manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Pedigo
  6. •
  7. Medical Equipment
  8. •
  9. Pedigo P-2140 User manual

Pedigo P-2140 User manual

OPERATION & CARE
MANUAL FOR
P-2140 & P-2145
FLUID & BLANKET
WARMING
COMBINATION
CABINETS
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
1
UNPACKING AND SET-UP
Transport and Storage Environmental Conditions (not to exceed 15 days)
•Ambient temperature range of -40°to +159°F (-40°to +70°C)
•Relative humidity range of 10% to 100%, including condensation
•Atmospheric pressure range of 50KPa to 106KPa
COMBINATION BLANKET /FLUID WARMING CABINET
DELIVERY
The Pedigo Fluid Cabinet has been thoroughly tested
and inspected to insure only the highest quality unit is
provided. Upon receipt, check for any possible
shipping damage and report it at once to the
delivering carrier. See Transportation Damage and
Claims section located in this manual.
This appliance, complete with unattached items and
accessories, may have been delivered in one or more
packages. Check to ensure that all standard items
and options have been received with each model as
ordered.
Save all the information and instructions packed with
the appliance. Complete and return the warranty
card to the factory as soon as possible to assure
prompt service in the event of a warranty parts and
labor claim.
This manual must be read and understood by all
people using or installing the equipment model.
Contact the Pedigo service department if you have
any questions concerning installation, operation, or
maintenance.
NOTE: All claims for warranty must include the full
model number and serial number of
the unit.
UNPACKING
1. Carefully remove the
appliance from the carton or
crate.
NOTE: Do not discard the
carton and other
packaging material
until you have
inspected the unit
for hidden damage
and tested it for
proper operation.
2. Read all instructions in this manual carefully before
initiating the installation of this appliance.
DO NOT DISCARD THIS MANUAL.
This manual is considered to be part of the
appliance and is to be provided to the owner
or manager of the business or to the person
responsible for training operators. Additional
manuals are available from the Pedigo
service department.
3. Remove all protective plastic film, packaging
materials, and accessories from the appliance
before connecting electrical power.
TRANSPORT AND STORAGE
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
2
SAFETY PROCEDURES AND PRECAUTIONS
Knowledge of proper procedures is essential to the
safe operation of electrically and/or gas energized
equipment. In accordance with generally accepted
product safety labeling guidelines for potential hazards,
the following signal words and symbols
may be used throughout this manual.
Used to indicate the presence
of a hazard that will cause
severe personal injury, death,
or substantial property
damage if the warning
included with this symbol is
ignored.
Used to indicate the
presence of a hazard that
can cause personal injury,
possible death, or major
property damage if the
warning included with this
symbol is ignored.
Used to indicate the
presence of a hazard that can
or will cause minor or
moderate personal injury or
property damage if the
warning included with this
symbol is ignored.
Used to indicate the presence
of a hazard that can or will
cause minor personal injury,
property damage, or a
potential unsafe practice if the
warning included with this
symbol is ignored.
Used to notify personnel of
installation, operation, or
maintenance information that
is important but not hazard related.
1. Enthermics blanket warmers are intended for
warming cotton blankets ONLY. No other use
for this device is authorized or recommended.
Enthermics fluid warmers are ONLY intended
for warming medical solutions for irrigation and
injection. The IRRIGATION MODE should be
selected for warming irrigation fluids, and the
INJECTION MODE should be selected for warming
injection fluids. Please refer to the labeling of the
manufacturer of the products to be warmed
regarding the recommended temperature and the
duration of warming. No other use for this device
is authorized or recommended.
2. This device is intended for use in commercial
establishments where all operators are familiar
with the purpose, limitations, and associated
hazards of this device. Operating instructions and
warnings must be read and understood by
all operators and users.
3. Any troubleshooting guides, component views, and
parts lists included in this manual are for general
reference only and are intended for use by qualified
technical personnel.
4. This manual should be considered a permanent
part of this device. This manual and all supplied
instructions, diagrams, schematics, parts lists,
notices, and labels must remain with the device
if the item is sold or moved to another location.
NOTE:
Enthermics warmers should not be left unattended for
periods of more than 24 hours. In case of absences
longer than 24 hours, disconnect the warmer from its
power source.
Pedigo warmers should not be left unattended for
periods of more than 24 hours. In case of absences
longer than 24 hours, disconnect the wamrer from
its power source.
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
3
DANGER
DO NOT use this warming cabinet in
the presence of flammable
anesthetic mixture (with air or with
oxygen or nitrous oxide).
THIS COULD RISK AN EXPLOSION!
IMPORTANT
Do not load the metal basket beyond the
recommended maximum capacity:
P-2140 = 14 liters per basket
P-2145 = 30 liters per basket
Overloading may cause lower or uneven
temperatures of product and damage to basket
and basket rail supports. Baskets that are
