Ontech Alarmbox 9012 User manual

Ontech Alarmbox 9012
Users manual
Acknowledge an alarm
When an alarm has been sent it has to be acknowledge before the unit can send
another alarm.
First make sure that the alarm sensor is not active, that is for example shut an
open door that is alarmed.
Then acknowledge by sending an SMS with the content ABCD#9#.
Compability
Ontech Alarmbox 9012 is fully compatible with master units with software revi-
sion R7 or higher.
For master units with software revision R6 or lower the temperature will not be
shown.
Alarmbox units ID will not be shown in status SMS more than one minute after
an update has been sent from the Alarmbox to the master unit.
See master units manual for instruction of how to check the software revision.
Troubble shooting
Symptom Reason
The LED is blinking all the
time
Dipswitches 6, 7 and 8 are all in position OFF.
Set valid ID.
Alarm messages is sent
continuously
Check that the cable jumper is connected on
the NC and GND connectors on the terminal (If
NC alarm sensor is connected there shall be no
jumper)
The magnetic switch is not
working
Check the distanse between the cabinet and
the magnet. Check that the jumber is removed.
Tip
If there is no radio connection between the master unit and the Alarmbox, first
move the units to a distance of approx. 2 meters in order to ensure that the radio
works.
Also check that the DIP switch 6 on the master unit is in OFF position.
If radio contact not can be established one Ontech Relay 9010 can be used as a
repeater if placed between the master unit and the Alarmbox.
Se the manual for the master unit for further instructions.
Declaration of conformity
Ondico AB, Datavägen 14A, 436 32 Askim, Sweden, hereby declares that the
product Ontech Alarmbox 9012 is in conformity with the provisions of the Radio
& Teleterminal directive R&TTE 1999/5/EG..
Status SMS
Below is shown an example of an status SMS and how it is interpreted.
Example Explanation
*Ontech9030 Asterix (*) means the alarm function is activated.
Units:
1; 2/24; 3/22 Indicates the IDs for the units connected to the master
unit. Also the temperature at each Alarmbox is indicated.
Temp:
24; 24,2 Indicates the temperature at the master unit.
Tstat:
OFF Indicates the status of the Thermostat function.
English
When the unit is alarming
When an alarm is activated an SMS will be sent to all mobile telephone numbers
on the alarm list. The red LED is double blinking 1-3 times. Up to ten different
persons can be alerted.
Below is shown an example of an alarm SMS.
Example Explanation
*Ontech9030 Asterix (*) means the alarm function is activated.
Alarm:
2a, 3b Indicates all alarms that have been activated since the
last acknowledge. A aafter the ID number means it is a
normal alarm. A bafter the ID number means it is a low
battery alarm. Se below.
Inputs:
2a Indicates the ID of the units where the alarm sensor is still
active. In this example it means the input in unit ID 2 is
active and must be deactivated before you acknowledge
the alarm.
Units:
1; 2/24; 3/22 Indicates the IDs for the units connected to the master
unit. Also the temperature at each Alarmbox is indicated.
Temp:
24; 24,2 Indicates the temperature at the master unit.
Tstat:
OFF Indicates the status of the Thermostat function.
Low battery warning
If the battery is low the unit will send an SMS with a bafter the ID number.
Replace the battery.
Technical specications
Short range radio Frequncy 2,4 GHZ
Power max 1 mW
Alarm inputs Activated by closing or opening function. The mag-
netic switch is activated with the attached magnet.
Power Litium battery 1/2 AA, 3 V. Will operate the unit
more than two years with normal usage.
Temperature range -20º C to +40ºC
15230_IB_EN_120801
www.ondico.se

Installation
1. Power up you Ontech master unit.
2. Deactivate the alarm function in the master unit by sending an SMS with the
content:
ABCD*7*0# (ABCD is the PINCODE you have decided, see your manual for
the master unit.)
3. Remove the cabinet from the Alarmbox by unscrew the screw and fold up
the upper part.
4. Set the unit ID number
a. Factory setting is ID 2. If you have two or more Alarmboxes you sure want
to know which one that is sending the alarm. DIP-switch 6, 7 and 8 is used
to set ID number according to the table below.
