3.2 Function
K35 - 3-temperature mixing valve with additional
connection for a second flow temperature
The 3-temperature mixing valve is used in combination
with a buffer tank which can be heated either by a solar
installation, a solid fuel boiler or a conventional boiler.
If the consumer only needs a low temperature level, such
as for radiant panel heating systems, the 3-temperature
mixing valve first takes the flow water from the
intermediate part of the storage tank. Only when the
temperature in this part is no longer sufficient, the hot
water from the upper part of the tank is used.
Application range:
●Heating systems with buffer
tank & solar heating support
●Control of radiant floor
heating & panel heating
systems
By using two parts of the storage tank for two different
flow temperatures, the energy from the buffer tank can be
used more efficiently.
The return temperatures are low and the stratification in
the buffer tank is maintained.
3.2.1 3-temperature mixing valve [specialist]
The 3-temperature mixing valve, driven by an electric actuator, adjusts the flow temperature of the
consumer circuit to the required value by means of the flow sensor and the controller. It is equipped
with a second flow connection (C-3) on the back side. This connection allows to withdraw water with a
lower flow temperature from the intermediate part of the tank, f. ex. of a buffer tank.
K35: A check valve is integrated in this second flow connection to avoid unwanted circulation in the
mixing valve. This check valve is designed for heating pumps with a maximum head of 7 m. If you
want to use a more powerful pump, an additional check valve may be necessary in the feed line.
MC45: A non-return valve (D-1) prevents unwanted circulation.