overloaded may slip off rail supports, resulting
in possible damage to product and equipment,
as well as causing possible injury.
Hazardous
Voltage Present
Protective Earth
Ground Symbol
POWER REQUIREMENTS - P-2140
120 V.A.C. — 50/60 Hz, 1 ph
1920 Watts, 16.0. Amps
Safety Class I Equipment
Medical Equipment classified by Underwriters
Laboratories with Respect to Electrical Shock, Fire
and Mechanical Hazards only, in Accordance with
UL 60601-1 and CAN/CSA C22.2 No. 601.1.
UL File No.
E201645
Grounding reliability can only be achieved when equipment is
connected to an equivalent receptacle marked “Hospital Grade.”
NEMA 5-20P
20A - 125V Plug
Hospital Grade
POWER REQUIREMENTS - P-2145
120 V.A.C. — 50/60 Hz, 1 ph
1920 Watts, 16.0 Amps
Safety Class I Equipment
NEMA 5-20P
20A - 125V Plug
Hospital Grade
CAUTION
INJECTION FLUIDS
SHOULD NOT BE WARMED
OVER 110°F (43°C)
CAUTION
THIS UNIT HAS NOT BEEN
APPROVED FOR WARMING OF
BLOOD OR BLOOD PRODUCTS.
DANGER
ENSURE POWER SOURCE
MATCHES VOLTAGE STAMPED
ON APPLIANCE NAMEPLATE.
ELECTRICAL INFORMATION
The power specifications are located on the unit identification nameplate. This nameplate is
permanently attached to the unit and must be located to verify power requirements.
PREPARATION
Before operating the cabinet, clean both the interior and exterior of the unit with a damp cloth and mild soap
solution. Wipe with an appropriate disinfectant. Clean and install the cabinet basket support assembly and
the blanket support assembly.
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
4
GENERAL INFORMATION
This warming cabinet is designed to safely store warm
irrigation or injection fluids and blankets.
The dual-chambered warming cabinet is constructed with
a 20 gauge stainless steel exterior casing and door with
handles and hinges designed to withstand heavy usage. A
door with window allows observation of inventory with
the door closed. The cabinet is warmed using the
patented Halo Heat®low-heat-density electrothermal
cable array. The electrothermal cable is positioned in the
floor and two sides of the warming cabinet, providing
even heating of the interior chamber. Each chamber
temperature is regulated by a separate electronic control.
A fan located inside the chamber mixes the air to prevent
temperature stratification and to ensure an accurate
chamber temperature within +0/-2°F (+0/-1.1°C) of the
set point for temperatures up to 110°F (43°C) and within
+0/-3ºF (+0/-1.7°C) of the set point for temperatures
above 110° to 150°F (43°C to 66°C). Each chamber has
an individual electronic control consisting of a 4 digit
L.E.D. display, ON/OFF key, INCREASE and DECREASE
keys, integrated LOCK feature and a series of prompt
sequence indicators.
The blanket warming chamber has an adjustable
temperature range of 98° to 200°F (37° to 94°C). This
chamber also has a TIMER mode that allows the user to
program the control to automatically turn on and turn off
once during a 24-hour period at a selected time. This
enables the blanket warming chamber (only) to be shut
off automatically at night to save energy, but to turn on
again in the early morning to ensure warm blankets are
available.
The fluid warming chamber can be programmed to
warm either irrigation fluids (IRR) or injection fluids
(INJ), with separate temperature ranges provided
depending on the choice selected. The P-2140 IRR
temperature may be adjusted from 98° to 150°F (37° to
66°C), and the INJ temperature can be adjusted from 98°
to 110°F (37° to 43°C). The P-2145 IRR temperature
may be adjusted from 98° to 150°F (37° to 66°C), and the
INJ temperature can be adjusted from 98° to 110°F (37° to
43°C). An alarm will sound if temperatures exceed 10°F
(6°C) over the set-point temperature, and a TEMP
indicator will blink indicating an over-temperature
condition.
A warming shut-off system, separate from the electronic
controls, prevents overheating. The electronic controls
can easily be set to operate in Fahrenheit or Celsius.
After a power failure, the cabinet will remember its
programming and begin to operate as before. The
ON/OFF indicator will blink to indicate a failure
occurred; pressing the ON/OFF key once will eliminate
this blinking.
P-2140 CAPACITY
The blanket warming chamber contains an epoxy-coated
blanket support assembly and one (1) shelf. The fluid
warming chamber is equipped with three (3) white,
epoxy-coated wire baskets to accommodate fluids
packaged in bags or bottles, mounted on basket rail
supports. Each basket has a 14 liter maximum
capacity. The cabinet is furnished with a full perimeter
rubber bumper assembly for exterior protection, and one
(1) set of 5" (127mm) heavy-duty casters, two with
locking brake.
P-2145 CAPACITY
The blanket warming chamber contains an epoxy-coated
blanket support assembly and two (2) shelves. The fluid
warming chamber is equipped with one (1) white, epoxy-
coated metal basket to accommodate fluids packaged in
bags or bottles, mounted on basket rail supports. The
basket has a maximum capacity of 30 liters. The
cabinet is furnished with one (1) set of 5" (127mm) heavy-
duty casters, two with locking brake.
CAUTION
THIS UNIT HAS NOT BEEN
APPROVED FOR WARMING OF
BLOOD OR BLOOD PRODUCTS.
DANGER
AT NOTIME SHOULDTHE INTERIOR
OR EXTERIOR BE STEAM CLEANED,
HOSED DOWN, OR FLOODEDWITH
WATER OR LIQUID SOLUTION OF
ANY KIND. DO NOT USEWATER JET
TO CLEAN.
SEVERE DAMAGE OR
ELECTRICAL HAZARD
COULD RESULT.
WARRANTY BECOMES VOID IF
APPLIANCE IS FLOODED
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
5
P-2140 DIMENSIONS
33.10" (840.9mm)
53.00" (1345.6mm)
34.90" (886.4mm)
28.80" (730.8mm)
25.10"
(636.4mm)
30.00" (463.1mm)
22.10
"
