manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. PDK
  6. •
  7. Controllers
  8. •
  9. PDK Red 4 User manual

PDK Red 4 User manual

3. Reader Connection2. Mounting Controller
6. Locking Relay
5. Input B / REX Connection4. Input A / DPS Connection
1. Package Contents
Jumpers (8) Diode (4)
Red 4
Four Door Controller (1) Battery Leads (1)
Can Lock (1)
Mount - Mount the Red 4 enclosure securely to a wall.
POWER
HEART
LINK
BUS
+-BUS
+-
BUS
+-BUS
+-
POE IN
POE OUT
12-24
BATTERY
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
OSDP OSDP
OSDP OSDP PORT2
PORT3
PORT4
PORT1
AReader(s) - Use a 22/5 or 22/6 wire to wire the reader to the controller, as
shown above. Be sure to check polarity and voltage prior to powering the
controller.
BOSDP - Place jumper to enable OSDP (see OSDP reference guide at the end
of this guide for more info)
OSDP
Wiring
+
-
0 1 L
B
AReader(s)
POWER
HEART
LINK
BUS
+-BUS
+-
BUS
+-BUS
+-
POE IN
POE OUT
12-24
GND
+
BATTERY
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
OSDP OSDP
OSDP OSDP PORT2
PORT3
PORT4
PORT1
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
A
A
A
OSDP
+
ADPS (Door Position Switch) - The DPS is mounted on the door frame in the
desired location with a 22/2 wire running from the DPS to the controller.
Wire the DPS to the controller as shown above. When using two DPS sensors
for double doors, you will wire them in series with only two conductors
running back to the controller for connection.
AUX Input - A rule can be set up to trigger events or outputs based on this
input trigger.
B
POWER
HEART
LINK
BUS
+-BUS
+-
BUS
+-BUS
+-
POE IN
POE OUT
12-24
GND
+
BATTERY
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
OSDP OSDP
OSDP OSDP PORT2
PORT3
PORT4
PORT1
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
A
DPS Contact
B
A
-
B
Double
DPS Contact
Maglock - When installing a Maglock, it is typical to install a REX (Request to
Exit) at the door for free egress. Run an 18/2 wire from the Maglock to the
Door Controller, connecting to the Maglock as shown.
REX (Request to Exit) - The REX is mounted in the desired location with an
18/5 wire ran from the REX to the controller. Wire the REX to the controller
and Maglock, as shown above. If reporting is not needed in the system, simply
eliminate the green-labeled wire.
A
B
Jumper Block(s) -Use to designate (+) or (-) board voltage out of NO and NC.
If the jumper is off, the relay is a standard dry contact needing input into
common.
C
AUX Input - A rule can be set up to trigger events or outputs based on this input trigger.
If using a powered REX,
run to any 12VDC output
on controller.
POWER
HEART
LINK
BUS
+-BUS
+-
BUS
+-BUS
+-
POE IN
POE OUT
12-24
GND
+
BATTERY
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
OSDP OSDP
OSDP OSDP PORT2
PORT3
PORT4
PORT1
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
Maglock
BREX
A
CBUS
+-
POWER
HEART
LINK
BUS
+-BUS
+-
BATTERY
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
OSDP OSDP PORT2
PORT1
D
BUS
+-
C
A
BOR
Diode - The provided diode must be installed when using a strike. Install at
the strike with the grey stripe of the diode on positive and the black on
negative.
A
NC - Used for maglocks (or strikes in fail-safe configuration). Connect the
negative (-) of the maglock or strike to NC on the door controller.
B
NO - Used for strikes in fail-secure configuration. Connect the negative (-) of
the strike to NO on the door controller.
C
Jumper Block - Use to designate (+) or (-) board voltage out of NO and NC. If
the jumper is off, the relay is a standard dry contact needing input into
common.
D
Reference Guide
8. Power Connection
OSDP Reference Guide
7. Communication Connections
POWER
HEART
LINK
BUS
+-BUS
+-
BUS
+-BUS
+-
POE IN
POE OUT
12-24
GND
+
BATTERY
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
OSDP OSDP
OSDP OSDP PORT2
PORT3
PORT4
PORT1
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
Ethernet - All Red controllers come with a built-in RJ45 connection for
network connectivity. Once connected, the Red 4 controller is
Self-Discoverable from pdk.io using IPV6. Alternatively, you may use IPV4
or assign a static IP using pdk.io if desired.
A
Wireless (PN: RMW) and
PoE (PN: RMPOE) module
kits can be purchased for
optional communication
add-ons.
A
POWER
HEART
LINK
BUS
+-BUS
+-
BUS
+-BUS
+-
POE IN
POE OUT
12-24
BATTERY
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
+
-
0 1 L A
-
B NC NOC
OSDP OSDP
OSDP OSDP PORT2
PORT3
PORT4
PORT1
DC Input - Use the included 12VDC, 5 amp transformer for DC power input.
It is recommended to use 18/2 wire. For high voltage applications, use the HV
converter (PN: HVC)
Battery - The enclosure will fit most 12 VDC 8 Ah batteries. The battery is
connected with supplied leads and is polarity sensitive. Receive up to 8 hrs of
battery backup using a strike in fail-secure.
A
B
Battery
12 VDC / 8 Ah
BUS
+-
BUS
+
POE IN
12-24
GND
+
BATTERY
+
-
0 1 L A
-
B NC NOC
OSDP
OSDP PORT2
PORT4
+
-
0 1 L A
-
B NC NOC
B
A
What is OSDP - Open Supervised Device Protocol (OSDP) is an access control
communications standard developed by the Security Industry Association to
improve interoperability among access control and security products. OSDP
brings heightened security and improved functionality. It is more secure than
Wiegand and supports AES-128 encryption.
OSDP Wire Specication - Four (4) conductor twisted pair shielded is
recommended to remain fully TIA-485 compliant at the maximum supported
baud rates and cable distances.
NOTE - It’s possible to reuse existing Wiegand wiring for OSDP. However, using a
simple stranded cable typical of Wiegand readers generally does not meet the
RS485 twisted pair recommendations.
OSDP Multi-Drop - Multi-drop gives you the capability to accommodate
many readers by running one length of 4-conductor cable, eliminating the
need to run wire for each wire.
NOTE - Four (4) is the maximum number of readers each port can support.
NOTE - Wiegand readers will not work when OSDP jumpers are installed.
Fire Input - To integrate the fire system using a Red 4 door controller, refer to
wiring diagrams in the Partner Portal at
prodatakey.zendesk.com
Programming - After the Red 4 door controller has been connected back to
the Cloud Node, access the configuration software as instructed in the
programming manual. This manual is available for download at
prodatakey.zendesk.com
Reader Compatibility - ProdataKey does not require proprietary readers.
Door controllers accept a Wiegand input, including biometric readers and
keypads. OSDP readers are supported by using an included jumper (see
OSDP reference guide). Contact support for details.
UL 294 Compliance - All equipment must meet appropriate UL certifications.
For UL listed installations, all cable runs must be less than 30 meters (98.5’)
Part Number - R4
PDK Technical Support
Phone: 801.317.8802 option #2
Email: support@prodatakey.com
PDK Knowledge Base: prodatakey.zendesk.com
www.prodatakey.com
801.317.8802
REV 12142021
View the user manual here:
prodatakey.zendesk.com
PN:R4
Copyright © 2021 ProdataKey Inc. All rights reserved. Pdk, Pdk io, and
the Red logos are trademarkes of ProdataKey Inc.
Quick Start Guide