ID Switch 6 Switch 7 Switch 8
ID2 OFF OFF ON
ID3 OFF ON OFF
ID4 OFF ON ON
ID5 ON OFF OFF
ID6 ON OFF ON
ID7 ON ON OFF
ID8 ON ON ON
5. Set the radio channel
a. Normally you do not have to change this. If two or more Ontech system
is working close to each other or if there is other types of interference
another radio channel can be set. DIP-switch 2, 3, 4 and 5 is used for this
purpose. They can be set in any position but most important that the
setting is same on master unit and all connected Alarmboxes.
6. Attach the bottom part of the cabinet with two screws at the place you want.
If the magnetic switch shall be used the magnet is placed along the left
side of the Alarmbox (se figure) and is centred along the side. The distance
between the Alarmbox and the magnet must not be more than 3 mm.
7. Connect alarm sensors
a. The built-in magnetic switch
If the built-in magnetic switch shall be used at for example a door or win-
dow you must disconnect the cable jumper between the NC and GND
terminal.
b. Alarm sensor with Normally Closed (NC) operation
The relay output from the alarm sensor is normally closed. When alarming
the circuit is opened. Many PIR devices is constructed in this way.
Disconnect the cable jumper on the terminals NC and GND connectors
and connect instead the two cables from the alarm sensor.
c. Alarm sensor with Normally Open (NO) operation
The relay output from the alarm sensor is normally open. When alarming
the circuit is closed. For example level guards are constructed in this way.
Connect the cables in the NO and GND connectors on the terminal. NB,
The cable jumper should NOT be removed.
8. Take away the plastic insolation strap from the battery. Now the red LED is
blinking a couple of times.
9. Press the microswitch. The red LED shall now single blink or double blink one
or two times. If it is a double blink an alarm sensor is active.
If it is single blinking or double blinking three times it means that the unit has
no connection with the master unit. Control the setting of the radio channel
and control/adjust the distance between the Alarmbox and the master unit.
10. Attach the cover of the cabinet and fix it with the screw. If you have con-
nected an alarm sensor with wires it is necessary to make a hole for it in the
lower left corner.
11. Press the button on the main unit at least two times in order to acknowledge
the alarm sent when the Alarmbox was powered.
12. Make a status request to the main unit by sending an SMS with the content
ABCD#8#. You shall receive a reply SMS with information of which units that
are connected to the master unit. For interpreting the SMS, se next side.
13. Activate the alarm function on the master unit by sending an SMS with the
content ABCD#7*1#.
14. Activate the alarm sensor and check that all telephones on the alarm list
receives the Alarm SMS.
Introduction
• Ontech Alarmbox 9012 is a wireless device which send alarms to Ontech
GSM 9020 and Ontech GSM 9030 via a short range radio at frequency 2,4
GHz. Ontech GSM 9020 and Ontech GSM 9030 will in this manual be called
the master unit.
• The Alarmbox is sending an alarm message when one of the alarm inputs;
NO (Normally Open) eller NC (Normally Closed) has been activated. A
built-in magnetic switch is connected in parallel with the NC input. There
is also a sabotage alarm, a microswitch is activated when the cabinet cover
is removed.
• The Alarmbox has a built-in temperature sensor and in all messages from
the unit the temperature is reported.
• Up to seven Alarmboxes can individually be connected to each main unit.
One or more Ontech Relay 9010 in your Ontech system decreases the
number of Alarmbox you can connect. Highest total sum of Ontech Relay
9010 and Alarmbox units is seven.
• Operating range is at least 30 meters in free field. Construction and material
in houses affect the indoor operating range.
• In this manual all commands are described as SMS commands.
• Ontech also has developed apps for Android system and Iphones. Inside
those apps the function is described. Search on Ontech control on Google
Play or App stor. Or use the QR codes below.
Idle operating mode
The Alarmbox is sending status information at start up and then every twenty
minutes. This information is stored until next status update or longest 60
minutes. This means that if the Alarmbox is disconnected or stops working it will
take maximum 60 minutes until it disappears from SMS messages.
Google Play App store
1 8765432
ON
+
NC NO GNDGND
LED
Magnet
Terminal
Microswitch
DIP-switch
Battery
Position of the components
Above the unit is shown without the cover of the cabinet. The figure is simplified
in order to easy show the position of the components.
Ondico AB is not responsible for damages that may occur due to incorrect use or
if the product does not work as desired.
Welcome
Thank you for choosing to update your Ontech GSM system with an Alarmbox.
We hope that this manual will help you to easy install the unit and that you will
be satisfied with the unit and its functions.
ments on the unit and this manual.