(561.3mm)
7.69"
(195.3mm)
17.10
"
(434.0mm)
11.00"
(280.1mm)
2.20" (56.4mm)
18.90"
(480.3mm)
Cavity
22.13"
(562.0mm)
67.00" (1702.6mm)
5.50" (139.2mm)
25.20" (639.2mm)
26.90" (683.5mm)
Cavity 26.90" (683.5mm)
Cavity
72.50" (1841.8mm)
TIMER
11.00"
(280.1mm)
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
6
P-2145 DIMENSIONS
54.76" (1390.9 mm)
29.40" (746.8mm)
4.68"
(118.8mm)
4.10"
(104.0mm)
84.16" (2137.7mm)
0.58"
(14.8mm)
25.36" (644.1mm)
27.29" (693.2mm)
ON
OFF LOCK
TIME START STOP
TIMER
ON
OFF OVER
TEMP IRR INJ
LOCK
OVERTEMP
ERROR
0.96"
(24.3mm)
30.18" (766.7mm)
64.14" (1629.3mm)
70.92" (1801.4mm)
6.78"
(172.2mm) 26.53" (673.8mm)
Cavity
32.53" (826.2mm)
Cavity
14.84" (375.9mm)
Cavity
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
7
BLANKET CONTROL FEATURES
The following refers to features that are available when the
control is powered on. When an audible alarm is
referenced, the unit will only beep if the audible alarm
feature is selected.
CONTROL PANEL KEYS
ON/OFF KEY
Press the ON/OFF key to power on the control. Press and
hold the ON/OFF key for 2 seconds to power the control
off. The control will beep for one second when turned on
or off, and the status indicator light will illuminate
according to the power state.
UP ARROW / DOWN ARROW KEYS
Used to adjust the temperature set-point, current date and
time, as well as auto-start and auto-stop times.
TIMER KEY
Blanket warmers have a timer key which is used to
program the time of day, as well as the automated start
and stop times. To set the start and stop times, press and
hold the timer key for 2 seconds. See “Setting the Time”
instructions on this page.
L.E.D. DIGITAL DISPLAY
The control has a four-digit L.E.D. display. When the
control is activated, the display will show current
temperature set-point. When programming the timer, the
display will show hour and minutes.
L.E.D. DISPLAY STATUS INDICATORS
TIME
Illuminates while current time of day is displayed when
programming the TIMER mode.
START
Illuminates while the start time is displayed when
programming the TIMER mode.
STOP
Illuminates while the stop time is displayed when
programming the TIMER mode.
LOCK
Illuminates when the lock feature is engaged.
POWER FAIL DETECTION
If the power were to fail for any reason while heating, the
warmer will retain its current operating state in memory.
When the power is restored, the control will resume
operating, but several indicators will alert the operator
that such an event has occurred:
A. The ON/OFF status indicator will flash.
B. Display will indicate ‘128’ (or another number)
alternating with the setting. Please see important note
below if a number other than ‘128’ is displayed.
C. Control will beep until the power failure is
acknowledged.
Press the ON/OFF key once to acknowledge that the
power has been restored. The ON/OFF status indicator
will stop flashing and the “beep” will be silenced. The
display will indicate the approximate time period of the
outage, then return to the normal display and
previously set mode.
NOTE: The display of ‘128’ is a normal Power-On Reset
for the control. Any other number displayed may
indicate a problem. Make note of the number,
and if the unit fails to operate properly, provide
that number to service to assist them in
troubleshooting the problem.
TEMPERATURE FORMAT SELECTION
While the controller is in the off mode, press and hold the
UP ARROW key for 4 seconds to switch between
Fahrenheit or Celsius.
AUDIBLE ALARM SELECTION
While the controller is in the off mode, press and hold the
DOWN ARROW key for five seconds to switch between
audible alarm “ON” and “OFF” modes. When the audible
alarm is in the “OFF” mode, an audible alarm will still
sound if there is an OVERTEMP error, the door is left open
for more than 2 minutes, or in the event of power loss.
SETTING THE DATE AND TIME
NOTES: If you do not wish to use the automated timer
feature, then you do not need to set the date and
time and this section can be skipped. All times
will be displayed in hours and minutes (HH:MM)
in a 24-hour format. 1:00pm will display as
13:00. The clock will need to be manually reset
for Daylight Saving Time.
While the unit is off, hold the TIMER button for 2 seconds
to display the year (2000-2099). Adjust the year up or
ON
OFF
LOCK
TIME START STOP
L.E.D.
DISPLAY
STATUS INDICATOR L.E.D. UP ARROW
DOWN ARROW AUTOTIMER
KEY
ON / OFF
KEY
L.E.D. = LIGHT EMITTING DIODE
TIMER
THERMOSTAT CONTROL AND L.E.D. DISPLAY
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
8
BLANKET CONTROL FEATURES (CONTINUED)
down using the arrow buttons. Press the TIMER button
again to transition to the month and day (MM.DD).
Adjust the month and day up or down. Press the TIMER
button again to enter the time set mode. The current time
of day will show on the display in 24-hour format
(HH:MM). Adjust the time up or down. Press the TIMER
button again to transition to the Auto-On Time. The
currently programmed Auto-On time will show on the
display in 24-hour format. This is the time that the control
will automatically turn on when enabled. Adjust to desired
time. Press the TIMER button again to transition to the
Auto-Off Time. The currently programmed Auto-Off time
will show on the display. This is the time the control will
automatically turn off when enabled. Adjust to desired
time. Press the TIMER button again to enable the Auto-
Timer feature. The Time indicator light will turn on. To
disable, press and hold the TIMER key for 2 seconds and
the indicator light will turn off.
When adjusting the TIMER with the unit on, the year and
date will not be adjustable, and will start the
programming sequence with the current time of day.
