10
FC2E-U020 FC2E-U030 FC2E-U040 FC2E-U050 FC2E-U060 FC2E-U070
Total cooling capacity1) Lo/Med /Hi kW 1,6 / 1,8 / 2,4 1,9 / 2,9 / 4,0 2,8 / 3,5 / 4,7 3,4 / 4,4 / 6,1 3,7 / 5,5 / 7,2 4,1 / 6,5 / 9,6
Sensible cooling capacity1) Lo/Med/Hi kW 1,3 / 1,5 / 2,0 1,4 / 2,2 / 3,1 2,1 / 2,7 / 3,6 2,6 / 3,5 / 4,7 2,7 / 4,1 / 5,4 3,0 / 4,9 / 7,2
Water flow Lo/Med/Hi l/h 267 / 306 / 409 325 / 497 / 688 481 / 604 / 808 579 / 765 / 1050 640 / 944 / 1243 700 / 1119 / 1649
Water pressure drop Lo/Med/Hi kPa 4,2 / 6,9 / 11,2 3,5 / 8,6 / 14,6 6,8 / 11,4 / 18,6 8,4 / 13,1 / 22,2 3,4 / 7,6 / 11,7 5,8 / 13,1 / 24,6
Heating capacity2) Lo/Med /Hi kW 2,2 / 2,5 / 3,2 2,3 / 3,7 / 4,5 3,7 / 4,6 / 6,2 4,5 / 6,0 / 8,1 4,5 / 7,4 / 10,0 5,2 / 9,2 / 13,0
PAW-
FC4E-U020 FC4E-U030 FC4E-U040 - FC4E-U060 FC4E-U070
Total cooling capacity1) Lo/Med /Hi kW 1,4 / 1,5 / 2,0 2,0 / 2,7 / 3,4 2,6 / 3,2 / 4,0 - 3,0 / 5,0 / 6,6 3,2 / 6,1 / 7,9
Sensible cooling capacity1) Lo/Med/Hi kW 1,2 / 1,4 / 1,9 1,5 / 2,1 / 2,6 2,1 / 2,6 / 3,3 - 2,3 / 3,8 / 5,1 2,6 / 4,7 / 6,3
Water flow Lo/Med/Hi l/h 234 / 262 / 344 344 / 464 / 581 442 / 556 / 690 - 516 / 858 / 1144 549 / 1041 / 1366
Water pressure drop Lo/Med/Hi kPa 6,6 / 9,1 / 14,0 4,4 / 8,2 / 11,7 6,7 / 10,9 / 15,5 - 6,0 / 14,1 / 22,4 7,2 / 19,2 / 30,1
Heating capacity2) Lo/Med /Hi kW 0,8 / 0,9 / 1,2 2,2 / 3,1 / 3,8 3,0 / 3,5 / 4,1 - 3,7 / 5,5 / 7,0 4,5 / 7,1 / 9,8
Water flow Lo/Med/Hi l/h 132 / 153 / 201 374 / 530 / 658 521 / 603 / 699 - 636 / 939 / 1210 776 / 1214 / 1686
Water pressure drop Lo/Med/Hi kPa 25,7 / 33,4 / 53,6 13,7 / 24,2 / 35,0 24,2 / 30,9 / 39,8 - 7,6 / 13,8 / 20,7 10,2 / 20,8 / 36
1) According to Eurovent standard. Air: 27°C DB / 19°C WB. Water in/out: 7°C / 12°C.
2) According to Eurovent standard. Air: 20°C. Water in/out: 45°C / 40°C.
5. Installation
CAUTION
- The unit installation work must be done by qualified personnel according to the local rules and this manual.
- The unit should not be installed in a bathroom, a laundry, a sauna or a swimming-pool.
During the installation:
•Take care to avoid any rough handling or impacts when
unloading and moving the appliance.
•Before hoisting into position, test lift to insure stability and
balance. Avoid twisting or uneven lifting of the units.
•The units shall be carefully inspected before unit
installation to make sure that no handling damage has
occurred.
•All these sections have been inspected before leaving the
factory. It is therefore important to insure that no bolts,
screws or other fixing system are loosened or missing
before the commissioning. During the handling of the
machine it is mandatory to provide all the devices
necessary to guarantee personal safety.
5.1 Unit location – Recommendations
Select the unit location with the following aspects in mind:
•Choose an area free from obstructions which may cause
uneven air distribution and/or return.
•Consider using an area where installation is easy.
•Choose a position that allows for the clearances required.
•Look for a position in the room which ensures the best
possible air distribution.
•Install unit in a position where condensate can easily be
piped to an appropriate drain.
Positions to avoid:
•Exposure to direct sunlight.
•Exposure to oil vapours.
•Areas close to heat sources.
•Installation in areas with high frequency waves.
•On damp walls or in positions that may be exposed to
water hazard.
•Where curtains or furniture may obstruct free air circulation.
•Positions too close to heating sources which may damage
the unit.