3. Reader Connection
2. Mounting Controller
6. Locking Relay
5. Input B / REX Connection4. Input A / DPS Connection
1. Package Contents
Jumpers (4)
Diodes (2)
Red Gate Controller (1)
Battery Leads (1)
Enclosure Screws (4)
Mount - Mount the Red Gate enclosure securely to a wall.
+
-
0 1 L +
-
0 1 L
A
-
B A
-
B NC NOCNC NOC 12VDC
+GND
OSDP
OSDP
PORT1
BUS
+-
PORT2
BUS
+-
ETHERNET
POWER
HEART
LINK
ACTIVITY
BATTERY
POE IN
POE OUT
OSDP
Wiring
D
+
-
0 1 L +
-
0 1 L
A
-
B A
-
B NC NOCNC NOC 12VDC
+GND
OSDP
OSDP
PORT1
BUS
+-
PORT2
BUS
+-BATTERY
B
C
AReader
Red Gate Controller
+
-
0 1 L
AMain Reader - The main reader is mounted at the door with a 22/5 or 22/6
wire ran to the door controller. Wire the reader to the controller as shown
above. Be sure to check polarity and voltage prior to powering the controller.
BSecondary Reader - Wire the second reader to the controller as shown
above. Be sure to check polarity and voltage prior to powering the controller.
DPiezo - Can be connected to available relay and configured with software.
COSDP - Place jumper(s) to enable OSDP (see OSDP reference guide at the
end of this guide for more info)
+
-
0 1 L +
-
0 1 L
A
-
B A
-
B NC NOCNC NOC 12VDC
+GND
OSDP
OSDP
PORT1
BUS
+-
PORT2
BUS
+-BATTERY
Double DPS
Contact
A
+
-
0 1 L +
-
0 1 L
A
-
B A
-
B NC NOCNC NOC 12VDC
+GND
OSDP
OSDP
PORT1
BUS
+-
PORT2
BUS
+-BATTERY
DPS (Door Position Switch) - The DPS is mounted on the door frame in the
desired location with a 22/2 wire running from the DPS to the controller.
Wire the DPS to the controller as shown above. When using two DPS sensors
for double doors, you will wire them in series with only two
conductors running back to the controller for connection.
AUX Input - A rule can be set up to trigger events or outputs based on this
input trigger.
B
DPS Contact
A
B
+
-
0 1 L +
-
0 1 L
A
-
B A
-
B NC NOCNC NOC 12VDC
+GND
OSDP
OSDP
PORT1
BUS
+-
PORT2
BUS
+-BATTERY
If using a powered REX,
run to any 12VDC
output on controller.
B
A
Maglock
REX
C
PORT1
BUS
+-
Maglock - When installing a Maglock, it is typical to install a REX (Request to
Exit) at the door for free egress. Run an 18/2 wire from the Maglock to the
door controller, connecting to the Maglock as shown.
REX (Request to Exit) - The REX is mounted in the desired location with an
18/5 wire ran from the REX to the controller. Wire the REX to the controller
and Maglock, as shown above. If reporting is not needed in the system, simply
eliminate the green-labeled wire.
A
B
Jumper - Use the designated jumper(s) to energize the relay output NO and
NC to utilize the output as a wet contact.
C
Gate Operator - Follow the gate operator wiring instructions to connect the
gate operator to an ELK 912B Isolation Relay.
Isolation Relay - Installation of an ELK 912B Isolation relay is recommended
to prevent electrical damage to the Red Gate, Isolation relay is
sold separately.
Locking Relay - Connect the ELK 912B Isolation relay to the Red Gate by
connecting the positive wire into a positive port and the negative wire into
the NO port on the board.
Jumper - Use the designated jumper(s) to energize the relay output to be NO
by placing the jumper on the negative (-) and center pins.
+
-
0 1 L +
-
0 1 L
A
-
B A
-
B NC NOCNC NOC 12VDC
+GND
OSDP
OSDP
PORT1
BUS
+-
PORT2
BUS
+-BATTERY
C
A
D
B
NO NO
COM
D2
Wiring from Gate Operator
-
+
PORT1
BUS
+-
ELK 912B
Isolation Relay
(sold separately)
A
B
C
D
Reference Guide
8. Power Connection
OSDP Reference Guide
7. Communication Connections
Ethernet - All Red controllers come with a built-in RJ45 connection for
network connectivity. Once connected, the Red Gate controller is Self-Dis-
coverable from pdk.io using IPV6. Alternatively, you may use IPV4 or
assign a static IP using pdk.io if desired.
A
PORT1
BUS
+
PORT2
ETHERNET
POWER
HEART
LINK
ACTIVITY
POE IN
POE OUT
A
+
-
0 1 L
A
-
B A
-
B NC NOCNC NOC 12VDC
+GND
OSDP
PORT1
BUS
+-
PORT2
BUS
+-BATTERY
DC INPUT - Use included 14 VDC, 2 Amp transformer for DC power
input. It is recommended to use 18/2 wire. For high voltage applications, use
the HV Converter (PN: HVC).
BATTERY - The enclosure will fit most 12 VDC 1.2 Ah batteries.
The battery is connected with supplied leads and is polarity sensitive.
A
A
B
Battery
12 VDC / 1.2 Ah
B
What is OSDP - Open Supervised Device Protocol (OSDP) is an access control
communications standard developed by the Security Industry Association to
improve interoperability among access control and security products. OSDP
brings heightened security and improved functionality. It is more secure than
Wiegand and supports AES-128 encryption.
OSDP Wire Specification - Four (4) conductor twisted pair overall shield is
recommended to remain fully TIA-485 compliant at maximum supported baud
rates and cable distances.
NOTE - It’s possible to reuse existing Wiegand wiring for OSDP, however, using
simple stranded cable typical of Wiegand readers generally does not meet the
RS485 twisted pair recommendations.
OSDP Multi-Drop - Multi-drop gives you the capability to accommodate
many readers by running one length of 4-conductor cable, eliminating the
need to run wire for each wire.
NOTE - Four (4) is the maximum number of readers each port can support.
NOTE - Wiegand readers will not work when OSDP jumpers are installed.
Fire Input - To integrate the fire system using a Red gate, refer to wiring
diagrams at prodatakey.zendesk.com
Programming - After the Red Gate controller has been installed, full
configuration and system programming will be performed within the pdk io
software. Full configuration instructions can be found in the programming
manual at prodatakey.zendesk.com
Reader Compatibility - ProdataKey does not require proprietary readers.
Door controllers accept a wiegand input, including biometric readers and
keypads. OSDP readers are supported by using included jumper (see OSDP
reference guide). Contact support for details.
UL 294 Compliance - All equipment must meet appropriate UL certifications.
For UL listed installations, all cable runs must be less than 30 meters (98.5’)
Part Number - RGE
PDK Technical Support
Phone: 801.317.8802 option #2
Email: support@prodatakey.com
PDK Knowledge Base: prodatakey.zendesk.com www.prodatakey.com
801.317.8802
REV 12162021
View the user manual here:
prodatakey.zendesk.com
PN:RGE
Copyright © 2021 ProdataKey Inc. All rights reserved. Pdk, Pdk io, and
the Red logos are trademarkes of ProdataKey Inc.
Quick Start Guide
gate
outdoor controller
ethernet