This manual suits for next models

1

Other PDK Controllers manuals

PDK Red gate RGE User manual

PDK

PDK Red gate RGE User manual

PDK Red 8 User manual

PDK

PDK Red 8 User manual

PDK Red 2 User manual

PDK

PDK Red 2 User manual

PDK Red 1 User manual

PDK

PDK Red 1 User manual

PDK Red RGE User manual

PDK

PDK Red RGE User manual

PDK Red 2 User manual

PDK

PDK Red 2 User manual

PDK Red 1 User manual

PDK

PDK Red 1 User manual

PDK RED 2 User manual

PDK

PDK RED 2 User manual

PDK Red Pedestal RPE User manual

PDK

PDK Red Pedestal RPE User manual

Popular Controllers manuals by other brands

Seac Sub SORIUS 1000 instruction manual

Seac Sub

Seac Sub SORIUS 1000 instruction manual

DSC PowerSeries Neo 3G8080I installation manual

DSC

DSC PowerSeries Neo 3G8080I installation manual

MZ electronic KOMPASS-8-868 Instructions for use

MZ electronic

MZ electronic KOMPASS-8-868 Instructions for use

GF Signet 8900 user manual

GF Signet

GF Signet 8900 user manual

Innotech GENII CSFCAH REM manual

Innotech

Innotech GENII CSFCAH REM manual

Prevac MG15 user manual

Prevac

Prevac MG15 user manual

Omnitronic KEY-2816 user manual

Omnitronic

Omnitronic KEY-2816 user manual

Datakom D Series user guide

Datakom

Datakom D Series user guide

anytronics Anyscene 512 Installation and operation guide

anytronics

anytronics Anyscene 512 Installation and operation guide

Christie TVC-500 user manual

Christie

Christie TVC-500 user manual

Nelson SoloRain DuraLife 8020 instructions

Nelson

Nelson SoloRain DuraLife 8020 instructions

Honeywell S4965V3250 Functional description

Honeywell

Honeywell S4965V3250 Functional description

gefran GEFLEX GFX-M1 Series Operating instructions and warnings

gefran

gefran GEFLEX GFX-M1 Series Operating instructions and warnings

Siemens SIMATIC S7-1200 System manual

Siemens

Siemens SIMATIC S7-1200 System manual

Philips Light System Manager installation instructions

Philips

Philips Light System Manager installation instructions

AMX AXB-EM232 Specifications

AMX

AMX AXB-EM232 Specifications

Trust OCTOPUS Online manual

Trust

Trust OCTOPUS Online manual

Kantech Door Controller Innovative and Powerful... installation manual

Kantech

Kantech Door Controller Innovative and Powerful... installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.