NOTE: When the Auto-On Time and the Auto-Off Times are
equal, the unit will recognize the Auto-Off time ONLY
and the control will never turn on without user
intervention.
USING THE CONTROL LOCK
The warmer control can be locked so that no changes can
be made to the temperature set-point or the mode
selection. Press the ON/OFF key and the UP arrow key at
the same time. The LOCK indicator will illuminate.
Attempts to operate the ON/OFF key, or to change the
temperature set-point will be unsuccessful. To unlock the
warmer control, press the ON/OFF key and the DOWN
arrow button at the same time. The control will unlock
and the LOCK indicator will extinguish.
1. The appliance should be plugged into a
hospital grade, NEMA 5-20P receptacle
(120V) or an appropriate receptacle for a
230V appliance.
2. Turn on the power circuit breaker
switch, which is located at the back
of the appliance. It is a rocker-type
switch with international ON (I) and
OFF (O) markings.
3. ACTIVATE CONTROL BY PRESSING THE ON/OFF KEY
ON CONTROL PANEL ONCE.
The ON/OFF indicator will illuminate and remain lit
until the unit is turned off. The digital L.E.D. display
will indicate last temperature set-point of compartment.
4. SET DESIRED TEMPERATURE.
To set the blanket warming temperature, press and hold
the UP or DOWN ARROW keys to change the value
shown in the display. The temperature set-point range
is 98 - 200°F (37 - 93°C).
5. LOAD THE CHAMBER WITH 100% COTTON BLANKETS.
DO NOT WARM SYNTHETIC BLEND FABRICS OR ITEMS
CONTAINING PLASTIC, RUBBER OR METAL SNAPS,
STUDS, HOOKS, ETC.
Check that the epoxy-coated blanket support assembly
and shelf is in place. This blanket support assembly and
shelf MUST be used to hold blankets. A full load of
blankets will take 2-3 hours to reach optimum
temperature. Make certain the cabinet door is securely
closed after initial loading and following each blanket
removal.
Note: Do not block sensor by overloading cabinet
with blankets.
6. ROTATE LOAD OF BLANKETS DAILY.
Rotate the blankets at the bottom of the load to the top
to ensure equal usage. Failure to rotate blankets can
cause blankets to discolor.
Note: Avoid using flammable cabinet cleaning
agents, as well as blanket cleaning agents
that cause fabric to become brittle over
time.
POWER
CIRCUIT BREAKER
SWITCH
Load blankets only to
the top of the blanket support assembly.
BLANKET CHAMBER OPERATIONAL PROCEDURES
P-2140 Blanket
Warming Chamber P-2145 Blanket
Warming Chamber
CAUTION
BLANKET SUPPORT ASSEMBLY AND SHELF
MUST BE USED WHEN WARMING BLANKETS.
CAUTION
DO NOT OVERLOAD CABINET.
BLANKETS MUST NOT EXCEED HEIGHT OF
SUPPORT ASSEMBLY. ALLOW 1" GAP BETWEEN
LOWER BLANKETS AND MIDDLE SHELF.
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
9
CONTROL PANEL KEYS
ON/OFF KEY
Press and release the ON/OFF key to activate control. The
green indicator located at the top left of the ON/OFF key
will illuminate when the warmer is on. To turn the
warmer off, press and hold the ON/OFF key for 2 seconds.
UP ARROW / DOWN ARROW KEYS
These keys are used to increase or decrease the set-point
temperature as desired.
OVERTEMP ALARM KEY
Depressing this key displays the current over-temperature
trip-point. The alarm trip-point is always 10°F (6°C) above
the temperature setting. When the green overtemp
indicator is blinking, the warmer has entered an over-
temperature condition.
IRR KEY
The IRR key is used to select the Irrigation Fluids mode and
to display the IRR set-point temperature. The temperature
range is 98-150°F (37-66°C). The green IRR indicator
illuminates when in the Irrigation fluids mode. The yellow
indicator on the IRR key illuminates when the IRR set-point
temperature is being displayed.
INJ KEY
The INJ key is used to select the Injection Fluids mode and
to display the set-point temperature. The temperature
range is 98-110°F (37-43°C). The green INJ indicator
illuminates when in the Injection Fluids mode. The yellow
indicator on the INJ key illuminates when the INJ set-point
temperature is being displayed.
NOTE: In order to switch between the irrigation and
injection modes, you must first turn the unit off
and then turn the unit back on. Be careful to
properly cool the cavity down prior to switching
from a high temperature in IRRIGATION mode to
a much lower temperature in INJECTION mode so
that a false overtemp or E-31 overtemp alarm is
not tripped.
L.E.D. DISPLAY STATUS INDICATORS
ERROR
This illuminates when an over-temperature condition is
detected. The ERROR indicator will remain illuminated,
even after the over-temperature condition is cleared, until
the warmer is turned off. This will alert the operator that
the control has indicated an OVERTEMP.
OVERTEMP
When the control senses a temperature 10°F (6°C) greater
than the set point, this indicator will illuminate. An alarm
will also sound. The alarm can be muted by pressing any
key. This indicator will extinguish and the green indicator
of the overtemp key will stop blinking once the warmer
temperature drops back to the set point temperature.
POWER FAIL DETECTION
If the power were to fail for any reason while heating, the
warmer will retain in memory its current operating state.
When the power is restored, the control will resume
operating, but several things will alert the operator that
such an event has occurred:
A. The ON/OFF status indicator will be flashing.
B. Display will indicate ‘128’ (or another number)
alternating with the setting. Please see important note
below if a number other than ‘128’ is displayed.
C. Control will beep until the power failure is
acknowledged.
Press the ON/OFF key once to acknowledge that the
power has been restored. The ON/OFF status indicator