Other PDK Controllers manuals

PDK Red Pedestal RPE User manual

PDK

PDK Red Pedestal RPE User manual

PDK RED 2 User manual

PDK

PDK RED 2 User manual

PDK Red RGE User manual

PDK

PDK Red RGE User manual

PDK Red 2 User manual

PDK

PDK Red 2 User manual

PDK Red 1 User manual

PDK

PDK Red 1 User manual

PDK Red 1 User manual

PDK

PDK Red 1 User manual

PDK Red 8 User manual

PDK

PDK Red 8 User manual

PDK Red 4 User manual

PDK

PDK Red 4 User manual

PDK Red 2 User manual

PDK

PDK Red 2 User manual

Popular Controllers manuals by other brands

GYS GYSPack 610 manual

GYS

GYS GYSPack 610 manual

Capella AX5000 Series manual

Capella

Capella AX5000 Series manual

Linear Technology Analog Devices LT8708 datasheet

Linear Technology

Linear Technology Analog Devices LT8708 datasheet

SUNFORGE Genasun GVB-8-WP Series manual

SUNFORGE

SUNFORGE Genasun GVB-8-WP Series manual

HIMA HIMatrix manual

HIMA

HIMA HIMatrix manual

Helios EDR Installation and Operation Specification

Helios

Helios EDR Installation and Operation Specification

Cisco CS-MARS-20-K9 - Security MARS 20 user guide

Cisco

Cisco CS-MARS-20-K9 - Security MARS 20 user guide

Gemini Valve 600 Series Technical data sheet

Gemini Valve

Gemini Valve 600 Series Technical data sheet

Ropex RES-225 operating instructions

Ropex

Ropex RES-225 operating instructions

Gardner Denver GD Connect 12 manual

Gardner Denver

Gardner Denver GD Connect 12 manual

YASKAWA Z1000 CIMR-ZU*A Series user manual

YASKAWA

YASKAWA Z1000 CIMR-ZU*A Series user manual

Victron energy CCGX manual

Victron energy

Victron energy CCGX manual

ABB ACS 800 Series Application guide

ABB

ABB ACS 800 Series Application guide

opti-solar SC-Max series user manual

opti-solar

opti-solar SC-Max series user manual

Danfoss AMV 150 instructions

Danfoss

Danfoss AMV 150 instructions

GCE druva PTLH0FT Instructions for use

GCE druva

GCE druva PTLH0FT Instructions for use

Anviz DAC844 user manual

Anviz

Anviz DAC844 user manual

Martin M6 Series instructions

Martin

Martin M6 Series instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.