ABB ACS310 User manual

Quickstart Guide
ABB PLC and drives integration using Modbus RTU

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐2‐ PLCanddrivesintegration
Contents
Introduction...................................................................................................................................................................4
Safetyinstructions .........................................................................................................................................................4
Limitations .....................................................................................................................................................................4
Fieldbusgrounding ....................................................................................................................................................6
Fieldbusshield ...........................................................................................................................................................6
Endtermination.........................................................................................................................................................6
Pullup/pulldownresistors........................................................................................................................................6
Driveswithembeddedfieldbus.................................................................................................................................7
FieldbusmodulesforABBdrives...............................................................................................................................8
Commonrecommendations......................................................................................................................................8
ABBcableTK505........................................................................................................................................................9
AC500COM1–Masteratthebuslineend .........................................................................................................11
AC500COM2–Masteratthebuslineend .........................................................................................................11
AC500‐eCoCOM1–Masteratthebuslineend..................................................................................................11
AC500‐eCoCOM2–Masteratthebuslineend..................................................................................................12
Driveconfiguration......................................................................................................................................................13
StartingupACS310driveswithembeddedModbusRTU .......................................................................................14
StartingupACS355driveswithFMBA‐01ModbusRTUadapter ............................................................................15
StartingupACS800driveswithRMBA‐01ModbusRTUadapter............................................................................17
StartingupACS850,ACQ810driveswithembeddedModbusRTU ........................................................................18
StartingupACS880driveswithFSCA‐01ModbusRTUadapter..............................................................................19
StartingupACSM1driveswithFSCA‐01ModbusRTUadapter ..............................................................................20
Installdriveslibrary .................................................................................................................................................21
ControlBuilderPlusforPLCandDrives.......................................................................................................................22
Hardwareconfiguration ..........................................................................................................................................22
IPconfigurationofCPU(forEthernetconnectionbetweenPCandPLC) ...............................................................24
CODESYS ..................................................................................................................................................................25
CODESYStabs ......................................................................................................................................................25

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐3‐ PLCanddrivesintegration
LibraryManager ..................................................................................................................................................26
PLClogic...............................................................................................................................................................27
DownloadprogramtoPLC...................................................................................................................................32
Createbootproject .............................................................................................................................................33
Testtheprogram .................................................................................................................................................34
ReadandwritemoredatabetweenPLCanddrive(optional)............................................................................36
Visualizations.......................................................................................................................................................43
Addmoredrives(optional)..................................................................................................................................46
Actualizationrate ................................................................................................................................................47
Otherusefuldocumentation.......................................................................................................................................47
Revision .......................................................................................................................................................................47

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐4‐ PLCanddrivesintegration
Introduction
ThisguidewilltakeyouthroughthehardwareinstallationandconfigurationofABBACSDrivesandPLCinorderto
prepareforModbusRTUcontrol.ABB‐specificready‐madefunctionblocksandvisualizationsfromthePS553‐
DRIVESlibrarywillbeusedforthecontrolofthedrives.WhiletheguideisapplicabletoallAC500PLCsandall
ModbusRTUcompatibleABBACSdrives,theexampleisbuiltupwithanAC500‐eCoPLCandanACS355drive.
Note!Thematerialinthisapplicationmightneedtobeadaptedaccordingtoactualequipmentandfunction
beforeitisused.Testingoftheequipmentmustalwaysbeperformedbytheresponsiblestart‐uppersonaccording
tocurrentlegislationbeforetheequipmentisplacedinservice.ABBdoesnottakeanyresponsibilityforpossible
damagecausedbyusingthematerialinthisapplication(shownexamples,data,projecttools,etc.).
Safetyinstructions
Followallsafetyinstructionsdeliveredwiththeusedcomponents:
Readthecompletesafetyinstructionsfortheuseddrivebeforeyouinstall,commissionorusethedrive.
Thecompletesafetyinstructionsaregivenatthebeginningofthedrivesuser’smanual(e.g.forACS355:
3AUA0000066143[English]).
ReadallsafetyandinstallationinstructionsoftheusedPLC.SeetheonlinehelpinCoDeSys(Help→
Contents→TargetSystem→AC500/S500→Introduction→Overview→Regulations).
Limitations
Thefollowinglimitationsarevalidforthisguide:
General
oAllinstructionsinthisguidearebasedondefaultsettingsinPLCanddrives
oPS501ControlBuilderPlusversion2.2.0orlater
oThedrivemustbeequippedwithembeddedModbusRTUoraModbusRTUadapter
FunctionblockandvisualizationlibraryPS553‐DRIVEScompatibility
oCommunicationprofile:ABBdrives
oDrivetypes:AllModbusRTUcompatibleABBACSdrives
oApplicationtypes:Speed/FrequencycontrolorTorquecontrol