will stop flashing and the audible alarm will be silenced.
The display will indicate the approximate time period of
the outage, then return to the normal display and
previously set mode.
NOTE: The display of ‘128’ is a normal Power-On Reset
for the control. Any other number displayed may
indicate a problem. Make note of the number,
and if the unit fails to operate properly, provide
that number to service to assist them in
troubleshooting the problem.
TEMPERATURE FORMAT SELECTION
While the controller is in the off mode, press and hold the
UP ARROW key for 5 seconds to switch between
Fahrenheit or Celsius.
THERMOSTAT CONTROL AND L.E.D. DISPLAY
L.E.D. = LIGHT EMITTING DIODE
ON
OFF OVER
TEMP IRR INJ
LOCKOVERTEMP
ERROR
UP
ARROW
DOWN
ARROW STATUS INDICATOR L.E.D.
STATUS INDICATOR L.E.D.
INJECTABLES
MODE KEY
IRRIGATION
MODE KEY
OVERTEMP ALARM
KEY
ON/OFF
KEY
FLUID CONTROL FEATURES
DANGER
DO NOT use this warming cabinet in
the presence of flammable
anesthetic mixture (with air or with
oxygen or nitrous oxide).
THIS COULD RISK AN EXPLOSION!
L.E.D. DISPLAY
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
10
1. The appliance should be plugged into a hospital grade,
NEMA 5-20P receptacle (120V) or an
appropriate receptacle for a 230V appliance.
2. Turn on the power circuit breaker switch,
which is located at the back of the appliance.
It is a rocker-type switch with international
ON (I) and OFF (O) markings.
3. ACTIVATE CONTROL BY PRESSING THE
ON/OFF KEY ON CONTROL PANEL ONCE.
The ON/OFF indicator will illuminate and remain lit
until the unit is turned off. The digital L.E.D. display
will indicate last temperature set-point of
compartment.
4. SELECT DESIRED MODE OF OPERATION.
Press the IRR key to select the irrigation fluids mode or
the INJ key to choose the injection fluids mode. The last
set-point temperature for that mode of operation will
appear in the display.
NOTE: In order to switch between the irrigation and
injection modes, you must first turn the unit off
and then turn the unit back on.
5. SET DESIRED TEMPERATURE.
To set the fluid warming temperature, press and hold
the UP or DOWN ARROW keys to change the value
shown in the display. The irrigation fluids set-point
temperature range is 98-150°F (37° to 66°C) and the
injection fluids set-point temperature range is 98-110°F
(37-43°C).
NOTE: The warmer is designed to warm fluids to
appropriate temperature recommended by your
supplier. The warm-up stabilization time will
vary depending on the warmer load. Exercise
judgment to determine inventory rotation
protocols and warm-up time for the fluids you
use.
CAUTION:
• Check fluid temperature prior to use.
• Verify that the fan at the back of the chamber is
rotating freely. If it is not working, discard your
inventory, contact your service representative, and
discontinue use of unit until it is repaired.
• If the warmer control has failed, or if error messages
are displayed, discard your inventory and contact your
service representative.
• The unit may tip over if more than one drawer
is extended simultaneously. Open only one drawer
at a time when loading or unloading fluids.
AUDIBLE ALARM SELECTION
While the unit is off, press and hold the DOWN ARROW
key for five seconds to switch between audible alarm
“ON” and “OFF” modes. When the audible alarm is in
the “OFF” mode, an audible alarm will still sound if there
is an OVERTEMP error, the door is left open for more than
15 minutes, or in the event of power loss.
SETTING THE DATE AND TIME
While the unit is off, hold the OVERTEMP button for 2
seconds to set the year (2000-2099). Adjust the year up or
down using the arrow buttons. Press the OVERTEMP
button again to transition to the month and day
(MM.DD). Adjust the month and day up or down. Press
the OVERTEMP button again to enter the time set mode.
The current time of day will show on the display in 24-
hour format (HH:MM). Adjust the time up or down.
USING THE CONTROL LOCK
The warmer control can be locked so that no changes can
be made to the temperature set-point or the mode
selection. Press the ON/OFF key and the UP arrow key at
the same time. The LOCK indicator will illuminate.
Attempts to operate the ON/OFF key, or to change the
temperature set-point will be unsuccessful. To unlock the
warmer control, press the ON/OFF key and the DOWN
arrow button at the same time. The control will unlock
and the LOCK indicator will extinguish.
FLUID CHAMBER OPERATIONAL PROCEDURES
POWER
CIRCUIT BREAKER
SWITCH
P-2140 Fluid
Warming Chamber
P-2145 Fluid
Warming Chamber
CAUTION
INJECTION FLUIDS
SHOULD NOT BE WARMED
OVER 110°F (43°C)
WARNING
REFER TO FLUID MANUFACTURER’S
LABELING FOR RECOMMENDED
WARMING PROCEDURES
FLUID CONTROL FEATURES (CONTINUED)
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
11
CLEANING AND PREVENTIVE MAINTENANCE
PROTECTING STAINLESS STEEL SURFACES
It is important to guard against
corrosion in the care of stainless
steel surfaces. Harsh, corrosive,
or inappropriate chemicals can
completely destroy the protective
surface layer of stainless steel.
Abrasive pads, steel wool, or metal
implements will
abrade surfaces causing damage to this protective
coating and will eventually result in areas of corrosion.
Even water, particularly hard water that contains high to
moderate concentrations of chloride, will cause
oxidation and pitting that result in rust and corrosion.
In addition, many acidic spills left to remain on metal
surfaces are contributing factors that will corrode
surfaces.
Proper cleaning agents, materials, and methods are vital
to maintaining the appearance and life of this appliance.
Spilled items should be removed and the area wiped as