Installation
1. Power up you Ontech master unit.
2. Deactivate the alarm function in the master unit by sending an SMS with the
content:
ABCD*7*0# (ABCD is the PINCODE you have decided, see your manual for
the master unit.)
3. Remove the cabinet from the Alarmbox by unscrew the screw and fold up
the upper part.
4. Set the unit ID number
a. Factory setting is ID 2. If you have two or more Alarmboxes you sure want
to know which one that is sending the alarm. DIP-switch 6, 7 and 8 is used
to set ID number according to the table below.
ID Switch 6 Switch 7 Switch 8
ID2 OFF OFF ON
ID3 OFF ON OFF
ID4 OFF ON ON
ID5 ON OFF OFF
ID6 ON OFF ON
ID7 ON ON OFF
ID8 ON ON ON
5. Set the radio channel
a. Normally you do not have to change this. If two or more Ontech system
is working close to each other or if there is other types of interference
another radio channel can be set. DIP-switch 2, 3, 4 and 5 is used for this
purpose. They can be set in any position but most important that the
setting is same on master unit and all connected Alarmboxes.
6. Attach the bottom part of the cabinet with two screws at the place you want.
If the magnetic switch shall be used the magnet is placed along the left
side of the Alarmbox (se figure) and is centred along the side. The distance
between the Alarmbox and the magnet must not be more than 3 mm.
7. Connect alarm sensors
a. The built-in magnetic switch
If the built-in magnetic switch shall be used at for example a door or win-
dow you must disconnect the cable jumper between the NC and GND
terminal.
b. Alarm sensor with Normally Closed (NC) operation
The relay output from the alarm sensor is normally closed. When alarming
the circuit is opened. Many PIR devices is constructed in this way.
Disconnect the cable jumper on the terminals NC and GND connectors
and connect instead the two cables from the alarm sensor.
c. Alarm sensor with Normally Open (NO) operation
The relay output from the alarm sensor is normally open. When alarming
the circuit is closed. For example level guards are constructed in this way.
Connect the cables in the NO and GND connectors on the terminal. NB,
The cable jumper should NOT be removed.
8. Take away the plastic insolation strap from the battery. Now the red LED is
blinking a couple of times.
9. Press the microswitch. The red LED shall now single blink or double blink one
or two times. If it is a double blink an alarm sensor is active.
If it is single blinking or double blinking three times it means that the unit has
no connection with the master unit. Control the setting of the radio channel
and control/adjust the distance between the Alarmbox and the master unit.
10. Attach the cover of the cabinet and fix it with the screw. If you have con-
nected an alarm sensor with wires it is necessary to make a hole for it in the
lower left corner.
11. Press the button on the main unit at least two times in order to acknowledge
the alarm sent when the Alarmbox was powered.
12. Make a status request to the main unit by sending an SMS with the content
ABCD#8#. You shall receive a reply SMS with information of which units that
are connected to the master unit. For interpreting the SMS, se next side.
13. Activate the alarm function on the master unit by sending an SMS with the
content ABCD#7*1#.
14. Activate the alarm sensor and check that all telephones on the alarm list
receives the Alarm SMS.
Introduction
• Ontech Alarmbox 9012 is a wireless device which send alarms to Ontech
GSM 9020 and Ontech GSM 9030 via a short range radio at frequency 2,4
GHz. Ontech GSM 9020 and Ontech GSM 9030 will in this manual be called
the master unit.
• The Alarmbox is sending an alarm message when one of the alarm inputs;
NO (Normally Open) eller NC (Normally Closed) has been activated. A
built-in magnetic switch is connected in parallel with the NC input. There
is also a sabotage alarm, a microswitch is activated when the cabinet cover
is removed.
• The Alarmbox has a built-in temperature sensor and in all messages from
the unit the temperature is reported.
• Up to seven Alarmboxes can individually be connected to each main unit.
One or more Ontech Relay 9010 in your Ontech system decreases the
number of Alarmbox you can connect. Highest total sum of Ontech Relay
9010 and Alarmbox units is seven.
• Operating range is at least 30 meters in free field. Construction and material
in houses affect the indoor operating range.
• In this manual all commands are described as SMS commands.
• Ontech also has developed apps for Android system and Iphones. Inside
those apps the function is described. Search on Ontech control on Google
Play or App stor. Or use the QR codes below.
Idle operating mode
The Alarmbox is sending status information at start up and then every twenty
minutes. This information is stored until next status update or longest 60
minutes. This means that if the Alarmbox is disconnected or stops working it will
take maximum 60 minutes until it disappears from SMS messages.