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐5‐ PLCanddrivesintegration
Setupexample
ControlBuilderPlus
AC500PLC
ABBACSDrives
ETHERNETor
serialconnection
ModbusRTU
ABBModbus
RTUmodules
orembedded

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐6‐ PLCanddrivesintegration
Hardwarephysicalconnection
Inthefollowingchapter,physicalconnectionofthehardwarewillbeexplained.
Fieldbusgrounding
ForAC500,whichhasopto‐isolatedCOMinterfaces,itisrecommendednottoconnecttheground.ForAC500‐
eCo,wheretheCOMinterfacesarenotopto‐isolated,itisrecommendedtoconnectthegroundatoneplace,
typicallyinthebusmaster.Forconnectionexamples,seechapter“Installationexamples”.
Fieldbusshield
TheshieldshouldalwaysbeconnectedinaModbusRTUline.ThepurposeoftheshieldistoprotectagainstEMC
disturbancesandreflectiononthebusline.Forconnectionexamples,seechapter“Installationexamples”.
Endtermination
Purpose:Toavoidsignalreflections.
Resistorsize:120Ohms,¼W.
Wheretoconnect:Oneresistorineachendofthebusline(firstandlastnode).
Pullup/pulldownresistors
Purpose:Tokeepadefinedhighlevelonthebuswhilethereisnodataexchange.
Resistorsize:Dependsonbusmaster(COM)voltagelevel.470ΩforAC500(5Voutput)and270Ωfor
AC500‐eCo(3.3Voutput).
Wheretoconnect:Activatepull‐upandthepull‐downresistors,butonlyonceoneverybusline,atthebus
master.

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐7‐ PLCanddrivesintegration
AC500andAC500eCoCOMportoverview
AC500AC500‐eCoCM574‐RS
COM1COM2COM1COM2
(optional)
COM1=COM2
(seeCOM1of
AC500,exceptpull‐
up/pull‐down)
COMVoltagelevel5V5V3,3V3,3V5V
Opto‐isolated
(electricallyisolated)
YESYESNO
optional*)
NOYES
Maximumbuscable
length
Acc.toRS485
standard
Acc.toRS485
standard
50m
*)Accto
RS485
standard
50mAcc.toRS485
standard
ConnectionTerminal9poleD‐sub9poleD‐sub
*)Terminal
TerminalTerminal
Terminationresistor
built‐in
NONONONONO
Terminationresistor
size
120Ω 120Ω 120Ω 120Ω 120Ω
Pull‐up/pull‐down
resistorsbuilt‐in
YES(connect
withbridges)
NONO
*)yesconnect
withbridges
YES(connect
withbridges)
YES(connectwith
bridges)
Pull‐up/pull‐down
resistorsize
470Ω 470Ω 270Ω 270Ω 475Ω
Pull‐up/pull‐down
resistorsconnection
point
Master(CPU)
COMport
Master(CPU)
COMport
Master(CPU)
COMport
Master
(CPU)COM
port
Master(CPU)COM
port
Pull‐up/pull‐down
connection
Bridges:1to
2and3to4
External470
Ωresistors
External270Ω
resistors
Bridges:1to
2and3to4
Bridges:1to2and3
to4
*)usingTK506RS485isolatorforPM554/PM564withindexA3andhigher
Driveswithembeddedfieldbus
ThefollowingABBdriveshaveModbusRTUembedded:
ACS310
ACS/ACH550
ACS850
Sincethebuilt‐inendterminationofthedriveautomaticallyalsoactivatespull‐up/pull‐downresistors,itis
recommendedtoskipthebuilt‐inoption.
Itisrecommendedtoconnectaseparateendterminationresistortothefirstnode(i.e.thePLCCOMinterface)
andthelastnode(i.e.thelastdriveonthebus).
Forconnectionexamples,seechapter“Installationexamples”.

