentiometer
For details on CT inputs, refer to
Appendix, About Current Transformer
in the
E5AK-T/E5EK-T User’s Manual (H83/H85)
.
For details on the potentiometer, refer to the
Instruction Manual
for the valve connected to the Controller. The variable resistance range is
100 Ωto 2.5 kΩ.
Remote SP Input
Connect the input (RSP) to be used as the remote SP to terminal numbers 15 and 16. However, note that the remote SP cannot be used
on the E5EK-TPRR2 Controller. Only 4 to 20 mA inputs can be connected. Connect the input as follows:
10
9
8
7
6
5
4
3
2
1
20
19
18
17
16
15
14
13
12
11
21 22
23
15
+
--
16
4to20mA
Event Input
Connect event inputs 1 and 2 (EV1/2) to terminal numbers 18 to 20. However, note that terminal numbers 18 to 20 cannot be used on
Controllers with a communications function. Connect the event inputs as follows:
+
+
--
10
9
8
7
6
5
4
3
2
1
20
19
18
17
16
15
14
13
12
11
21 22
23
20
19
18
Event input 1 and 2
EV1
EV2
COM
Use event inputs under the following conditions:
Contact input ON: 1 kΩmax., OFF: 100 kΩmin.
No-contact input ON: Residual voltage 1.5 V max.,
OFF: Leakage current 0.1 mA max.

Other manuals for E5AK-T

1

This manual suits for next models

1

Other Omron Controllers manuals

Omron Z500 Series User guide

Omron

Omron Z500 Series User guide

Omron C200HX Series Parts list manual

Omron

Omron C200HX Series Parts list manual

Omron TJ2-MC64 Owner's manual

Omron

Omron TJ2-MC64 Owner's manual

Omron SYSMAC C500 User manual

Omron

Omron SYSMAC C500 User manual

Omron SYSMAC CS1W-CLK11 User manual

Omron

Omron SYSMAC CS1W-CLK11 User manual

Omron C200H Series Parts list manual

Omron

Omron C200H Series Parts list manual

Omron CJ1W-CT021 Installation manual

Omron

Omron CJ1W-CT021 Installation manual

Omron NV3W-MR20L-V1 User manual

Omron

Omron NV3W-MR20L-V1 User manual

Omron E5EK User manual

Omron

Omron E5EK User manual

Omron CJ1G/H-CPU series User manual

Omron

Omron CJ1G/H-CPU series User manual

Omron CJ2*-CPU Series User manual

Omron

Omron CJ2*-CPU Series User manual

Omron G9SP Series User manual

Omron

Omron G9SP Series User manual

Omron E5AR-T User manual

Omron

Omron E5AR-T User manual

Omron CS Series User manual

Omron

Omron CS Series User manual

Omron V680-CA5D01-V2 User manual

Omron

Omron V680-CA5D01-V2 User manual

Omron V600 Series User manual

Omron

Omron V600 Series User manual

Omron trajexia CJ1W-MCH72 User manual

Omron

Omron trajexia CJ1W-MCH72 User manual

Omron NX Series User manual

Omron

Omron NX Series User manual

Omron NL-200 User manual

Omron

Omron NL-200 User manual

Omron G9SP-N10D User manual

Omron

Omron G9SP-N10D User manual

Omron E5AR User manual

Omron

Omron E5AR User manual

Omron E5ZN Series User manual

Omron

Omron E5ZN Series User manual

Omron TJ2-MC64 Quick user guide

Omron

Omron TJ2-MC64 Quick user guide

Omron NX102 series User manual

Omron

Omron NX102 series User manual

Popular Controllers manuals by other brands

StoneL Prism PI Installation maintenance and operating instructions

StoneL

StoneL Prism PI Installation maintenance and operating instructions

Legato GSMS-THR Setup Software guide

Legato

Legato GSMS-THR Setup Software guide

Regada SP 3 Installation, service and maintenance instructions

Regada

Regada SP 3 Installation, service and maintenance instructions

Samlexpower SMC-10 owner's manual

Samlexpower

Samlexpower SMC-10 owner's manual

Ltech LT-312RF quick start guide

Ltech

Ltech LT-312RF quick start guide

ABB ACS310 quick start guide

ABB

ABB ACS310 quick start guide

QED MicroPurge basics MP10UH instruction manual

QED

QED MicroPurge basics MP10UH instruction manual

Gasboy Islander PLUS installation manual

Gasboy

Gasboy Islander PLUS installation manual

Watts AERCO EXT Installation, operation & maintenance manual

Watts

Watts AERCO EXT Installation, operation & maintenance manual

MICRO-EPSILON capaNCDT 6110 Quick manual

MICRO-EPSILON

MICRO-EPSILON capaNCDT 6110 Quick manual

Elko iNels SA3-022M quick start guide

Elko

Elko iNels SA3-022M quick start guide

ADTRAN D4 DS0 DP Practices

ADTRAN

ADTRAN D4 DS0 DP Practices

Drive.web smarty dw24 Series Installation & operation manual

Drive.web

Drive.web smarty dw24 Series Installation & operation manual

ECKELMANN UA 410 L operating manual

ECKELMANN

ECKELMANN UA 410 L operating manual

Novatech MC9200 Series Technical reference guide

Novatech

Novatech MC9200 Series Technical reference guide

Jung KNX 230 .16 REGHM Series Operation instructions

Jung

Jung KNX 230 .16 REGHM Series Operation instructions

Grundfos LLC 1000W Installation and operating instructions

Grundfos

Grundfos LLC 1000W Installation and operating instructions

ModelCraft Fail-Safe operating instructions

ModelCraft

ModelCraft Fail-Safe operating instructions