Google Play App store
1 8765432
ON
+
NC NO GNDGND
LED
Magnet
Terminal
Microswitch
DIP-switch
Battery
Position of the components
Above the unit is shown without the cover of the cabinet. The figure is simplified
in order to easy show the position of the components.
Ondico AB is not responsible for damages that may occur due to incorrect use or
if the product does not work as desired.
Welcome
Thank you for choosing to update your Ontech GSM system with an Alarmbox.
We hope that this manual will help you to easy install the unit and that you will
be satisfied with the unit and its functions.
ments on the unit and this manual.

Installation
1. Power up you Ontech master unit.
2. Deactivate the alarm function in the master unit by sending an SMS with the
content:
ABCD*7*0# (ABCD is the PINCODE you have decided, see your manual for
the master unit.)
3. Remove the cabinet from the Alarmbox by unscrew the screw and fold up
the upper part.
4. Set the unit ID number
a. Factory setting is ID 2. If you have two or more Alarmboxes you sure want
to know which one that is sending the alarm. DIP-switch 6, 7 and 8 is used
to set ID number according to the table below.
ID Switch 6 Switch 7 Switch 8
ID2 OFF OFF ON
ID3 OFF ON OFF
ID4 OFF ON ON
ID5 ON OFF OFF
ID6 ON OFF ON
ID7 ON ON OFF
ID8 ON ON ON
5. Set the radio channel
a. Normally you do not have to change this. If two or more Ontech system
is working close to each other or if there is other types of interference
another radio channel can be set. DIP-switch 2, 3, 4 and 5 is used for this
purpose. They can be set in any position but most important that the
setting is same on master unit and all connected Alarmboxes.
6. Attach the bottom part of the cabinet with two screws at the place you want.
If the magnetic switch shall be used the magnet is placed along the left
side of the Alarmbox (se figure) and is centred along the side. The distance
between the Alarmbox and the magnet must not be more than 3 mm.
7. Connect alarm sensors
a. The built-in magnetic switch
If the built-in magnetic switch shall be used at for example a door or win-
dow you must disconnect the cable jumper between the NC and GND
terminal.
b. Alarm sensor with Normally Closed (NC) operation
The relay output from the alarm sensor is normally closed. When alarming
the circuit is opened. Many PIR devices is constructed in this way.
Disconnect the cable jumper on the terminals NC and GND connectors
and connect instead the two cables from the alarm sensor.
c. Alarm sensor with Normally Open (NO) operation
The relay output from the alarm sensor is normally open. When alarming
the circuit is closed. For example level guards are constructed in this way.
Connect the cables in the NO and GND connectors on the terminal. NB,
The cable jumper should NOT be removed.
8. Take away the plastic insolation strap from the battery. Now the red LED is
blinking a couple of times.
9. Press the microswitch. The red LED shall now single blink or double blink one
or two times. If it is a double blink an alarm sensor is active.
If it is single blinking or double blinking three times it means that the unit has
no connection with the master unit. Control the setting of the radio channel
and control/adjust the distance between the Alarmbox and the master unit.
10. Attach the cover of the cabinet and fix it with the screw. If you have con-
nected an alarm sensor with wires it is necessary to make a hole for it in the
lower left corner.
11. Press the button on the main unit at least two times in order to acknowledge
the alarm sent when the Alarmbox was powered.
12. Make a status request to the main unit by sending an SMS with the content
ABCD#8#. You shall receive a reply SMS with information of which units that
are connected to the master unit. For interpreting the SMS, se next side.
13. Activate the alarm function on the master unit by sending an SMS with the
content ABCD#7*1#.
14. Activate the alarm sensor and check that all telephones on the alarm list
receives the Alarm SMS.
Introduction
• Ontech Alarmbox 9012 is a wireless device which send alarms to Ontech
GSM 9020 and Ontech GSM 9030 via a short range radio at frequency 2,4
GHz. Ontech GSM 9020 and Ontech GSM 9030 will in this manual be called
the master unit.
• The Alarmbox is sending an alarm message when one of the alarm inputs;
NO (Normally Open) eller NC (Normally Closed) has been activated. A
built-in magnetic switch is connected in parallel with the NC input. There
is also a sabotage alarm, a microswitch is activated when the cabinet cover
is removed.
• The Alarmbox has a built-in temperature sensor and in all messages from
the unit the temperature is reported.