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐8‐ PLCanddrivesintegration
FieldbusmodulesforABBdrives
ThefollowingABBdrivesModbusRTUmoduleshaveanoptiontoactivatebuilt‐inendterminationandpull‐
up/pull‐downresistors.
RMBA‐01(usedwithforinstanceACS550andACS800)
FSCA‐01(usedwithforinstanceACS880andACSM1)
ThefollowingABBdrivesModbusRTUmoduledoesnothaveanoptiontoactivatebuilt‐inendresistorsincluding
pull‐up/pull‐downresistors.
FMBA‐01(usedwithforinstanceACS355)
Sincethebuilt‐inendterminationofthemodules(RMBA‐01andFSCA‐01)automaticallyalsoactivatespull‐
up/pull‐downresistors,itisrecommendedtoskipthebuilt‐inoption.
Itisrecommendedtoconnectaseparateendterminationresistortothefirstnode(i.e.thePLCCOMinterface)
andthelastnode(i.e.thelastdriveonthebus).
Forconnectionexamples,seechapter“Installationexamples”.
Commonrecommendations
Note!Thefollowingbulletsareonlyrecommendationsandnogeneralrules.
Installationwheretotalcablelengthismorethan50m
oUseCPUAC500ratherthanAC500‐eCoorAC500‐eCowithTK506RS485isolatorforCOM1.
Installationwherethereisariskthatgroundconnectionsindifferentnodescouldvaryinvoltagepotential
(typicallyinshipinstallationsorwithcablelengthsmorethan50m).
oUseCPUAC500anddonotconnectgroundcable,onlyshield→2‐wiresolution,oruseAC500‐eCo
withTK506RS485isolatorforCOM1.
WhenAC500‐eCoisused
oUseof3‐wireconnectionisrecommendedbecausetheCOMinterfaceisnotopto‐isolated,
oruseAC500‐eCowithTK506RS485isolatorforCOM1.
oUseofcablelengthmorethan50mshouldberealizedwithrepeaters,
oruseAC500‐eCowithTK506RS485isolatorforCOM1.
Cabletype
oUseonlycableswithtwistedpairwiresandbraidedshields.Foilshieldsarenotrobustenough,
cannotbecontactedwellandhavepoorHF(HighFrequency)properties.
oGroundthecableshielddirectlywithaclipwhenenteringtheswitch‐gearcabinet.Donotcutthe
shielduntilthecablereachestheconnectedmodule.
oTheconnectionbetweenthePEbarandtheshieldbarmusthavelowimpedance.
oUseABBcableTK505whensuitableforeasyinstallation.

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐9‐ PLCanddrivesintegration
Busline
Construction2cores,twisted,withcommonshield
Conductorcrosssection>0.22mm2(24AWG)
‐recommendation0.5mm2correspondstoØ0.8mm
Twistingrate<10/meter(symmetricallytwisted)
CoreinsulationPolyethylene(PE)
Resistancepercore<100Ω/km
CharacteristicimpedanceAppr.120Ω(100…150Ω)
Capacitancebetweenthecores<55nF/km(ifhigher,thenmaxbuslength
mustbereduced)
Terminatingresistors120Ω,¼Watbothlineends
RemarksCableswithPVCcoreinsulationandacore
diameterof0.8mmcanbeuseduptoa
lengthofappr.250m.Inthiscase,thebus
terminatingresistorisappr.100Ω.
ABBcableTK505
ForaneasyModbusinstallationintheCPUend,thepre‐madeABBcableTK505canbeused.Itincludesa9poleD‐
subcontactwithbuilt‐inendtermination(120Ω)andpull‐up/pull‐downresistors(2*270Ω).Thiscontactis
suitableforAC500‐eCoCOM1.ItcanalsobeusedforAC500COM2(eventhoughanothervoltagelevelisused),
butonlyiftheGNDwireisnotconnectedtotheModbusslaves(2‐wiresolution,preferredforAC500COMports).