soon as possible but at the very least, a minimum of once
a day. Always thoroughly rinse surfaces after using a
cleaning agent and wipe standing water as quickly as
possible after rinsing.
CLEANING AGENTS
Use non-abrasive cleaning products designed for use on
stainless steel surfaces. Cleaning agents must be
chloride-free compounds and must not contain
quaternary salts. Never use hydrochloric acid (muriatic
acid) on stainless steel surfaces. Always use the proper
cleaning agent at the manufacturer's recommended
strength. Contact your local cleaning supplier for
product recommendations.
CLEANING MATERIALS
The cleaning function can usually be accomplished with
the proper cleaning agent and a soft, clean cloth. When
more aggressive methods must
be employed, use a non-
abrasive scouring pad on
difficult areas and make
certain to scrub with the
visible grain of surface metal
to avoid surface scratches.
Never use wire brushes, metal
scouring pads, or scrapers to
remove residue.
ANNUAL PREVENTATIVE MAINTENANCE
1. Ensure that the correct Operation and Care manual is
available to all users.
2. Ensure that all users have been properly trained in
unit’s operation.
3. Do not exceed the unit’s capacity.
4. Inspect condition of plug and cord. Replace if
damaged.
5. Clean dust from outer vents surrounding the unit and
around top of bonnet.
6. Check door gasket. Are there any tears? Is the gasket
worn or loose? Make sure seal is tight to unit body.
Replace gasket if integrity is compromised.
7. Check air temperature sensor mounted on the interior
of chamber. Is the metal guard in place? Are the wires
in good condition?
8. Check the blanket support assembly and shelf (if
applicable) Is the assembly in place? Are any pieces
missing?
9. Check basket and side rail condition (if applicable).
Do baskets move smoothly and freely?
10. check caster or leg condition. Ensure mounting
bolts and assembly is secure.
11. Check control panel overlay condition. Are there
any tears or excessive wear on the graphic? Does
control work properly when buttons are pushed?
12. Check that all control LEDs light up as applicable.
13. Is the Set Temperature comparable to the Actual
temperature
displayed? If not,
control needs
calibration. Call
Service.
Contact Service
for immediate
repair if any of
the above
problems exist.
CAUTION
TO PROTECT STAINLESS STEEL
SURFACES, COMPLETELY AVOID
THE USE OF ABRASIVE CLEANING
COMPOUNDS, CHLORIDE BASED
CLEANERS, OR CLEANERS
CONTAINING QUATERNARY SALTS.
NEVER USE HYDROCHLORIC ACID
(MURIATIC ACID) ON STAINLESS
STEEL. NEVER USE WIRE
BRUSHES, METAL SCOURING
PADS OR SCRAPERS.
N
O
S
C
R
A
P
E
R
S
N
O
W
I
R
E
B
R
U
S
H
E
S
N
O
S
T
E
E
L
P
A
D
S
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
12
CARE AND CLEANING
The cleanliness and appearance of this equipment will contribute considerably to its operating
efficiency. Make certain the cabinet and door gasket are kept free of any debris that may
accumulate. Good equipment that is kept clean works better and lasts longer.
CLEAN THE UNIT REGULARLY:
1. Disconnect the cabinet from the power source.
2. Remove all detachable items such as the metal basket and basket rail supports.
Clean these items separately.
NOTE: Avoid the use of abrasive cleaning compounds, chloride based cleaners, or cleaners containing
quaternary salts. Never use hydrochloric acid (muriatic acid) on stainless steel.
3. Clean the interior metal surfaces of the cabinet with a damp cloth and any mild commercial
detergent. Avoid the use of abrasive cleaning compounds. Rinse surfaces by wiping with sponge &
clean warm water. Remove excess water with sponge and wipe dry with a clean cloth or air dry.
Leave doors open until interior is completely dry.
4. Interior can be wiped with a sanitizing solution after cleaning and rinsing. This solution must be
approved for use on stainless steel surfaces. Replace blanket support assembly.
5. To help maintain the protective film coating on polished stainless steel, clean the exterior of the cabinet with a cleaner
recommended for stainless steel surfaces. Spray the cleaning agent on a clean cloth and wipe with the grain of the
stainless steel.
6. Clean the window glass with a standard commercial glass cleaner.
7. Wipe control panel, door vents, door handles, and door gaskets thoroughly since these areas harbor debris.
8. Wipe door gaskets and control panel dry with a clean, soft cloth.
Always follow appropriate state or local health (hygiene) regulations regarding all applicable cleaning and sanitation requirements.
9. To help maintain the protective film coating on polished stainless steel, clean the exterior of the cabinet with a cleaner
recommended for stainless steel surfaces. Spray the cleaning agent on clean closth a wipe with grain of the stainless steel.
(Listed as Ordinary Equipment.)
AT NO TIME SHOULD THE INTERIOR OR
EXTERIOR BE STEAM CLEANED, HOSED
DOWN, OR FLOODED WITH WATER OR
LIQUID SOLUTION OF ANY KIND. DO NOT
USE WATER JET TO CLEAN.
SEVERE DAMAGE OR ELECTRICAL HAZARD
COULD RESULT.
WARRANTY BECOMES VOID IF APPLIANCE IS FLOODED.
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
13
TROUBLE SHOOTING GUIDE
ERROR DESCRIPTION ACTION REQUIRED
E-10 Sensor Short • Detach the sensor from the terminal block. Use an Ohm meter to measure the resistance of
the sensor. Check sensor at 32°F (0°C) using a container of ice water.
If Ohm reading is 100, replace display. If Ohm reading is ±10, replace sensor.
• Check wires for integrity. Check for proper and secure connections at the control and
terminal block. If necessary, re-secure the faulty connections.
• If error continues call Service.
