7
(EN)
Setting Up Remote Controller Functions
The functions of the wireless remote controller can be set on site.
(These settings are saved in nonvolatile memory in the remote controller. Therefore, the settings do 
not revert to the defaults even when its batteries are changed.)
<Note> Only service personnel should make the settings because the operation of the air conditioner 
may be affected, depending on the settings made. 
Furthermore, making changes to these settings may cause actual operation to deviate from 
what is printed in the Operating Instructions, so be sure to fully explain this to the customer.
Making Settings (Do with unit stopped)
(1) Holding down the swing/flap ( ) + OFF timer ( ) + mode select ( ) buttons at the same 
time for 4 or more seconds will open the setting screen. (See figure below.) 
(2) Use the Temperature setting buttons / ( ) to select the number of the item to be set.
(3) Use the ON timer buttons / ( ) to change settings.
(4) The settings are saved with the once/every day button ( ). When this is done, the SET displayed 
on the LCD changes from blinking to lighting.
(5) If other settings are to be changed, repeat steps (2) to (4).
(6) When all settings have been made, press the start/stop ( ) button.
Operation procedure and 
function display
Item 
Number
(1)
(2)
(6)
(3)
(4)
Detected contents Set Contents Factory
setting
1 Operation Mode
2 Flap Display (No Display)
 (*1)
3 Select Fan Speed (No Display)
4 Display of Set 
Temperature 
°C °F Setting Off (*2) °C
5 Time Display 24 Hour (No Display) AM/PM 24 Hour
6 Ventilation Fan 
ON/OFF
OFF (No Display) ON OFF 
(*3)
7 Cool temp Max 05 to 35°C 30
8 Cool temp Min 05 to 35°C 18
9 Heat temp Max 05 to 35°C 30 (*4)
10 Heat temp Min 05 to 35°C 16
11 Dry temp Max 05 to 35°C 30
12 Dry temp Min 05 to 35°C 18
13 Auto temp Max 05 to 35°C 27
14 Auto temp Min 05 to 35°C 17
16 Address Setting 
Max Value
00 (ALL only) 01 to 031 06 (*5)
17 Heat temp Max 
ON/OFF
JP (Heater Max Temp Change 
Off) EP (ON)
JP
Attention
While the unit is in the SWING mode (swing/flap), the flap cannot be stopped in a desired position.
When Setting OFF is selected, “°C” is displayed on the LCD.
You can toggle between ON and OFF by pressing ventilation “( )”button for 4 seconds or more.
If the Heater Max ON/OFF setting is not changed to EP (ON), the setting change will not be 
reflected.
This is the number of addresses that can be set in the address change mode. Do not set it to 07 or 
above.