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐10‐ PLCanddrivesintegration
Installationexamples
Bestconnectionofshieldistoconnectdirectlytothemountingplateofthecabinetasnearaspossibletothe
AC500.Themountingplatehastobeconnectedtocommonearthinthecabinetatonepoint.
or

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐11‐ PLCanddrivesintegration
AC500COM1–Masteratthebuslineend
AC500COM2–Masteratthebuslineend
AC500eCoCOM1–Masteratthebuslineend

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐12‐ PLCanddrivesintegration
AC500eCoCOM2–Masteratthebuslineend

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐13‐ PLCanddrivesintegration
Driveconfiguration
DriveswithoutembeddedModbusRTUneedtobeequippedwithModbusRTUadapteraccordingtoactualdrive
type.
ThefollowingdriveconfigurationstepswilladaptthedrivetoModbusRTUcontrolbasedonABB‐specificdrives
libraryPS553‐DRIVES.
Driveparameterscanbesetfromthedrive’scontrolpanelorfromdrive‐specificpctool(DriveWindowLightfor
ACS355andACS550,DriveStudioforACS850andACSM1,DriveComposerforACS880andDriveWindowfor
ACS800).
Note!Allparametersettingsarebasedondrivedefaultsettings.Ifthedrivehasbeenparameterizedpreviously,
returntodefaultsettingsbeforecontinuing.Itcanbedoneby:
Changingmacro(andthenchangingbackagain)inparameter99.02forACS310,ACS355andACS550.
Settingparameter99.03APPLICRESTOREtoYESinACS800.
Settingparameter16.04ParamrestoretoRestoredefsinACS850andACSM1.
Settingparameter96.06ParameterrestoretoRestoredefaultsinACS880.

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐14‐ PLCanddrivesintegration
StartingupACS310driveswithembeddedModbusRTU
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
ParameterDescriptionSettingComment
98.02COMMPROTSELSTD
MODBUS
Activatesfieldbuscommunication
53.02EFBSTATIONID[Address]ModbusRTUnodeaddressofthedrive
53.03EFBBAUDRATE19.2kbit/s
(example)
Transferrateofthelink.Samebaudratemustbe
definedintheModbusRTUmaster.
53.04EFBPARITY8NONE1
(example)
Parityandstopbits.Sameparityandstopbitsmust
bedefinedintheModbusRTUmaster.
53.05PROFILEABBDRV
FULL
Communicationprofile“ABBDrives”
Drivepowerdownandpowerupforthenewfieldbussettingstotakeeffect!
10.01EXT1COMMANDSCOMMFieldbusinterfaceassourceforstartandstop
11.02EXT1/EXT2SELCOMMFieldbusinterfaceassourcetoswitchtoEXT2
11.03REF1SELECTCOMMFieldbusinterfaceassourceforspeedreference
16.04FAULTRESETSELCOMMFieldbusinterfaceassourceforfaultreset
Optionalparametersettings
30.18COMMFAULT
FUNC
[optional]Howthedrivereactstoafieldbuscommunication
break.
30.19COMMFAULTTIME[optional]Timebetweencommunicationbreakdetectionand
theselectedaction.
(11.05)REF1MAX[Scalemax]Maxspeed/frequencyscalingvalue(usedinfunction
block/visualizationinput“SPEED_REF_MAX”).Must
belessorequaltodriveparametermax
speed/frequency.