• Up to seven Alarmboxes can individually be connected to each main unit.
One or more Ontech Relay 9010 in your Ontech system decreases the
number of Alarmbox you can connect. Highest total sum of Ontech Relay
9010 and Alarmbox units is seven.
• Operating range is at least 30 meters in free field. Construction and material
in houses affect the indoor operating range.
• In this manual all commands are described as SMS commands.
• Ontech also has developed apps for Android system and Iphones. Inside
those apps the function is described. Search on Ontech control on Google
Play or App stor. Or use the QR codes below.
Idle operating mode
The Alarmbox is sending status information at start up and then every twenty
minutes. This information is stored until next status update or longest 60
minutes. This means that if the Alarmbox is disconnected or stops working it will
take maximum 60 minutes until it disappears from SMS messages.
Google Play App store
1 8765432
ON
+
NC NO GNDGND
LED
Magnet
Terminal
Microswitch
DIP-switch
Battery
Position of the components
Above the unit is shown without the cover of the cabinet. The figure is simplified
in order to easy show the position of the components.
Ondico AB is not responsible for damages that may occur due to incorrect use or
if the product does not work as desired.
Welcome
Thank you for choosing to update your Ontech GSM system with an Alarmbox.
We hope that this manual will help you to easy install the unit and that you will
be satisfied with the unit and its functions.
ments on the unit and this manual.

Installation
1. Power up you Ontech master unit.
2. Deactivate the alarm function in the master unit by sending an SMS with the
content:
ABCD*7*0# (ABCD is the PINCODE you have decided, see your manual for
the master unit.)
3. Remove the cabinet from the Alarmbox by unscrew the screw and fold up
the upper part.
4. Set the unit ID number
a. Factory setting is ID 2. If you have two or more Alarmboxes you sure want
to know which one that is sending the alarm. DIP-switch 6, 7 and 8 is used
to set ID number according to the table below.
ID Switch 6 Switch 7 Switch 8
ID2 OFF OFF ON
ID3 OFF ON OFF
ID4 OFF ON ON
ID5 ON OFF OFF
ID6 ON OFF ON
ID7 ON ON OFF
ID8 ON ON ON
5. Set the radio channel
a. Normally you do not have to change this. If two or more Ontech system
is working close to each other or if there is other types of interference
another radio channel can be set. DIP-switch 2, 3, 4 and 5 is used for this
purpose. They can be set in any position but most important that the
setting is same on master unit and all connected Alarmboxes.
6. Attach the bottom part of the cabinet with two screws at the place you want.
If the magnetic switch shall be used the magnet is placed along the left
side of the Alarmbox (se figure) and is centred along the side. The distance
between the Alarmbox and the magnet must not be more than 3 mm.
7. Connect alarm sensors
a. The built-in magnetic switch
If the built-in magnetic switch shall be used at for example a door or win-
dow you must disconnect the cable jumper between the NC and GND
terminal.
b. Alarm sensor with Normally Closed (NC) operation
The relay output from the alarm sensor is normally closed. When alarming
the circuit is opened. Many PIR devices is constructed in this way.
Disconnect the cable jumper on the terminals NC and GND connectors
and connect instead the two cables from the alarm sensor.
c. Alarm sensor with Normally Open (NO) operation
The relay output from the alarm sensor is normally open. When alarming
the circuit is closed. For example level guards are constructed in this way.
Connect the cables in the NO and GND connectors on the terminal. NB,
The cable jumper should NOT be removed.
8. Take away the plastic insolation strap from the battery. Now the red LED is
blinking a couple of times.
9. Press the microswitch. The red LED shall now single blink or double blink one
or two times. If it is a double blink an alarm sensor is active.
If it is single blinking or double blinking three times it means that the unit has
no connection with the master unit. Control the setting of the radio channel
and control/adjust the distance between the Alarmbox and the master unit.
10. Attach the cover of the cabinet and fix it with the screw. If you have con-
nected an alarm sensor with wires it is necessary to make a hole for it in the
lower left corner.
11. Press the button on the main unit at least two times in order to acknowledge
the alarm sent when the Alarmbox was powered.
12. Make a status request to the main unit by sending an SMS with the content
ABCD#8#. You shall receive a reply SMS with information of which units that
are connected to the master unit. For interpreting the SMS, se next side.
13. Activate the alarm function on the master unit by sending an SMS with the
content ABCD#7*1#.