E-11 Sensor Open • Detach the sensor from the terminal block. Use an Ohm meter to measure the resistance of
the sensor. Check sensor at 32°F (0°C) using a container of ice water.
If Ohm reading is 100, replace display. If Ohm reading is ±10, replace sensor.
• Check wires for integrity. Check for proper and secure connections at the control and
terminal block. If necessary, re-secure the faulty connections.
• If error continues call Service.
E-30 Under Temp Error
(Blanket warmers only)
• Blanket chamber temperature has been lower than the set temperature for 90 minutes or longer.
• Check that door is closed.
• Verify that the high limit switch located at the rear of the unit has not been tripped. If it has been
tripped, reset by pressing in the limit reset button. After resetting, the cause of the high limit trip
must be corrected. If the high limit switch will not reset, the high limit switch is defective and
must be replaced. This is a safety device and must not be jumped out or removed from the
circuit.
E-31 Over Temp • Unit may be overloaded. Redistribute inventory. Do not exceed height of basket assembly.
• Check sensor at 32°F (0°C) using a container of ice water. The sensor reading should be
100 ohms.
• Relay (solid state) may be defective.
• Control may have defective temperature circuit.
• If error continues call Service.
E-60 Real-Time Clock Checksum Error • Unit may have been unplugged for an extended period of time.
• To resolve, turn circuit breaker switch to ON position for 1 minute, then turn circuit breaker
switch to the OFF position for 5 seconds, and then back to ON. The error message should no
longer appear in the display.
• In order for the unit to fully recharge, it should remain plugged in and power circuit breaker
switch turned ON for at least 24 hours after resetting.
• Upon resolving an E-60 error, check that the date and time are correct.
E-80 EPROM Data • Call Service.
E-81 Calibration Values Out of
Expected Range
• Call Service.
E-82 Calibration Data Error • Call Service.
E-99 Hardware Over Temp • Inspect connections and condition of high limit bimetal thermostat.
• If error continues call Service.
DANGER
DISCONNECT UNIT FROM
POWER SOURCE BEFORE
CLEANING OR SERVICING.
If your unit is not operating properly, check the following before calling your authorized service agent. Check the power
applied to the unit. Is the plug in outlet? Is the power circuit breaker switch in rear of unit OK? Has the high limit
manual reset tripped? If so, reset. (See “Manual Reset Instructions” below.)
If temperature calibration adjustment is required, call Enthermics Service for proper instruction.
Do not attempt to repair or service beyond this point. Contact manufacturer for nearest authorized service agent.
Repairs made by any other service agent without prior authorization by manufacturer will void the warranty on the unit.
This chart is provided for the assistance of qualified technicians only and is not intended for use by untrained or
unauthorized service personnel.
NOTE: All error codes must be cleared using the circuit breaker switch or power cord on the rear of the unit.
Manual Reset Instructions: Locate the manual reset button on back of unit. Using a pen, screwdriver or other long, thin
implement, firmly push reset button. You will hear an audible click when the button is reset. If reset button trips again while
unit is running, contact a qualified service technician. Manual reset button Circuit breaker
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
15
Service View of P-2140
PE-26912
CONTROL PANEL
OVERLAY
5001253
WINDOW DOOR
ASSEMBLY, RH
HD-24171
DOOR HANDLES
GS-23794
DOOR GASKET
ASSEMBLY
CS-24875
CASTERS,
5” (127mm) SWIVEL
WITH BRAKE
GI-25942
DRAWER
SLIDE GUIDE
SH-25908
BLANKET
SUPPORT
ASSEMBLY
5001253
WINDOW DOOR
ASSEMBLY, RH
GS-23794
DOOR GASKET
ASSEMBLY
SN-33541
SENSOR
5002972
BASKET SUPPORT
ASSEMBLY
SH-25911
BLANKET
SHELF HG-22338
HINGES
5004206
LAMP GUARD
ASSEMBLY
HG-22338
HINGES
BS-26690
BASKETS
SN-33541
SENSOR
5003357
FULL-PERIMETER
RUBBER BUMPER
ASSEMBLY
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
16
Service View of P-2140
SW-33858
CIRCUIT BREAKER
SWITCH
CC-34423
CONTROL ASSEMBLY
BK-3019
TERMINAL BLOCK
RL-34434
RELAY, 12V
DC, COIL
BP-3567
BEEPER
RL-33829
RELAY, 230V
BA-34596
POWER SUPPLY
BOARD
RL-34434
RELAY, 12V
DC, COIL
E3029CD
CORDSET,
HOSPITAL GRADE
BU-3964
STRAIN RELIEF
BUSHING
CR-33717
CONNECTOR, 10 PIN
CR-33763
CONNECTOR, 4 PIN
CR-33718
CONNECTOR, 9 PIN
CC-34423
CONTROL ASSEMBLY
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
17
Service View of P-2140
CS-24874
CASTERS,
5” (127mm) RIGID
5003418
CORD GRIP
ASSEMBLY
FA-3973
BOX FAN
5003357
FULL-PERIMETER
RUBBER BUMPER
ASSEMBLY
SW-33858
CIRCUIT BREAKER SWITCH
E3029CD
CORDSET,
HOSPITAL GRADE 05/05
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
18
P-2140 Wiring Diagram
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
20
PE-26912
CONTROL PANEL
OVERLAY
5001899
DOOR, FLUID
CHAMBER
HD-24171
DOOR HANDLES
CS-24875
CASTERS,
5” (127mm) SWIVEL
WITH BRAKE
GI-26237
DRAWER
SLIDE GUIDE
IS-27242
BLANKET
SUPPORT
ASSEMBLY
GS-26321
DOOR GASKET
ASSEMBLY, UPPER
CS-24874
CASTERS,
5” (127mm) RIGID
IS-27272
FLUID INSERT
ASSEMBLY
1003115
BLANKET
SHELF
Service View of P-2145
GS-26892
DOOR GASKET
ASSEMBLY, LOWER
IS-27271
BASKET ASSEMBLY,
FLUID METAL
Pedigo P-2140 & P-2145 Fluid & Blanket Warming Combination Cabinet Operation and Care Manual
21
SN-33540
SENSOR
1493
SENSOR
GUARD
5004206
LAMP GUARD
ASSEMBLY
(BLANKET CHAMBER)
LP-33268
BULB ONLY
LP-33267
LAMP
ASSEMBLY
GI-26237
DRAWER SLIDE
GLIDE
Service View of P-2145
5002359
BASKET
ASSEMBLY,
FLUID METAL
5002359
BASKET
SUPPORT
ASSEMBLY