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐15‐ PLCanddrivesintegration
StartingupACS355driveswithFMBA01ModbusRTUadapter
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
ParameterDescriptionSettingApplicMacro
”AC500
MODBUS”*)
Comment
98.02COMMPROTSELSTD
MODBUS
STD
MODBUS
Activatesfieldbusmodule
53.02EFBSTATIONID[Address]2ModbusRTUnodeaddressofthedrive
53.03EFBBAUDRATE19.2kbit/s
(example)
19.2kbit/sTransferrateofthelink.Samebaudratemust
bedefinedintheModbusRTUmaster.
53.04EFBPARITY8NONE1
(example)
8NONE1Parityandstopbits.Sameparityandstopbits
mustbedefinedintheModbusRTUmaster.
53.05PROFILEABBDRV
FULL
ABBDRV
FULL
Communicationprofile“ABBDrives”
53.10ActualSpeed101101Actualspeedfeedback
53.11ActualValue2105303Actualvalue2(e.gtorque105)(303=Status
Word1)
Drivepowerdownandpowerupforthenewfieldbussettingstotakeeffect!
10.01EXT1COMMANDSCOMMCOMMFieldbusinterfaceassourceforstartandstop
11.02EXT1/EXT2SELCOMMCOMMFieldbusinterfaceassourcetoswitchtoEXT2
11.03REF1SELECTCOMMCOMMFieldbusinterfaceassourceforspeed
reference
16.04FAULTRESETSELCOMMCOMMFieldbusinterfaceassourceforfaultreset
Optionalparametersettings
30.18COMMFAULT
FUNC
[optional]FAULTHowthedrivereactstoafieldbus
communicationbreak.
30.19COMMFAULTTIME[optional]Default:.3sTimebetweencommunicationbreakdetection
andtheselectedaction.
(11.05)REF1MAX[Scalemax] Maxspeed/frequencyscalingvalue(usedin
functionblock/visualizationinput
“SPEED_REF_MAX”).Mustbelessorequalto
driveparametermaxspeed/frequency.
*)inPar.99.02theApplicationMacrocanbesetto“AC500Modbus(10)”thentheparametersareautomatically
setasshown.

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐16‐ PLCanddrivesintegration
StartingupACS550withembeddedModbusRTU
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
ParameterDescriptionSettingComment
98.02COMMPROTSELEXTFBAActivatesfieldbuscommunication
53.02EFBSTATIONID[Address]ModbusRTUnodeaddressofthedrive
53.03EFBBAUDRATE19.2kbit/s
(example)
Transferrateofthelink.Samebaudratemustbe
definedintheModbusRTUmaster.
53.04EFBPARITY8NONE1
(example)
Parityandstopbits.Sameparityandstopbitsmust
bedefinedintheModbusRTUmaster.
53.05PROFILEABBDRV
FULL
Communicationprofile“ABBDrives”
Drivepowerdownandpowerupforthenewfieldbussettingstotakeeffect!
10.01EXT1COMMANDSCOMMFieldbusinterfaceassourceforstartandstop
11.02EXT1/EXT2SELCOMMFieldbusinterfaceassourcetoswitchtoEXT2
11.03REF1SELECTCOMMFieldbusinterfaceassourceforspeedreference
16.04FAULTRESETSELCOMMFieldbusinterfaceassourceforfaultreset
Optionalparametersettings
30.18COMMFAULT
FUNC
[optional]Howthedrivereactstoafieldbuscommunication
break.
30.19COMMFAULTTIME[optional]Timebetweencommunicationbreakdetectionand
theselectedaction.
(11.05)REF1MAX[Scalemax]Maxspeed/frequencyscalingvalue(usedinfunction
block/visualizationinput“SPEED_REF_MAX”).Must
belessorequaltodriveparametermax
speed/frequency.

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐17‐ PLCanddrivesintegration
StartingupACS800driveswithRMBA01ModbusRTUadapter
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
ParameterDescriptionSettingComment
98.02COMM.MODULE
LINK
STD
MODBUS
Activatesfieldbusmodule
98.07COMMPROFILEABBDRIVES Communicationprofile“ABBDrives”
52.01STATION
NUMBER
[Address]ModbusRTUnodeaddressofthedrive
52.02BAUDRATE19.2kbit/s
(example)
Transferrateofthelink.Samebaudratemustbe
definedintheModbusRTUmaster.
52.03PARITYNONE1STO
PBIT
(example)
Parityandstopbits.Sameparityandstopbitsmustbe
definedintheModbusRTUmaster.
Drivepowerdownandpowerupforthenewfieldbussettingstotakeeffect!
10.01EXT1
STRT/STP/DIR
COMM.CWFieldbusinterfaceassourceforstartandstop
11.02EXT1/EXT2
SELECT
COMM.CWFieldbusinterfaceassourcetoswitchtoEXT2control
location
11.03EXTREF1SELECTCOMM.REFFieldbusinterfaceassourceforspeedreference
16.04FAULTRESETSELCOMM.CWFieldbusinterfaceassourceforfaultreset
92.02MAINDSACT1102Actualspeedvaluetakenfrom01.02
92.02MAINDSACT2e.g.105Actualvalue2.E.gtorquetakenfrom01.05
Optionalparametersettings
30.18COMMFLTFUNC[optional]Howthedrivereactstoafieldbuscommunication
break.
30.19MAINREFDST‐
OUT
[optional]Timebetweencommunicationbreakdetectionandthe
selectedaction.
(11.05)EXTREF1
MAXIMUM
[Scalemax]Maxspeed/frequencyscalingvalue(usedinfunction
block/visualizationinput“SPEED_REF_MAX”).Mustbe
lessorequaltodriveparametermaxspeed/frequency.