14. Activate the alarm sensor and check that all telephones on the alarm list
receives the Alarm SMS.
Introduction
• Ontech Alarmbox 9012 is a wireless device which send alarms to Ontech
GSM 9020 and Ontech GSM 9030 via a short range radio at frequency 2,4
GHz. Ontech GSM 9020 and Ontech GSM 9030 will in this manual be called
the master unit.
• The Alarmbox is sending an alarm message when one of the alarm inputs;
NO (Normally Open) eller NC (Normally Closed) has been activated. A
built-in magnetic switch is connected in parallel with the NC input. There
is also a sabotage alarm, a microswitch is activated when the cabinet cover
is removed.
• The Alarmbox has a built-in temperature sensor and in all messages from
the unit the temperature is reported.
• Up to seven Alarmboxes can individually be connected to each main unit.
One or more Ontech Relay 9010 in your Ontech system decreases the
number of Alarmbox you can connect. Highest total sum of Ontech Relay
9010 and Alarmbox units is seven.
• Operating range is at least 30 meters in free field. Construction and material
in houses affect the indoor operating range.
• In this manual all commands are described as SMS commands.
• Ontech also has developed apps for Android system and Iphones. Inside
those apps the function is described. Search on Ontech control on Google
Play or App stor. Or use the QR codes below.
Idle operating mode
The Alarmbox is sending status information at start up and then every twenty
minutes. This information is stored until next status update or longest 60
minutes. This means that if the Alarmbox is disconnected or stops working it will
take maximum 60 minutes until it disappears from SMS messages.
Google Play App store
1 8765432
ON
+
NC NO GNDGND
LED
Magnet
Terminal
Microswitch
DIP-switch
Battery
Position of the components
Above the unit is shown without the cover of the cabinet. The figure is simplified
in order to easy show the position of the components.
Ondico AB is not responsible for damages that may occur due to incorrect use or
if the product does not work as desired.
Welcome
Thank you for choosing to update your Ontech GSM system with an Alarmbox.
We hope that this manual will help you to easy install the unit and that you will
be satisfied with the unit and its functions.
ments on the unit and this manual.

Ontech Alarmbox 9012
Users manual
Acknowledge an alarm
When an alarm has been sent it has to be acknowledge before the unit can send
another alarm.
First make sure that the alarm sensor is not active, that is for example shut an
open door that is alarmed.
Then acknowledge by sending an SMS with the content ABCD#9#.
Compability
Ontech Alarmbox 9012 is fully compatible with master units with software revi-
sion R7 or higher.
For master units with software revision R6 or lower the temperature will not be
shown.
Alarmbox units ID will not be shown in status SMS more than one minute after
an update has been sent from the Alarmbox to the master unit.
See master units manual for instruction of how to check the software revision.
Troubble shooting
Symptom Reason
The LED is blinking all the
time
Dipswitches 6, 7 and 8 are all in position OFF.
Set valid ID.
Alarm messages is sent
continuously
Check that the cable jumper is connected on
the NC and GND connectors on the terminal (If
NC alarm sensor is connected there shall be no
jumper)
The magnetic switch is not
working
Check the distanse between the cabinet and
the magnet. Check that the jumber is removed.
Tip
If there is no radio connection between the master unit and the Alarmbox, first
move the units to a distance of approx. 2 meters in order to ensure that the radio
works.
Also check that the DIP switch 6 on the master unit is in OFF position.
If radio contact not can be established one Ontech Relay 9010 can be used as a
repeater if placed between the master unit and the Alarmbox.
Se the manual for the master unit for further instructions.
Declaration of conformity
Ondico AB, Datavägen 14A, 436 32 Askim, Sweden, hereby declares that the
product Ontech Alarmbox 9012 is in conformity with the provisions of the Radio
& Teleterminal directive R&TTE 1999/5/EG..
Status SMS
Below is shown an example of an status SMS and how it is interpreted.
Example Explanation
*Ontech9030 Asterix (*) means the alarm function is activated.
Units:
1; 2/24; 3/22 Indicates the IDs for the units connected to the master
unit. Also the temperature at each Alarmbox is indicated.
Temp:
24; 24,2 Indicates the temperature at the master unit.
Tstat:
OFF Indicates the status of the Thermostat function.
English
When the unit is alarming
When an alarm is activated an SMS will be sent to all mobile telephone numbers
on the alarm list. The red LED is double blinking 1-3 times. Up to ten different
persons can be alerted.
Below is shown an example of an alarm SMS.