Other manuals for P-2140

1

This manual suits for next models

1

Other Pedigo Medical Equipment manuals

Pedigo 500 Operating manual

Pedigo

Pedigo 500 Operating manual

Pedigo 500 User manual

Pedigo

Pedigo 500 User manual

Pedigo ivNow Series User manual

Pedigo

Pedigo ivNow Series User manual

Pedigo P-172 User manual

Pedigo

Pedigo P-172 User manual

Popular Medical Equipment manuals by other brands

Sirona SIROLaser Advance operating instructions

Sirona

Sirona SIROLaser Advance operating instructions

Mollii Jacket user manual

Mollii

Mollii Jacket user manual

KaVo ESTETICA E70 Vision Care Instructions

KaVo

KaVo ESTETICA E70 Vision Care Instructions

Gaumard S230.7 user guide

Gaumard

Gaumard S230.7 user guide

Olsen VERSATILE user manual

Olsen

Olsen VERSATILE user manual

VISIOMED Baby Doo Cleaner MX6-ONE user manual

VISIOMED

VISIOMED Baby Doo Cleaner MX6-ONE user manual

BOLD T20 manual

BOLD

BOLD T20 manual

EKOM DK50 2V S INSTALLATION, OPERATION AND MANTENANCE MANUAL

EKOM

EKOM DK50 2V S INSTALLATION, OPERATION AND MANTENANCE MANUAL

Accu-Chek Combo Training handbook

Accu-Chek

Accu-Chek Combo Training handbook

Graham Field intensa IN587W Series Assembly and operating instructions

Graham Field

Graham Field intensa IN587W Series Assembly and operating instructions

capsule SmartLinx Axon Series Instructions for use

capsule

capsule SmartLinx Axon Series Instructions for use

WeGo HYBRID user manual

WeGo

WeGo HYBRID user manual

Atmos Chair Comfort operating instructions

Atmos

Atmos Chair Comfort operating instructions

Microlife NEB 10 instruction manual

Microlife

Microlife NEB 10 instruction manual

baxter AK 98 Quick reference guide

baxter

baxter AK 98 Quick reference guide

C-Pro Direct ADM Fittings guide

C-Pro Direct

C-Pro Direct ADM Fittings guide

Roche CoaguChek XS Plus Operator's manual

Roche

Roche CoaguChek XS Plus Operator's manual

Weinmann OXYMAT 3 Servicing and Repair Instructions

Weinmann

Weinmann OXYMAT 3 Servicing and Repair Instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.