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐18‐ PLCanddrivesintegration
StartingupACS850,ACQ810driveswithembeddedModbusRTU
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
ParameterDescriptionSettingComment
50.15FbcwusedP.02.36SelectstheaddressofthefieldbusControlWordin
use.
58.01ProtocolenaselModbusRTUInitializesembeddedfieldbuscommunication.
Drive‐to‐drivelinkoperation(parametergroup
57)isautomaticallydisabled.
58.03Nodeaddress[Address]ModbusRTUnodeaddressofthedrive
58.04Baudrate19.2kbit/s
(example)
Transferrateofthelink.Samebaudratemustbe
definedintheModbusRTUmaster.
58.05Parity8none1
(example)
Parityandstopbits.Sameparityandstopbitsmust
bedefinedintheModbusRTUmaster.
58.06ControlprofileABBClassicCommunicationprofile“ABBDrives”
58.10Refreshsettings[optional]Refreshesthesettingsofparameters
58.01…58.09.
10.01Ext1startfuncFBFieldbusinterfaceassourceforstartandstop
12.01EXT1/EXT2SELP.02.36bit
15
FieldbusinterfaceassourcetoswitchtoEXT2
controllocation
21.01Speedref1selEFBref1Fieldbusinterfaceassourceforspeedreference
10.10FaultresetselP.02.36bit8Fieldbusinterfaceassourceforfaultreset
Optionalparametersettings
58.07Commlosstout[optional]DefinesthetimeoutlimitfortheEFB
communicationmonitoring.
58.08CommlossmodeNoneor
AnyMessage
Enables/disablesEFBcommunicationloss
monitoringanddefinesthemeansforresetting
thecounterofthecommunicationlossdelay.
58.09Commlossaction[optional]DefinesthedriveoperationaftertheEFB
communicationlossmonitoringawakes.
58.10Refreshsettings[optional]Refreshesthesettingsofparameters
58.01…58.09.
(19.01)Speedscaling[Scalemax]Maxspeed/frequencyscalingvalue(usedinfunction
block/visualizationinput“SPEED_REF_MAX”).Must
belessorequaltodriveparametermax
speed/frequency.

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐19‐ PLCanddrivesintegration
StartingupACS880driveswithFSCA01ModbusRTUadapter
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
ParameterDescriptionSettingComment
50.01FBAAenableEnableActivatesfieldbusmodule
51.02PROTOCOL/PROFIL
E
ABBDrives
Classicor
Enhanced
Communicationprofile“ABBDrives”
51.03STATIONID[Address]ModbusRTUnodeaddressofthedrive
51.04BAUDRATE19.2kbit/s
(example)
Transferrateofthelink.Samebaudratemustbe
definedintheModbusRTUmaster.
51.05EFBPARITY8NONE1
(example)
Parityandstopbits.Sameparityandstopbits
mustbedefinedintheModbusRTUmaster.
52.02FBAdatain2Act116bit(5)ActualspeedasDataWord2fromthedrive
53.02FBAdataout2Ref116bit(2)SpeedreferenceasDataWord2tothedrive
51.27FBAparrefreshConfigureUpdatesfieldbussettings(groups50to57)
19.11Ext1/Ext2selectionMcwBit11
(06.01)
FieldbusinterfaceassourcetoswitchtoEXT2
controllocation
20.01Ext1commandsFieldbusAFieldbusinterfaceassourceforstartandstop
20.02Ext1starttrigger LevelTodirectlyrestartafterCoastStop(Off3)
22.11Speedref1
selection
FBAref1Fieldbusinterfaceassourceforspeedreference
31.11Faultreset
selection
P.06.01bit7Fieldbusinterfaceassourceforfaultreset
Optionalparametersettings
50.02FBAAcommloss
func
[optional]Definesthedriveoperationafterthe
communicationlossmonitoringawakes.
51.06MODBUSTIMEOUT[optional]Timebetweencommunicationbreakdetection
andtheselectedaction.1=100ms.
51.07TIMEOUTMODECONTROL
WRITE
Howthedrivereactstoafieldbuscommunication
break.
51.27FBAPARREFRESHREFRESHUpdatesfieldbussettings(groups50to53)
(46.01)Speedscaling[Scalemax]Maxspeed/frequencyscalingvalue(usedin
functionblock/visualizationinput
“SPEED_REF_MAX”).Mustbelessorequaltodrive
parametermaxspeed/frequency.

Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐20‐ PLCanddrivesintegration
StartingupACSM1driveswithFSCA01ModbusRTUadapter
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
ParameterDescriptionSettingComment
50.01FBAENABLEEnableActivatesfieldbusmodule
51.02PROTOCOL/PROFILEABBDrives
Classic
Communicationprofile“ABBDrives”
51.03STATIONID[Address]ModbusRTUnodeaddressofthedrive
51.04BAUDRATE19.2kbit/s
(example)
Transferrateofthelink.Samebaudratemustbe
definedintheModbusRTUmaster.
51.05EFBPARITY8NONE1
(example)
Parityandstopbits.Sameparityandstopbits
mustbedefinedintheModbusRTUmaster.
52.01FBADATAIN14StatuswordasDataWord1fromthedrive
52.02FBADATAIN25ActualspeedasDataWord2fromthedrive
53.01FBADATAOUT11ControlwordasDataWord1tothedrive
53.02FBADATAOUT22SpeedreferenceasDataWord2tothedrive
51.27FBAPARREFRESHREFRESHUpdatesfieldbussettings(groups50to53)
10.01EXT1STARTFUNCFBAFieldbusinterfaceassourceforstartandstop
12.01EXT1/EXT2SELP.02.12bit15FieldbusinterfaceassourcetoswitchtoEXT2
controllocation
24.01SPEEDREF1SELFBAREF1Fieldbusinterfaceassourceforspeedreference
10.08FAULTRESETSELP.02.12bit8Fieldbusinterfaceassourceforfaultreset
Optionalparametersettings
51.06MODBUSTIMEOUT[optional]Timebetweencommunicationbreakdetection
andtheselectedaction.1=100ms.
51.07TIMEOUTMODECONTROL
WRITE
Howthedrivereactstoafieldbuscommunication
break.
50.02COMMLOSSFUNC[optional]Definesthedriveoperationafterthe
communicationlossmonitoringawakes.
51.27FBAPARREFRESHREFRESHUpdatesfieldbussettings(groups50to53)
(25.02)SPEEDSCALING[Scalemax]Maxspeed/frequencyscalingvalue(usedin
functionblock/visualizationinput
“SPEED_REF_MAX”).Mustbelessorequaltodrive
parametermaxspeed/frequency.
Other manuals for ACS310
5
This manual suits for next models
7
Table of contents
Other ABB Controllers manuals

ABB
ABB PSE User manual

ABB
ABB COMMANDER 310 User manual

ABB
ABB i-bus KNX JRA/S 6.230.3.1 User manual

ABB
ABB ACS580-01 drives User manual

ABB
ABB ACS 600 MultiDrive User manual

ABB
ABB Cylon FBXi Series User manual

ABB
ABB RHD250 User manual

ABB
ABB ES/S 4.1.2.1 User manual

ABB
ABB COMMANDER 310 User manual

ABB
ABB C1900RC User manual

ABB
ABB Contrac PME120AI User manual

ABB
ABB ACS 800 Series User manual

ABB
ABB Contrac PME120AI Original operating manual

ABB
ABB DSQC1016 User manual

ABB
ABB LME620-AI User manual

ABB
ABB PSTX370 User manual

ABB
ABB COMMANDER 360 User manual

ABB
ABB COM600 series User manual

ABB
ABB Relion 670 series User manual

ABB
ABB PSTX Series Guide