Example Explanation
*Ontech9030 Asterix (*) means the alarm function is activated.
Alarm:
2a, 3b Indicates all alarms that have been activated since the
last acknowledge. A aafter the ID number means it is a
normal alarm. A bafter the ID number means it is a low
battery alarm. Se below.
Inputs:
2a Indicates the ID of the units where the alarm sensor is still
active. In this example it means the input in unit ID 2 is
active and must be deactivated before you acknowledge
the alarm.
Units:
1; 2/24; 3/22 Indicates the IDs for the units connected to the master
unit. Also the temperature at each Alarmbox is indicated.
Temp:
24; 24,2 Indicates the temperature at the master unit.
Tstat:
OFF Indicates the status of the Thermostat function.
Low battery warning
If the battery is low the unit will send an SMS with a bafter the ID number.
Replace the battery.
Technical specications
Short range radio Frequncy 2,4 GHZ
Power max 1 mW
Alarm inputs Activated by closing or opening function. The mag-
netic switch is activated with the attached magnet.
Power Litium battery 1/2 AA, 3 V. Will operate the unit
more than two years with normal usage.
Temperature range -20º C to +40ºC
15230_IB_EN_120801
www.ondico.se

Ontech Alarmbox 9012
Users manual
Acknowledge an alarm
When an alarm has been sent it has to be acknowledge before the unit can send
another alarm.
First make sure that the alarm sensor is not active, that is for example shut an
open door that is alarmed.
Then acknowledge by sending an SMS with the content ABCD#9#.
Compability
Ontech Alarmbox 9012 is fully compatible with master units with software revi-
sion R7 or higher.
For master units with software revision R6 or lower the temperature will not be
shown.
Alarmbox units ID will not be shown in status SMS more than one minute after
an update has been sent from the Alarmbox to the master unit.
See master units manual for instruction of how to check the software revision.
Troubble shooting
Symptom Reason
The LED is blinking all the
time
Dipswitches 6, 7 and 8 are all in position OFF.
Set valid ID.
Alarm messages is sent
continuously
Check that the cable jumper is connected on
the NC and GND connectors on the terminal (If
NC alarm sensor is connected there shall be no
jumper)
The magnetic switch is not
working
Check the distanse between the cabinet and
the magnet. Check that the jumber is removed.
Tip
If there is no radio connection between the master unit and the Alarmbox, first
move the units to a distance of approx. 2 meters in order to ensure that the radio
works.
Also check that the DIP switch 6 on the master unit is in OFF position.
If radio contact not can be established one Ontech Relay 9010 can be used as a
repeater if placed between the master unit and the Alarmbox.
Se the manual for the master unit for further instructions.
Declaration of conformity
Ondico AB, Datavägen 14A, 436 32 Askim, Sweden, hereby declares that the
product Ontech Alarmbox 9012 is in conformity with the provisions of the Radio
& Teleterminal directive R&TTE 1999/5/EG..
Status SMS
Below is shown an example of an status SMS and how it is interpreted.
Example Explanation
*Ontech9030 Asterix (*) means the alarm function is activated.
Units:
1; 2/24; 3/22 Indicates the IDs for the units connected to the master
unit. Also the temperature at each Alarmbox is indicated.
Temp:
24; 24,2 Indicates the temperature at the master unit.
Tstat:
OFF Indicates the status of the Thermostat function.
English
When the unit is alarming
When an alarm is activated an SMS will be sent to all mobile telephone numbers
on the alarm list. The red LED is double blinking 1-3 times. Up to ten different
persons can be alerted.
Below is shown an example of an alarm SMS.
Example Explanation
*Ontech9030 Asterix (*) means the alarm function is activated.
Alarm:
2a, 3b Indicates all alarms that have been activated since the
last acknowledge. A aafter the ID number means it is a
normal alarm. A bafter the ID number means it is a low
battery alarm. Se below.
Inputs:
2a Indicates the ID of the units where the alarm sensor is still
active. In this example it means the input in unit ID 2 is
active and must be deactivated before you acknowledge
the alarm.
Units:
1; 2/24; 3/22 Indicates the IDs for the units connected to the master
unit. Also the temperature at each Alarmbox is indicated.
Temp:
24; 24,2 Indicates the temperature at the master unit.
Tstat:
OFF Indicates the status of the Thermostat function.
Low battery warning
If the battery is low the unit will send an SMS with a bafter the ID number.
Replace the battery.
