
6
PROGRAMMING
Once the device is connected, enter ‘programming mode’ using the appropriate switch. In the programming mode it is possible to arm the direction
of connection of the CTs to the respective terminals are correct, check the sequence of phases, specify the size of the CTs supplied to the device,
change the address of the device on the BUS, test if connection of the digital input and that of the digital output are correct.
-
Use the switch located on
the bottom of the device (see
chapter “Components”) to
enter programming mode.
With the NanOMeter, it is
possible to interact with the
device using the three buttons
on the front. The upper and
lower buttons scroll through
the screens on the tab (if the
tab made up of several screens,
an arrow icon will appear on
the right corner of the screen)
while with the central key it is
possible to scroll through the
tabs (always viewable in the
The loading screen for programming
mode appears automatically once the
switch is activated.
In the rst tab it is pos-
sible to check the CT
connection status for the
individual phases. The
example shows the three
possible connection sta-
tuses. The rst status,
in green, conrms the
correct connection. The
second, in red, alerts of
an incorrect connection
order (you need to rever-
se the direction of the CT)
and the third, in yellow,
corresponds to an inde-
terminate connection sta-
tus (CT not connected or
load on the line is absent).
In the second tab you
can set the size of the CT
supplied to the meter. To
change the values, hold
down the central key of
the keypad (the editable
values are highlighted in
yellow with the selected
one ashing) and adjust
the values to the desi-
red numbers using the
scroll buttons. Press and
hold again to conrm the
change.
In this screen it is possible to program the device address on the BUS.
In the event an error occurs while attempting to save the address, an
“error” message will appear in red.Tthe green message “saved” will
conrm the operation completed successfully.
On the second page of the tab shown above, the phase sequence
is indicated. The rst example demonstrates that the order of the
voltage connections correspond to the order of the phases. In the
event that the phases are not ordered correctly, the second example
on the screen will appear, while the third example indicates an
indeterminate connection status.
1Checking Connections
2CT settings and EDS addresses
lower bar with the respective icon). A quick press
of the central button leads to the next tab while a
long press leads to the previous one.
Version 1.2 - Subject to change without notice