Technical specications
Short range radio Frequncy 2,4 GHZ
Power max 1 mW
Alarm inputs Activated by closing or opening function. The mag-
netic switch is activated with the attached magnet.
Power Litium battery 1/2 AA, 3 V. Will operate the unit
more than two years with normal usage.
Temperature range -20º C to +40ºC
15230_IB_EN_120801
www.ondico.se

Ontech Alarmbox 9012
Users manual
Acknowledge an alarm
When an alarm has been sent it has to be acknowledge before the unit can send
another alarm.
First make sure that the alarm sensor is not active, that is for example shut an
open door that is alarmed.
Then acknowledge by sending an SMS with the content ABCD#9#.
Compability
Ontech Alarmbox 9012 is fully compatible with master units with software revi-
sion R7 or higher.
For master units with software revision R6 or lower the temperature will not be
shown.
Alarmbox units ID will not be shown in status SMS more than one minute after
an update has been sent from the Alarmbox to the master unit.
See master units manual for instruction of how to check the software revision.
Troubble shooting
Symptom Reason
The LED is blinking all the
time
Dipswitches 6, 7 and 8 are all in position OFF.
Set valid ID.
Alarm messages is sent
continuously
Check that the cable jumper is connected on
the NC and GND connectors on the terminal (If
NC alarm sensor is connected there shall be no
jumper)
The magnetic switch is not
working
Check the distanse between the cabinet and
the magnet. Check that the jumber is removed.
Tip
If there is no radio connection between the master unit and the Alarmbox, first
move the units to a distance of approx. 2 meters in order to ensure that the radio
works.
Also check that the DIP switch 6 on the master unit is in OFF position.
If radio contact not can be established one Ontech Relay 9010 can be used as a
repeater if placed between the master unit and the Alarmbox.
Se the manual for the master unit for further instructions.
Declaration of conformity
Ondico AB, Datavägen 14A, 436 32 Askim, Sweden, hereby declares that the
product Ontech Alarmbox 9012 is in conformity with the provisions of the Radio
& Teleterminal directive R&TTE 1999/5/EG..
Status SMS
Below is shown an example of an status SMS and how it is interpreted.
Example Explanation
*Ontech9030 Asterix (*) means the alarm function is activated.
Units:
1; 2/24; 3/22 Indicates the IDs for the units connected to the master
unit. Also the temperature at each Alarmbox is indicated.
Temp:
24; 24,2 Indicates the temperature at the master unit.
Tstat:
OFF Indicates the status of the Thermostat function.
English
When the unit is alarming
When an alarm is activated an SMS will be sent to all mobile telephone numbers
on the alarm list. The red LED is double blinking 1-3 times. Up to ten different
persons can be alerted.
Below is shown an example of an alarm SMS.
Example Explanation
*Ontech9030 Asterix (*) means the alarm function is activated.
Alarm:
2a, 3b Indicates all alarms that have been activated since the
last acknowledge. A aafter the ID number means it is a
normal alarm. A bafter the ID number means it is a low
battery alarm. Se below.
Inputs:
2a Indicates the ID of the units where the alarm sensor is still
active. In this example it means the input in unit ID 2 is
active and must be deactivated before you acknowledge
the alarm.
Units:
1; 2/24; 3/22 Indicates the IDs for the units connected to the master
unit. Also the temperature at each Alarmbox is indicated.
Temp:
24; 24,2 Indicates the temperature at the master unit.
Tstat:
OFF Indicates the status of the Thermostat function.
Low battery warning
If the battery is low the unit will send an SMS with a bafter the ID number.
Replace the battery.
Technical specications
Short range radio Frequncy 2,4 GHZ
Power max 1 mW
Alarm inputs Activated by closing or opening function. The mag-
netic switch is activated with the attached magnet.
Power Litium battery 1/2 AA, 3 V. Will operate the unit
more than two years with normal usage.
Temperature range -20º C to +40ºC
15230_IB_EN_120801
www.ondico.se
Table of contents
Other Ontech Security System manuals
Popular Security System manuals by other brands

System Sensor
System Sensor CH1224 Installation and maintenance instructions

Core Insight
Core Insight PLT003 user manual

ADEMCO
ADEMCO VISTA Series Engineer's manual

Reliance Controls Corporation
Reliance Controls Corporation THP211 installation instructions

Toa
Toa VS-900 installation manual

X10
X10 MS12A Set up and operating instructions